4
The charging programs:
MODE
ABS
V
FLOAT
V
STORAGE
V
RECONDITION
Max V@% of Inom
NORMAL
14,4
13,8
13,2
16,2@8%, max 1h
HIGH
14,6
13,8
13,2
16,5@8%, max 1h
LI-ION
14,2
13,35
13,35
n. a.
Notes:
a. For 24 V chargers: multiply all values by 2.
b.The absorbtion duration depends on how deep the battery was
discharged. Maximum duration: 8 hours.
c. RECONDITION is applicable to the NORMAL and HIGH
settings only.
d. During RECONDITION the max current is equal to the stated
% of the nominal current until the max voltage is reached.
Example for a 12/15 charger: the recondition current is
15 x 0,08 = 1,2 A.
The recondition LED will blink during recondition mode.
4. Technical specifications
Notes:
a. Temperature compensation: - 2 mV/°C per cell (lead acid only).
(
Measures ambient temperature during the charge/test phase and
compensates for temperature during absorption. Measures
temperature again when in low current mode during float or
storage)
b. The charger will start a new charge cycle during step 5 or 6 if,
due to a load, it switches to maximum current mode during more
than 4 seconds.
A new charge cycle can also be initiated by pressing the mode
button.