1.0  PRODUCT DESCRIPTION

Available Sizes by Component

•  Series AH1 Braided Hose:

 31, 36, 48, 60, 72"/790, 914, 1220, 1525, 1830 mm. Note: length includes adapter 

nipple and 5.75"/140 mm straight reducer.

•  Sprinkler Reducers:

 ½" and ¾"/15 and 20 mm sprinkler connections and 5.75"/140 mm, 9"/230 mm, 13"/330 mm 

straight lengths and short, long 90º elbows. Note: The short 90° elbow is typically used with concealed sprinklers 
while the long 90º elbow is typically used in the installation of recessed pendent sprinklers.

•  Adapter Nipples:

 1"/25 mm NPT or BSPT adapter nipples for attaching to pipe and fittings outlined in NFPA 

standards. ¾"/20 mm NPT or BSPT available for VdS. 1 ¼"/ 32mm BSPT available for LPCB.

•  Brackets:

•  Style AB1 for suspended and hard-lid ceilings, allows installation before ceiling tiles in place
•  Style AB2 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and installation before   
    ceiling tiles in place
•  Style AB3 for surface mount applications, wood, metal and block walls
•  Style AB4 for hard-lid ceilings with hat furring channel grid systems, allows for vertical sprinkler adjustment
•  Style AB6 for cold storage applications, refer to submittal 10.90
•  Style AB7 for suspended and hard-lid ceilings
•  Style AB7 Adjustable for suspended and hard-lid ceilings
•  Style AB8 for hard-lid ceilings with CD 60/27 profile metal studs (regionally available)
•  Style AB9 for hard-lid ceilings with hat furring channel grid systems
•  Style AB10 for Armstrong

®

 TechZone

 ceilings

Maximum Working Temperature

•  225°F/107°C

Maximum Working Pressure

•  200 psi/1375 kPa (FM Approval)
•  175 psi/1206 kPa (cULus Listed)
•  1600 kPa/232 psi (VdS/LPCB Approved)

Victaulic

®

 Vic-Flex™ Sprinkler Fittings

Series AH1 Braided Flexible Hose

10.95

1

System No.

Location

Submitted By

Date

Spec Section

Paragraph

Approved

Date

Содержание VicFlex AH1

Страница 1: ...for suspended and hard lid ceilings allows installation before ceiling tiles in place Style AB2 for suspended and hard lid ceilings allows for vertical sprinkler adjustment and installation before ce...

Страница 2: ...m cULus Listed 3 76 2 mm VdS LPCB Approved Maximum Allowable Sprinkler K Factors FM 15mm reducer K5 6 8 1 S I 20mm reducer K14 0 20 2 S I cULus 15mm reducer K8 0 11 5 S I 20mm reducer K14 0 20 2 S I V...

Страница 3: ...ches mm inches mm 31 790 25 25 641 31 790 36 915 31 25 794 36 915 48 1220 42 25 1073 48 1220 60 1525 54 25 1378 60 1525 72 1830 66 25 1683 72 1830 Standard Reducer 5 75 140 mm straight reducer Optiona...

Страница 4: ...ription 1 24 610mm or 48 1220mm Square Bar 2 Patented Center Bracket 3 End Bracket Both sizes FM VdS LPCB approved cULus listed Style AB2 Suspended Ceilings Hard Lid Ceilings Item Description 1 24 610...

Страница 5: ...Center bracket 3 End Bracket for Hat Furring Channel Both sizes FM VdS approved cULus listed Style AB7 Suspended Ceilings Hard Lid Ceilings Item Description 1 24 610mm or 48 1220mm Square Bar 2 Patent...

Страница 6: ...et 3 Both sizes FM VdS Both sizes FM VdS approved Style AB9 Hard Lid ceilings with Hat furring channel grid system Item Description 1 24 610mm or 48 1220mm Square Bar 2 Patented 1 Bee2 Center Bracket...

Страница 7: ...sion inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 R Minimum Bend Radi...

Страница 8: ...m inches mm inches mm inches mm R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 A Min 7 63 193 8 63 218 9 63 244 10 63 269 11 63 295 12...

Страница 9: ...mm 16 406 mm Stud C C 1 8 45 mm 2 4 Stud Bracket assembly Style AB2 10 Screw R See chart A See chart Finished sidewall face 23 8 60 mm max hole 2 51 mm min hole 3 5 89 mm 16 406 mm Stud C C 1 8 45 mm...

Страница 10: ...7 12 3 313 13 3 338 14 3 363 5 15 3 389 Hat Furring Channel Grid with Recessed Sprinkler with 90 Elbow Long Hat Furring Channel Grid with Concealed Sprinkler with 90 Elbow Short A See Chart 23 mm Typi...

Страница 11: ...B 5 75 146 1 9 228 6 13 330 2 5 75 146 1 9 228 6 13 330 2 9 228 6 13 330 2 13 330 2 13 330 2 5 75 146 1 9 228 6 13 330 2 5 75 146 1 9 228 6 13 330 2 9 228 6 13 330 2 13 330 2 13 330 2 Hose Clearance...

Страница 12: ...3 10 1 44 13 4 55 16 8 N A N A 36 900 15 33 10 1 43 13 1 53 16 2 63 19 2 N A 20 36 11 0 46 14 0 56 17 1 66 20 1 N A 48 1200 15 46 14 0 57 17 4 68 20 7 78 23 8 N A 20 51 15 5 60 18 3 71 21 6 88 26 8 N...

Страница 13: ...48 1200 11 2 16 1 20 Straight 82 7 25 2 3 20 90 Elbow 82 8 25 2 60 1500 11 2 16 1 20 Straight 109 1 33 2 4 20 90 Elbow 108 1 32 9 72 1800 11 2 16 1 20 Straight 135 5 41 3 4 20 90 Elbow 133 4 40 6 31 7...

Страница 14: ...n Pagos 16 Suckow Fischer 17 USG Donn No specific approval 1 Hilti 2 Knauf 3 Lafarge 4 Lindner 5 Rigips Series AH1 Braided Hose Style AB1 Bracket Length of Stainless Steel Flexible Hose Series AH1 Hos...

Страница 15: ...to change product specifications designs and standard equipment without notice and without incurring obligations Installation Reference should always be made to I VICFLEX AB1 AB2 AB10 I VICFLEX AB4 A...

Страница 16: ...3 size only Not on 2 175 PSI 12 1 Bar Non Shock Cold Water Conforms to MSS SP 80 UL ULC Listed Dimensions Weights Quantities Dimensions Size A B H Weight Box Master In mm In mm In mm In mm Lbs Kg Qty...

Страница 17: ...as to how we can improve or products or instructions If you have any difficulties at all please give us a call Thank you for purchasing our product IMPORTANT NOTE We use Stainless Steel Hardware where...

Страница 18: ...kflow Direct recommends using a weather proof rigid 90 degree pull elbow a weather proof rigid LB Conduit Body and close nipples x2 for installation of tamper switches to fire alarm panel 2 Philips He...

Страница 19: ...ll 90 Degree Pull Elbow A If the pull elbow did not come with a threaded end attach a close nipple to the 90 degree pull elbow B run the electrical leads from the gearbox through the 90 degree pull el...

Страница 20: ...l elbow and run electrical leads through the close nipple into the LB Conduit body F Attach to fire alarm panel leads and reinstall the weatherproof cover on the LB Conduit body G Attach flex conduit...

Страница 21: ...IES KT 585 70 UL Dimensions Size A B C D Port Weight Box Master In mm In mm In mm In mm In mm Lbs Kg Qty Ctn Qty 4 KT 580 70 UL Dimensions Size A B C D Port Weight Box Master In mm In mm In mm In mm I...

Страница 22: ...f metal beams purlins channel or angle iron Setscrew made of hardened steel Retainer straps available Conforms with Federal Specification WW H 171 Type 23 Manufacturers Standardization Society ANSI MS...

