13
F01 : Battery capacity in Amphours (Ah). This must be the capacity
at a 20h discharge rate and 20
°
C.
Default : 200Ah
Range : 20 – 2000Ah
Stepsize : 1Ah
F02 : Voltage-charged-parameter. The battery voltage must be
above this voltage level to consider the battery as fully
charged. Make sure the voltage-charged-parameter is always
slightly below the voltage at which the charger finishes
charging the battery (usually 0.1V or 0.2V below the ‘float’
stage voltage of the charger).
Default : 13.2V
Range : 8.0 – 33.0V
Stepsize : 0.1V
F03 : Current-charged-parameter. When the charge current value is
below this percentage of the battery capacity (see F01), the
battery can be considered as fully charged. Make sure the
current-charged-parameter is always greater than the
minimum current at which the charger maintains the battery,
or stops charging.
Default : 2.0%
Range : 0.5 – 10.0%
Stepsize : 0.5%
F04 : Charged-parameter-time. This is the time the charged-
parameters (as described in F02 and F03) must be met, in
order to consider the battery as fully charged.
Default : 4 minutes
Range : 1 – 4 minutes
Stepsize : 1 minutes
F05 : Low-battery alarm ON (discharge floor). When the state-of-
charge percentage has fallen below this value, the alarm relay
will be activated and the
CHARGE BATTERY
indication will
flash on the display to indicate the battery must be charged.
The time-to-go calculation is also linked to this value. It is
recommended to keep this value at or around
50.0%
.
Default : 50.0%
Range : 0.0 – 99.0%
Stepsize : 1.0%
Содержание BMV-501