FIRST POWER UP
Other than below procedure, no configuration is needed. The battery configuration is
automatically recognized.
6.1
Power up procedure
1.
Make sure that all energy consumers are switched off before starting up the
system.
2.
The Lynx Ion + Shunt will pre-charge the system before closing the safety
contactor. The Lynx Ion + Shunt will not start if there is more than 10A drawn by
the system during pre-charging.
3.
Press the START-button on the front of the Lynx Ion + Shunt to start the system.
4.
Now the system is being pre-charged. The safety contactor is closed as soon as
the voltage rises above 80% of the battery voltage.
5.
If the status LED is continuously on, then the system is running and ready for use.
6.2
Power down/reset procedure
Lynx Ion +Shunt to standby mode:
1.
Press and hold the START-button until the Lynx Ion goes into standby mode
(status LED off).
2.
Now the safety contactor is open and the batteries are disconnected from the
system.
Reset Lynx Ion + Shunt from error state:
1.
Press the START-button for 1 sec.
2.
The system will now restart.
6.3
Automatic power-up
The Lynx Ion + Shunt will automatically power-up from standby if a charge voltage on the
output is supplied for more than 10 seconds.
Содержание Lynx Ion + Shunt 350
Страница 1: ......
Страница 2: ......
Страница 4: ......
Страница 9: ......
Страница 10: ......
Страница 12: ......
Страница 14: ......
Страница 15: ......
Страница 17: ...4 Configure the Lynx Ion BMS Support assistant as follows ...
Страница 23: ......
Страница 24: ...Front view I G H J ...
Страница 25: ......
Страница 28: ......
Страница 29: ...Distributor Serial number Version 1 Date 10 June 2014 ...