Страница 23: ...cluded with each valve HEADLOSS EQUIVALENT LENGTH OF PIPE Valve Size Pipe O D Equivalent Feet of Pipe C 120 Sch 10 Sch 30 Sch 40 In mm In mm Ft m Ft m Ft m 2 2 375 5 8 4 7 50 60 3 1 8 1 4 21 2 2 875 5...

Страница 24: ...0 5 1 3 3 0 3 3 5 5 7 7 10 9 21 2 2 875 9 14 34 78 84 142 196 280 65 73 0 0 6 1 0 2 3 5 4 5 8 9 8 13 5 19 3 3 3 500 14 20 50 112 128 215 285 400 80 88 9 1 0 1 4 3 4 7 7 8 8 14 8 19 7 27 6 4 4 500 29 4...

Страница 25: ...SUPERVISORY SWITCH AUXILIARY SWITCH Notes 1 Single Pole Double Throw Switch wired Normally Closed supplied with Single Wire leads 2 Switch Schematic shown with Valve in the Full Open Position and Swi...

Страница 26: ......

Страница 27: ......

Страница 28: ...s NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3201 90 Elbow For Listings Approval Details and Limitations vis...

Страница 29: ...es Dimensions Style Approx Wt Each Male M x Female F A B C In mm PSI kPa In mm In mm In mm Lbs kg 1 x 1 2 500 0 75 0 25 1 42 Outside 0 22 25 x 15 3450 19 05 6 35 36 06 0 10 1 x 3 4 500 0 75 0 25 1 42...

Страница 30: ...Threads NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3224 Cap For Listings Approval Details and Limitations vi...

Страница 31: ...01R REDUCING 90 ELBOW Nominal Size Max Working Pressures Dimensions Approx Wt Each 1 x 2 A B In mm PSI kPa In mm In mm Lbs kg 1 x 1 2 500 1 26 1 36 0 44 25 x 15 3450 32 00 34 54 0 20 1 x 3 4 500 1 37...

Страница 32: ...inish Black Threads NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3221R Reducing Coupling For Listings Approval...

Страница 33: ...0 32 00 34 54 0 32 1 x 1 x 3 4 500 1 37 1 37 1 45 0 76 25 x 25 x 20 3450 34 80 34 80 36 83 0 34 1 x 1 x 11 4 500 1 67 1 67 1 58 0 98 25 x 25 x 32 3450 42 41 42 41 40 13 0 44 1 x 1 x 11 2 500 1 80 1 80...

Страница 34: ...NG TEE Nominal Size Max Working Pressures Dimensions Approx Wt Each 1 x 2 x 3 A B C In mm PSI kPa In mm In mm In mm Lbs kg 11 4 x 11 4 x 2 500 2 10 2 10 1 90 1 75 32 x 32 x 50 3450 53 34 53 34 48 26 0...

Страница 35: ...per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3205 Straight Tee For Listings Approval Details and Limitations visi...

Страница 36: ...ter supply Exposed design provides an economical method of satisfying Fire Department Inlet requirements STANDARD EQUIPMENT Cast brass two way inlet body only with double drop clappers and pin lug swi...

Страница 37: ...is recommended Finish Plain Contact Cooper B Line for alternative finishes and materials Order By Order by figure number pipe size to be braced followed by pipe size used for bracing 1 25mm or 11 4 3...

Страница 38: ...s cULus Max Rec Load Lbs FM Approx Wt 100 A C D Bolt Size 2 5 3 8 2 1 16 2 1 16 1 2 2015 247 2 1 2 6 7 16 2 1 2 2 3 4 1 2 2015 3000 253 3 7 2 3 4 3 1 16 1 2 2015 1550 268 4 8 1 2 3 3 8 3 11 16 1 2 201...

Страница 39: ...ials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association NFPA Finish Plain Contact Cooper B Line for alternative finishes and materials Order By...

