background image

05.2020 

 

 

INSTRUCTION MANUAL 

for installation and operation of pellet boiler

 CLASSIC 40C

 

 

 

29

 

 

WARRANTY CONDITIONS 

Trained  and  competent  persons  or  organizations  in  accordance  with  this  instruction  for  installation  and  operation 
must perform installing a pellet boiler and heating system. The manufacturer shall ensure proper and safe operation 
of the pellet boiler only in accordance with these requirements! 

The  warranty  period  of  the  pellet  boiler  is  24  (twenty  four)  months  from  the  date  of  installing,  but  not  more  than thirty  (30) 
months  from  the  date  of  sale,  on  the  condition,  that  they  meet  all  requirements  for  proper  transportation,  installation, 
commissioning and periodic maintenance. The warranty period of the ignition is six (6) months from the date of installing. The 
warranty period is interrupted for the time of filing the complaint to-repair. In bringing a claim must be presented commercial 
invoice and warranty card in the originals. Failing that provided, the claim is not accepted as valid and the buyer pays repair. 

On the territory of Bulgaria the term of the removal of the claim is up to three (3) days for settlements in which Victoria-05 Ltd. 
has  a  contract  with  distributors  (list  available  at 

http://v05.bg

)  and  10  (ten)  days  of  the  remaining  population.  For  other 

countries, please, contact you dealer. Any warranty repair of the pellet boiler is recorded in the diary of warranty. 

Warranty of the pellet boiler is NOT VALID in the following cases: 

-

 

Quickly worn out components: glass, seal, fire-grate, paint, insulation materials; 

-

 

Damages caused by improper transportation, handling and storage activities, not organized by the Victoria-05 Ltd; 

-

 

Do  not  met  the  requirements  for  installation,  putting  into  operation  and  periodic  maintenance,  specified  in  this 
instruction manual; 

-

 

Use of inappropriate fuel such as size, composition, moisture content and calorific value; 

-

 

Incorrect heat engineering calculations and a project for installation of pellet boiler; 

-

 

An attempt to repair the damage by the buyer or other incompetent persons; 

-

 

Made changes in the design of the pellet boiler; 

-

 

For damage caused by outside interference and intervention, weather conditions, electric shocks, natural disasters, 
fire, malfunctions in the electrical network and others that Victoria-05 Ltd bears no guilt and no control over them; 

 

WARRANTY CARD 

Condition for validity of warranty of pellet boiler is the warranty card to be completed legibly, signed and stamped! 

Date of production 

……………….... 

202

…….. 

 

Factory № 

…………………………..…………………. 

Quality control 

……………...………………… 

(stamp) 

Pellet boiler is delivered in proper condition to the buyer 

………………………………………………………………………………………………………………………………………………………..…………………………………………………………………………………………………………………………………………….....……………………………………

 

(name and last name) 

town 

………………………………………………………..….……………………...

, area code 

………………………………………….………………….. 

street 

…………………..…………………………………………………………….……………, 

………………. 

 

Dealer

…………………………………………….............................................................................................………………………….……….. 

Company 

………………………………………………………………………………………..……….………………….. 

          (name and last name)   

 

 

 

 

 

(name)   

town 

………………………………………………………..….……………………...

, area code 

………………………………………….………………….. 

street 

…………………..…………………………………………………………….……………, 

………………. 

 

Invoice № 

………………………………..……….. 

Date 

……………………………….

 

 

 

BUYER

……………………………………………....………………. 

INSTALLER

………………………………….…………………….  

 

              (signature)   

 

 

 

 

 

 

 

      (signature) 

 

 

Содержание CLASSIC 40C

Страница 1: ...INSTRUCTION MANUAL for installation and operation of pellet boiler CLASSIC 40C...

Страница 2: ...11 2 CONTROL PANEL DESCRIPTION 13 11 2 1 MAIN USER CONTROL PANEL 13 11 2 2 TYPES OF MODES OF THE CONTROL UNIT 14 11 2 3 MAIN MENU 14 11 2 5 SERVICE TECHNICIAN SETTINGS 18 12 INSTRUCTION MANUAL 19 12...

Страница 3: ...act with fire or hot surfaces Pellet boiler is equipped with safety components that guarantee automatically shut down in case of failure of any of its components Safety components are activated withou...

Страница 4: ...hould not be placed back in the pellet fuel hopper 3 Technical data and dimensions Fig 1 Button with safety cover to reset the thermo limiter Main switch with integrated socket for power cable out for...

Страница 5: ...construction of the pellet boiler allows mounting of the ashtray in left side or right side 1 1 1 Pellet boiler 2 Bracket 3 Screw 6 12 DIN 912 2 pcs 4 Washer 6 DIN 125 6 pcs 5 Screw 6 x 16 DIN 912 2 p...

Страница 6: ...ximum draught 12 Duration of combustion at nominal heat output at reduced heat output 14 h 47 h Fuel consumption minimum maximum 2 56 8 51 Type and dimensions of fuel Wood pellets 6 mm length 25 mm cl...

