Victron energy Hub-4 Скачать руководство пользователя страница 9

2020-12-11 00:44

9/13

Hub-4 / grid parallel - manual DEPRECATED

Victron Energy - https://www.victronenergy.com/live/

6. Battery charging and discharging behavior

(Note: All absolute voltages mentioned in the text below are for a 12V system and should be
multiplied by 2 or 4 for a 24V or 48V system.)

When there is less PV power available than needed by the loads (a PV shortage), energy stored
in the battery will be used to power the loads until the battery is considered empty. There are
three parameters that check if the Battery is empty:

Battery State of Charge. Minimum state of charge is configured in the Hub-4 Assistant.

1.

Battery Voltage. See Dynamic Cut-off section below.

2.

Low cell signal from BMS

3.

When the battery is empty, the Sustain mode is activated. See Sustain section below.
Whenever there is excess PV, the battery will be charged. Charge current and other parameters
are configured on the Charger tab in VEConfigure3.
The Hub-4 Assistant will disable PowerAssist. Please keep this option disabled.
Make sure to keep the lithium batteries checkbox on the charger page consistent with the
battery choice in the Assistant.

Sustain Mode

The purpose of the Sustain Mode is to prevent battery damage caused by leaving batteries in a
deeply discharged state. The Sustain Mode is entered as soon as the battery is discharged, see
above.

During Sustain Mode, the batteries will slowly be charged from the grid; maximum charge current is 5
Ampére. The Sustain level is 12.5V for lithium batteries. For non-lithium batteries, the sustain level is
11.5 V for the first 24 hours, and after that it is raised to 12.5 V.

Excess solar power will also be used to charge the batteries. Sustain stops as soon as there has been
sufficient excess solar power available to raise the battery voltage 0.1 V above the sustain level.
Normal operation will then continue: solar deficits are complemented with power from the battery
again.

Dynamic Cut-off

Note: dynamic cut-off is useful for batteries with a high internal resistance. For example OPzV and
OPzS. Less relevant for LiFePO4 batteries, see graph.

With Dynamic Cut-off, the dc-low-disconnect level is a function of the battery current drawn from the
battery. When a high current is being drawn from the battery, a lower DC cut-off voltage threshold is
being used, for example 10 V. And similarly, when the battery is only being discharged slowly, a high
DC cut-off voltage is used, for example 11.5 V.

This way, voltage drop caused by battery internal resistance is being compensated for, and battery
voltage can reliably be used to stop discharging when the battery is discharged.

The picture below shows the default 'Discharge' vs. 'DC input low shut-down voltage' curve for the
different battery types. The curve can be adjusted in the assistant.

Содержание Hub-4

Страница 1: ...gy is stored in the battery And that stored energy is then to power the loads at times when there is a shortage of PV power The system is managed by the Color Control GX CCGX which also provides exten...

Страница 2: ...bility is given to implement time shifting load management or other energy management optimization algorithms Either by ModbusTCP commands or by running additional self implemented code on the Color C...

Страница 3: ...ample the EM24DINAV53DISX which uses Current Transformers and can therefore work in systems 63A per phase Note that this model is not stocked by Victron Energy we recommend to purchase it locally 2 Ba...

Страница 4: ...nly one phase and compensate on that phase for the other two phases thereby e ectively regulating the total power of all three phases combined See the following example where the Hub is connected to L...

Страница 5: ...sate for the shortage Multis on phases with a net power production will be on idle Disabling phase compensation In a hub 4 system it is still possible to balance the grid power of each phase to 0W Dis...

Страница 6: ...ww victronenergy com live Printed on 2020 12 11 00 44 single phase setup diagram Note the jumper between terminals 1 and 4 Meter con guration Change the front selector of the AC sensor so it is not in...

Страница 7: ...USB converter to the CCGX using the supplied USB cable A few seconds after connecting the active LED should be on and the TX RX LED should be blinking the converter takes its power from the CCGX so th...

Страница 8: ...onverter Grid meter Yellow Terminal 41 Orange Terminal 42 Black Terminal 43 The Red Green and Brown wire are not used 5 Multi Quattro installation and con guration First follow the instructions as per...

Страница 9: ...entered as soon as the battery is discharged see above During Sustain Mode the batteries will slowly be charged from the grid maximum charge current is 5 Amp re The Sustain level is 12 5V for lithium...

Страница 10: ...he display will come to life If not check the wiring of the system 2 Within 60 seconds after power up the CCGX will detect the meter The meter will show up in 3 the device list on the display When sel...

Страница 11: ...sing terminals 3 6 and 9 Now you can chose on which phase you want the PV inverter by connecting the L1 line of the PV inverter to terminal 1 4 or 7 There are 3 options to connect the extra AC sensor...

Страница 12: ...sensor to measure both grid and PV inverter For wiring see the diagram below On the CCGX go to the grid meter in the Wired AC sensor settings Make sure Phase type is set to Single phase and PV invert...

Страница 13: ...n xxyy403 I get a lot of Low battery pre alarm warnings Solved by updating to xxyy403 or higher Does Hub 4 work for parallel systems Yes Hub 4 works for systems where multiple Multis or Quattros are i...

Отзывы: