www.tolco.com
Fig. 1001 - Sway Brace Attachment
Size Range
— Pipe size to be braced: 2
1
⁄
2
” thru 8” IPS.* Pipe size used
for bracing: 1” and 1
1
⁄
4
” Schedule 40 IPS.
Material
— Carbon Steel
Function
— For bracing pipe against sway and seismic disturbance. The
pipe attachment component of a sway brace system: The Fig. 1001 is
used in conjunction with a TOLCO 900 Series fitting and joined together
with bracing pipe per NFPA 13, forming a complete sway brace assembly.
Features
— Can be used to brace schedules 7 through 40 IPS. Field
adjustable, making critical pre-engineering of bracing pipe length unneces-
sary. Unique design requires no threading of bracing pipe. Can be used as
a component of a four-way riser brace. Comes assembled and ready for
installation. Fig. 1001 has built-in visual verification of correct installation.
See installation note below.
Installation Note
— Position Fig. 1001 over the pipe to be braced and
tighten two hex head cone point set bolts until heads bottom out. A mini-
mum of 1” pipe extension is recommended. Brace pipe can be installed on
top or bottom of pipe to be braced.
Approvals
— Underwriters Laboratories Listed in the USA
(UL)
and
Canada
(cUL)
. Approved by Factory Mutual Engineering
(FM)
.Included in
our Seismic Restraints Catalog approved by the State of California Office of
Statewide Health Planning and Development
(OSHPD)
. For additional load,
spacing and placement information relating to OSHPD projects, please refer
to the TOLCO Seismic Restraint Systems Guidelines.
Finish
— Plain
Note
— Available in Electro-Galvanized and HDG finish.
Order By
— Indicate pipe size to be braced followed by pipe size used for
bracing, figure number and finish.
Important Note
— The Fig. 1001 is precision manufactured to perform
its function as a critical component of a complete bracing assembly. To
ensure performance, the UL Listing requires that the Fig. 1001 must be
used only with other TOLCO bracing products.
Component of State of
California OSHPD Approved
Seismic Restraints System
Maximum Design Load
2-1/2” - 6” Allied DynaFlow (Sch. 7) - 1600 lbs.
2-1/2” - 6” Sch. 10 & 40 - 2015 lbs.
8” Sch. 10 & 40 - 2765 lbs.
FM Approved Design Loads*
2½ “ - 2400 lbs.
3” - 4” - 2500 lbs.
5” - 8” - 1500 lbs.
COOPER B-LINE
1375 Sampson Ave • Corona, CA 92879 • 800.786.5266 • FAX: 951.737.0330
Содержание VicFlex AH1
Страница 26: ......
Страница 27: ......
Страница 44: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Страница 75: ......
Страница 76: ......
Страница 93: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Страница 124: ......
Страница 125: ......
Страница 142: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Страница 153: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Страница 184: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...
Страница 215: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...