5. CONFIGURATION
•
Settings may only be changed by a qualified electrical engineer.
•
Read the instructions thoroughly before implementing changes.
5.1 Standard settings: ready for use
On delivery, the Phoenix Inverter is set to standard factory values. In general, these
settings are suitable fo stand-alone operation.
Standard factory settings
Inverter frequency
60Hz
Inverter voltage
120VAC
Stand-alone / parallel / 3-phase
stand-alone
AES (Automatic Economy Switch)
off
Programmable relay
alarm function
5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further
information, please refer to the help files in the software configuration programs (see
Section 5.3).
Inverter frequency
Output frequency
Adjustability: 50Hz; 60Hz
Inverter voltage
Output voltage of the Inverter.
Adjustability: 95 –128V
Stand-alone / parallel operation / 2-3 phase setting
Using several devices, it is possible to:
•
increase total inverter power (several devices in parallel)
•
create a 3-phase system.
To this end, the devices must be mutually connected with RJ45 UTP cables.
Standard device settings, however, are such that each device operates in stand-alone
operation. Reconfiguration of the devices is therefore required.
AES (Automatic Economy Switch)
If this setting is turned ‘on’, the power consumption in no-load operation and with low
loads is decreased by approx. 20%, by slightly 'narrowing' the sinusoidal voltage.
The AES Mode can be set with a DIP switch.
Applicable in stand-alone configuration only.
Содержание 12 120V
Страница 1: ...Manual EN Appendix Phoenix Inverter with firmware xxxx1xx 12 3000 120V 24 3000 120V ...
Страница 2: ......
Страница 4: ......
Страница 25: ...EN Appendix APPENDIX B Block diagram See table in chapter 4 2 Recommended DC fuse ...
Страница 26: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Страница 27: ...EN Appendix APPENDIX G Dimensions ...
Страница 28: ...Dimensions 3k cabinet ...
Страница 29: ......