Страница 7: ...tat of the pellet fuel hopper Placed on the auger housing near the pellet fuel hopper It interrupts feeding of the pellets if its temperature reaches 85 C also interrupts the indication of the water t...

Страница 8: ...er works with wood pellets These are cylindrical granules made of pressed wood whose combustion is controlled by an electronic control system The heat from the combustion process is given to the fluid...

Страница 9: ...ts can cause blockage of the auger and to stop the operation of the pellet boiler IF PELLET BOILER IS BLOCKED THE REASON WILL APPEAR ON THE DISPLAY AND IT WILL BE SAVED Using wood pellets of poor qual...

Страница 10: ...t wind Chimneys Pellet boiler works constantly with a fume extractor and pressure in the flue pipes and chimney It is forbidden the flue gases to be discharged directly from the pellet boiler through...

Страница 11: ...volume ensures good and smooth operation of the appliance and Pellet boiler MUST NEVER OPERATE without liquid in the heating system and under pressure less than 1 bar Failure to comply with these con...

Страница 12: ...with the standard circulation pump and at the same time to keep the same level of power output and performance The pump operates on the principle of proportional pressure Technical data Max pumping 6...

Страница 13: ...g the coating The flavor which is obtained as a result of the drying of the paint disappears after a few hours Ventilate the room where is located the pellet boiler If as a result of overheating or du...

Страница 14: ...he icon would start the screw conveyor for 10 seconds When this time is over the screw conveyor stops again and waits until a new icon click is done The icon would only be visible in Ready Mode wherea...

Страница 15: ...re one can set the Upper Buffer Bumper Sensor and the Lower Buffer Bumper Sensor operation temperature hermostat The Indoor Sensor can be either switched on or off Note It is possible that this settin...

Страница 16: ...three options The first one is Switch the Timer ON If set active the fireplace would automatically transfer to Timer Mode The second one is Delayed Start To set this one active it is important that th...

Страница 17: ...rst level is Installer The second level is Service Technician The third level is Delete Errors with a password 7777 The fourth password is 2468 and serves to unlock the display The display can be lock...

Страница 18: ...erature On Here one can set the Water Temperature which the pump switches on at 45 0 C Hysteresis 2 C 10 C This is the thermal lag at which the pump will stop operating I e if it has been set ot switc...

Страница 19: ...is way one can calculate the amount of pellets after which there should follow a cleaning process 1800 sec Fan 100 How long an Interim Purge will last The time is set within the range of 2 to 100 seco...

Страница 20: ...chamber If necessary the cleaning time and power output can be adjusted in menu Cleaning When the time is over the device transfers to Fuel Mode In this mode there is a countdown as well The screw co...

Страница 21: ...t one is for the Time Clock which has been preset to 600 seconds to run out and only after that the water heater temperature is checked to have decreased down below the preset one these two events hav...

Страница 22: ...ition system Clean and check the electronic control system Check all electrical cables Clean the pellet fuel hopper and check auger to loosen the screw and the gear motor Check and if needed replace t...

Страница 23: ...e has to drop below this value Unsuccessful Ignition Failed ignition The alarm is shown if during operation of the stove the fume outlet sensor detects lower than the set temperature When the alarm is...

Страница 24: ...on manual What is needed to prepare and do before installing the pellet boiler Chimney with a diameter of at least 100 mm Opening for fresh air with a cross section not less than 80 cm 2 1 1 4 connect...

Страница 25: ...ure in the heating system is reached The installer must make the appropriate setting How often should you clean the combustion chamber Before each ignition of the pellet boiler but only when it is tur...

Страница 26: ...05 2020 INSTRUCTION MANUAL for installation and operation of pellet boiler CLASSIC 40C 26...

Страница 27: ...allowed penetration of foreign substances in the firebox or hopper Do not use combustible materials to clean soot in the chimney Turn off the pellet boiler from the grid circuit before cleaning or ser...

Страница 28: ...hot water outlet 9 Electronic control system set 10 Control panel 11 Circulation pump WITA DELTA MIDI 60 32 180 12 Glass 4 x 100 x 100 mm 13 Combustion chamber retort set 192 00 14 00 14 Handle 15 Fir...

Страница 29: ...g population For other countries please contact you dealer Any warranty repair of the pellet boiler is recorded in the diary of warranty Warranty of the pellet boiler is NOT VALID in the following cas...

Страница 30: ...05 2020 INSTRUCTION MANUAL for installation and operation of pellet boiler CLASSIC 40C 30 DIARY for repairs under warranty Company Receipt date Type of repair Delivery date Carried out...

Страница 31: ...05 2020 INSTRUCTION MANUAL for installation and operation of pellet boiler CLASSIC 40C 31...

Страница 32: ...NUAL for installation and operation of pellet boiler CLASSIC 40C 32 Victoria 05 Ltd 1B Ivan Momchilov Str 5100 Gorna Oryahovitsa Republic of Bulgaria phone 359 618 60282 fax 359 618 60200 e mail info...

Отзывы: