Wiring Instructions 

 

  

 

Notes On Advanced Settings 

1. 

Temp calibration: Calibrate the temp detected by room sensor or 

floor sensor. 

2. 

Anti-frozen function: This option allows you to prevent your room 

freezing in really cold weather. 

3.

 

Sensor select: 

Room sensor: Run by room sensor. Floor sensor: Run by floor sensor. 

Both sensors: Run by room sensor with floor temp limit. 

4.

 Floor temp limit: Always use floor sensor for underfloor heating. 

5.

 Temp unit: °C and °F can be selected. 

6.

 Output delay: This option help you avoid inadvertent operation on 

heating. 

7.

 Temp tolerance: The value is 1°C. The thermostat starts to heat when 

the actual temp is 1°C lower than set temp and stops heating when the 
actual temp is 1°C higher than set temp. 

8.

 Brightness: This option allows you to change the brightness of the 

display. 

9.

 Energy use: N/A. 

10. 

Schedule: Select a weekly schedule to edit. There are 2 options: 

7: each day from Mon to Sun can be set individually. 
5+1+1: 5 days from Mon to Fri have the same events, Sat and

 Sun can 

be set individually. 

11. 

Adaptive function: After several days of installation and 

use, Adaptive function ensures that the required temp has 
already been reached when the next event begins. Only 
switch on when regular heating pattern is established. 

12. 

Reset: Yes - All parameters are restored to default values. 

Installation Instructions 

 

This Timerstat should only be wired by a ‘Part P’ qualified 

Electrician as required by IEE regulations.

 

The power supply 

must be on an RCD protected circuit and connected via a 
correctly fused switched fused spur isolator. Guarantee is void if 
these provisions are not followed. 

Before connecting, please test the resistance of the heating 

cable/s against the values shown in the relevant installation 
manual to make sure the cable h

asn’t been damaged. Also test 

between live/earth and neutral/earth for a zero reading. Check 
the floor probe resistance is in the range of 10K Ohms 

 

The ET-81 timerstat should be mounted using an 86x86x35mm 
deep wall box. 
Loosen the silver fixing screw on the bottom of the timerstat and 
separate the front from the back. 
Wire the timerstat back section as the above diagram. A 
maximum of 2 heating cables will go into the wire connectors. 
More than this should be connected into a junction box with a 
single correctly sized wire to the timerstat. Main

s earth and 

heating cable earth should be connected behind the timerstat 
using a block connector. 

Don’t forget 

to connect the floor probe 

(not polarised) otherwise the timerstat will not work properly.  
Reassemble the front to the back and ensure the pins are located 
in the socket on the back otherwise it will not work and tighten 
up the

 silver screw. 

 
 
 

 