Страница 40: ...ed Brace pipe can be installed on top or bottom of pipe to be braced Approvals Underwriters Laboratories Listed in the USA UL and Canada cUL Approved by Factory Mutual Engineering FM Included in our S...

Страница 41: ...SFRVJSFE EFQUI JO PSEFS UP PCUBJO UIF EFTJSFE GJSF SBUJOH BLF TVSF 4 0 DPOUBDUT BMM TVSGBDFT UP QSPWJEF NBYJNVN BEIFTJPO PS BQQMJDBUJPO PG 4 0 VTF B TUBOEBSE DBVMLJOH HVO GPJM QBDL HVO CVML MPBEFS BOE...

Страница 42: ...R indicates as respirable fraction A indicates as an aerosol mppcf million particles per cubic foot PHYSICAL DATA Appearance Red paste Odor Odorless Vapor Density air 1 Not determined Vapor Pressure...

Страница 43: ...onfined space without an appropriate air supplied respirator PRECAUTIONS FOR SAFE HANDLING AND USE Handling and Storing Precautions Store in a cool dry area preferably between 40 and 77 F Keep from fr...

Страница 44: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...

Страница 45: ...Switch Assembly stock no 1029030 Waterflowswitchesthataremonitoringwetpipesprinklersystemsshall not be used as the sole initiating device to discharge AFFF deluge or chemical suppression systems Wate...

Страница 46: ...t false alarms Flowing water activates device in one direction only DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION...

Страница 47: ...sions DWG 1146 14 3 50 in 89 0 mm 2 34 in 59 4 mm PIPE DIA 5 25 in 133 4 mm 5 56 in 141 2 mm 2 00 in 50 8 mm U BOLT NUT U BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U BOLT NOMINAL PIPE DIA 1 75 in 44...

Страница 48: ...waterflow switch 4 Remove the 2 mounting screws holding retard switch assembly to the base Do not remove the 2 retard housing screws 5 Remove the retard assembly by lifting it straight up over the tr...

Страница 49: ...7 31 18 Revise per Comments Re submittal not required Comments Please obtain all necessary approvals from local authorities having jurisdiction prior to beginning work Coordinate concealed sprinkler c...

Страница 50: ...lications wood metal and block walls Style AB4 for hard lid ceilings with hat furring channel grid systems allows for vertical sprinkler adjustment Style AB6 for cold storage applications refer to sub...

Страница 51: ...m cULus Listed 3 76 2 mm VdS LPCB Approved Maximum Allowable Sprinkler K Factors FM 15mm reducer K5 6 8 1 S I 20mm reducer K14 0 20 2 S I cULus 15mm reducer K8 0 11 5 S I 20mm reducer K14 0 20 2 S I V...

Страница 52: ...ches mm inches mm 31 790 25 25 641 31 790 36 915 31 25 794 36 915 48 1220 42 25 1073 48 1220 60 1525 54 25 1378 60 1525 72 1830 66 25 1683 72 1830 Standard Reducer 5 75 140 mm straight reducer Optiona...

Страница 53: ...ription 1 24 610mm or 48 1220mm Square Bar 2 Patented Center Bracket 3 End Bracket Both sizes FM VdS LPCB approved cULus listed Style AB2 Suspended Ceilings Hard Lid Ceilings Item Description 1 24 610...

Страница 54: ...Center bracket 3 End Bracket for Hat Furring Channel Both sizes FM VdS approved cULus listed Style AB7 Suspended Ceilings Hard Lid Ceilings Item Description 1 24 610mm or 48 1220mm Square Bar 2 Patent...

Страница 55: ...et 3 Both sizes FM VdS Both sizes FM VdS approved Style AB9 Hard Lid ceilings with Hat furring channel grid system Item Description 1 24 610mm or 48 1220mm Square Bar 2 Patented 1 Bee2 Center Bracket...

Страница 56: ...sion inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 R Minimum Bend Radi...

Страница 57: ...m inches mm inches mm inches mm R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 A Min 7 63 193 8 63 218 9 63 244 10 63 269 11 63 295 12...

Страница 58: ...mm 16 406 mm Stud C C 1 8 45 mm 2 4 Stud Bracket assembly Style AB2 10 Screw R See chart A See chart Finished sidewall face 23 8 60 mm max hole 2 51 mm min hole 3 5 89 mm 16 406 mm Stud C C 1 8 45 mm...

Страница 59: ...7 12 3 313 13 3 338 14 3 363 5 15 3 389 Hat Furring Channel Grid with Recessed Sprinkler with 90 Elbow Long Hat Furring Channel Grid with Concealed Sprinkler with 90 Elbow Short A See Chart 23 mm Typi...

Страница 60: ...B 5 75 146 1 9 228 6 13 330 2 5 75 146 1 9 228 6 13 330 2 9 228 6 13 330 2 13 330 2 13 330 2 5 75 146 1 9 228 6 13 330 2 5 75 146 1 9 228 6 13 330 2 9 228 6 13 330 2 13 330 2 13 330 2 Hose Clearance...

Страница 61: ...3 10 1 44 13 4 55 16 8 N A N A 36 900 15 33 10 1 43 13 1 53 16 2 63 19 2 N A 20 36 11 0 46 14 0 56 17 1 66 20 1 N A 48 1200 15 46 14 0 57 17 4 68 20 7 78 23 8 N A 20 51 15 5 60 18 3 71 21 6 88 26 8 N...

Страница 62: ...48 1200 11 2 16 1 20 Straight 82 7 25 2 3 20 90 Elbow 82 8 25 2 60 1500 11 2 16 1 20 Straight 109 1 33 2 4 20 90 Elbow 108 1 32 9 72 1800 11 2 16 1 20 Straight 135 5 41 3 4 20 90 Elbow 133 4 40 6 31 7...

Страница 63: ...n Pagos 16 Suckow Fischer 17 USG Donn No specific approval 1 Hilti 2 Knauf 3 Lafarge 4 Lindner 5 Rigips Series AH1 Braided Hose Style AB1 Bracket Length of Stainless Steel Flexible Hose Series AH1 Hos...

Страница 64: ...to change product specifications designs and standard equipment without notice and without incurring obligations Installation Reference should always be made to I VICFLEX AB1 AB2 AB10 I VICFLEX AB4 A...

Страница 65: ...3 size only Not on 2 175 PSI 12 1 Bar Non Shock Cold Water Conforms to MSS SP 80 UL ULC Listed Dimensions Weights Quantities Dimensions Size A B H Weight Box Master In mm In mm In mm In mm Lbs Kg Qty...

Страница 66: ...as to how we can improve or products or instructions If you have any difficulties at all please give us a call Thank you for purchasing our product IMPORTANT NOTE We use Stainless Steel Hardware where...

Страница 67: ...kflow Direct recommends using a weather proof rigid 90 degree pull elbow a weather proof rigid LB Conduit Body and close nipples x2 for installation of tamper switches to fire alarm panel 2 Philips He...

Страница 68: ...ll 90 Degree Pull Elbow A If the pull elbow did not come with a threaded end attach a close nipple to the 90 degree pull elbow B run the electrical leads from the gearbox through the 90 degree pull el...

Страница 69: ...l elbow and run electrical leads through the close nipple into the LB Conduit body F Attach to fire alarm panel leads and reinstall the weatherproof cover on the LB Conduit body G Attach flex conduit...

Страница 70: ...IES KT 585 70 UL Dimensions Size A B C D Port Weight Box Master In mm In mm In mm In mm In mm Lbs Kg Qty Ctn Qty 4 KT 580 70 UL Dimensions Size A B C D Port Weight Box Master In mm In mm In mm In mm I...

Страница 71: ...f metal beams purlins channel or angle iron Setscrew made of hardened steel Retainer straps available Conforms with Federal Specification WW H 171 Type 23 Manufacturers Standardization Society ANSI MS...

Страница 72: ...cluded with each valve HEADLOSS EQUIVALENT LENGTH OF PIPE Valve Size Pipe O D Equivalent Feet of Pipe C 120 Sch 10 Sch 30 Sch 40 In mm In mm Ft m Ft m Ft m 2 2 375 5 8 4 7 50 60 3 1 8 1 4 21 2 2 875 5...

Страница 73: ...0 5 1 3 3 0 3 3 5 5 7 7 10 9 21 2 2 875 9 14 34 78 84 142 196 280 65 73 0 0 6 1 0 2 3 5 4 5 8 9 8 13 5 19 3 3 3 500 14 20 50 112 128 215 285 400 80 88 9 1 0 1 4 3 4 7 7 8 8 14 8 19 7 27 6 4 4 500 29 4...

Страница 74: ...SUPERVISORY SWITCH AUXILIARY SWITCH Notes 1 Single Pole Double Throw Switch wired Normally Closed supplied with Single Wire leads 2 Switch Schematic shown with Valve in the Full Open Position and Swi...

Страница 75: ......

Страница 76: ......

Страница 77: ...s NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3201 90 Elbow For Listings Approval Details and Limitations vis...

Страница 78: ...es Dimensions Style Approx Wt Each Male M x Female F A B C In mm PSI kPa In mm In mm In mm Lbs kg 1 x 1 2 500 0 75 0 25 1 42 Outside 0 22 25 x 15 3450 19 05 6 35 36 06 0 10 1 x 3 4 500 0 75 0 25 1 42...

Страница 79: ...Threads NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3224 Cap For Listings Approval Details and Limitations vi...

Страница 80: ...01R REDUCING 90 ELBOW Nominal Size Max Working Pressures Dimensions Approx Wt Each 1 x 2 A B In mm PSI kPa In mm In mm Lbs kg 1 x 1 2 500 1 26 1 36 0 44 25 x 15 3450 32 00 34 54 0 20 1 x 3 4 500 1 37...

Страница 81: ...inish Black Threads NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3221R Reducing Coupling For Listings Approval...

Страница 82: ...0 32 00 34 54 0 32 1 x 1 x 3 4 500 1 37 1 37 1 45 0 76 25 x 25 x 20 3450 34 80 34 80 36 83 0 34 1 x 1 x 11 4 500 1 67 1 67 1 58 0 98 25 x 25 x 32 3450 42 41 42 41 40 13 0 44 1 x 1 x 11 2 500 1 80 1 80...

Страница 83: ...NG TEE Nominal Size Max Working Pressures Dimensions Approx Wt Each 1 x 2 x 3 A B C In mm PSI kPa In mm In mm In mm Lbs kg 11 4 x 11 4 x 2 500 2 10 2 10 1 90 1 75 32 x 32 x 50 3450 53 34 53 34 48 26 0...

Страница 84: ...per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3205 Straight Tee For Listings Approval Details and Limitations visi...

Страница 85: ...ter supply Exposed design provides an economical method of satisfying Fire Department Inlet requirements STANDARD EQUIPMENT Cast brass two way inlet body only with double drop clappers and pin lug swi...

Страница 86: ...s cULus Max Rec Load Lbs FM Approx Wt 100 A C D Bolt Size 2 5 3 8 2 1 16 2 1 16 1 2 2015 247 2 1 2 6 7 16 2 1 2 2 3 4 1 2 2015 3000 253 3 7 2 3 4 3 1 16 1 2 2015 1550 268 4 8 1 2 3 3 8 3 11 16 1 2 201...

Страница 87: ...ials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association NFPA Finish Plain Contact Cooper B Line for alternative finishes and materials Order By...

Страница 88: ...is recommended Finish Plain Contact Cooper B Line for alternative finishes and materials Order By Order by figure number pipe size to be braced followed by pipe size used for bracing 1 25mm or 11 4 3...

Страница 89: ...ed Brace pipe can be installed on top or bottom of pipe to be braced Approvals Underwriters Laboratories Listed in the USA UL and Canada cUL Approved by Factory Mutual Engineering FM Included in our S...

Страница 90: ...SFRVJSFE EFQUI JO PSEFS UP PCUBJO UIF EFTJSFE GJSF SBUJOH BLF TVSF 4 0 DPOUBDUT BMM TVSGBDFT UP QSPWJEF NBYJNVN BEIFTJPO PS BQQMJDBUJPO PG 4 0 VTF B TUBOEBSE DBVMLJOH HVO GPJM QBDL HVO CVML MPBEFS BOE...

Страница 91: ...R indicates as respirable fraction A indicates as an aerosol mppcf million particles per cubic foot PHYSICAL DATA Appearance Red paste Odor Odorless Vapor Density air 1 Not determined Vapor Pressure...

Страница 92: ...onfined space without an appropriate air supplied respirator PRECAUTIONS FOR SAFE HANDLING AND USE Handling and Storing Precautions Store in a cool dry area preferably between 40 and 77 F Keep from fr...

Страница 93: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...

Страница 94: ...Switch Assembly stock no 1029030 Waterflowswitchesthataremonitoringwetpipesprinklersystemsshall not be used as the sole initiating device to discharge AFFF deluge or chemical suppression systems Wate...

Страница 95: ...t false alarms Flowing water activates device in one direction only DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION...

Страница 96: ...sions DWG 1146 14 3 50 in 89 0 mm 2 34 in 59 4 mm PIPE DIA 5 25 in 133 4 mm 5 56 in 141 2 mm 2 00 in 50 8 mm U BOLT NUT U BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U BOLT NOMINAL PIPE DIA 1 75 in 44...

Страница 97: ...waterflow switch 4 Remove the 2 mounting screws holding retard switch assembly to the base Do not remove the 2 retard housing screws 5 Remove the retard assembly by lifting it straight up over the tr...

Страница 98: ...mmy Rosales Date No Exceptions Taken Comments Please obtain all necessary approvals from local authorities having jurisdiction prior to beginning work Coordinate concealed sprinkler cover color with A...

Страница 99: ...for suspended and hard lid ceilings allows installation before ceiling tiles in place Style AB2 for suspended and hard lid ceilings allows for vertical sprinkler adjustment and installation before ce...

Страница 100: ...m cULus Listed 3 76 2 mm VdS LPCB Approved Maximum Allowable Sprinkler K Factors FM 15mm reducer K5 6 8 1 S I 20mm reducer K14 0 20 2 S I cULus 15mm reducer K8 0 11 5 S I 20mm reducer K14 0 20 2 S I V...

Страница 101: ...ches mm inches mm 31 790 25 25 641 31 790 36 915 31 25 794 36 915 48 1220 42 25 1073 48 1220 60 1525 54 25 1378 60 1525 72 1830 66 25 1683 72 1830 Standard Reducer 5 75 140 mm straight reducer Optiona...

Страница 102: ...ription 1 24 610mm or 48 1220mm Square Bar 2 Patented Center Bracket 3 End Bracket Both sizes FM VdS LPCB approved cULus listed Style AB2 Suspended Ceilings Hard Lid Ceilings Item Description 1 24 610...

Страница 103: ...Center bracket 3 End Bracket for Hat Furring Channel Both sizes FM VdS approved cULus listed Style AB7 Suspended Ceilings Hard Lid Ceilings Item Description 1 24 610mm or 48 1220mm Square Bar 2 Patent...

Страница 104: ...et 3 Both sizes FM VdS Both sizes FM VdS approved Style AB9 Hard Lid ceilings with Hat furring channel grid system Item Description 1 24 610mm or 48 1220mm Square Bar 2 Patented 1 Bee2 Center Bracket...

Страница 105: ...sion inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 R Minimum Bend Radi...

Страница 106: ...m inches mm inches mm inches mm R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 R Minimum Bend Radius 2 50 3 80 4 100 5 125 6 150 7 175 A Min 7 63 193 8 63 218 9 63 244 10 63 269 11 63 295 12...

Страница 107: ...mm 16 406 mm Stud C C 1 8 45 mm 2 4 Stud Bracket assembly Style AB2 10 Screw R See chart A See chart Finished sidewall face 23 8 60 mm max hole 2 51 mm min hole 3 5 89 mm 16 406 mm Stud C C 1 8 45 mm...

Страница 108: ...7 12 3 313 13 3 338 14 3 363 5 15 3 389 Hat Furring Channel Grid with Recessed Sprinkler with 90 Elbow Long Hat Furring Channel Grid with Concealed Sprinkler with 90 Elbow Short A See Chart 23 mm Typi...

Страница 109: ...B 5 75 146 1 9 228 6 13 330 2 5 75 146 1 9 228 6 13 330 2 9 228 6 13 330 2 13 330 2 13 330 2 5 75 146 1 9 228 6 13 330 2 5 75 146 1 9 228 6 13 330 2 9 228 6 13 330 2 13 330 2 13 330 2 Hose Clearance...

Страница 110: ...3 10 1 44 13 4 55 16 8 N A N A 36 900 15 33 10 1 43 13 1 53 16 2 63 19 2 N A 20 36 11 0 46 14 0 56 17 1 66 20 1 N A 48 1200 15 46 14 0 57 17 4 68 20 7 78 23 8 N A 20 51 15 5 60 18 3 71 21 6 88 26 8 N...

Страница 111: ...48 1200 11 2 16 1 20 Straight 82 7 25 2 3 20 90 Elbow 82 8 25 2 60 1500 11 2 16 1 20 Straight 109 1 33 2 4 20 90 Elbow 108 1 32 9 72 1800 11 2 16 1 20 Straight 135 5 41 3 4 20 90 Elbow 133 4 40 6 31 7...

Страница 112: ...n Pagos 16 Suckow Fischer 17 USG Donn No specific approval 1 Hilti 2 Knauf 3 Lafarge 4 Lindner 5 Rigips Series AH1 Braided Hose Style AB1 Bracket Length of Stainless Steel Flexible Hose Series AH1 Hos...

Страница 113: ...to change product specifications designs and standard equipment without notice and without incurring obligations Installation Reference should always be made to I VICFLEX AB1 AB2 AB10 I VICFLEX AB4 A...

Страница 114: ...3 size only Not on 2 175 PSI 12 1 Bar Non Shock Cold Water Conforms to MSS SP 80 UL ULC Listed Dimensions Weights Quantities Dimensions Size A B H Weight Box Master In mm In mm In mm In mm Lbs Kg Qty...

Страница 115: ...as to how we can improve or products or instructions If you have any difficulties at all please give us a call Thank you for purchasing our product IMPORTANT NOTE We use Stainless Steel Hardware where...

Страница 116: ...kflow Direct recommends using a weather proof rigid 90 degree pull elbow a weather proof rigid LB Conduit Body and close nipples x2 for installation of tamper switches to fire alarm panel 2 Philips He...

Страница 117: ...ll 90 Degree Pull Elbow A If the pull elbow did not come with a threaded end attach a close nipple to the 90 degree pull elbow B run the electrical leads from the gearbox through the 90 degree pull el...

Страница 118: ...l elbow and run electrical leads through the close nipple into the LB Conduit body F Attach to fire alarm panel leads and reinstall the weatherproof cover on the LB Conduit body G Attach flex conduit...

Страница 119: ...IES KT 585 70 UL Dimensions Size A B C D Port Weight Box Master In mm In mm In mm In mm In mm Lbs Kg Qty Ctn Qty 4 KT 580 70 UL Dimensions Size A B C D Port Weight Box Master In mm In mm In mm In mm I...

Страница 120: ...f metal beams purlins channel or angle iron Setscrew made of hardened steel Retainer straps available Conforms with Federal Specification WW H 171 Type 23 Manufacturers Standardization Society ANSI MS...

Страница 121: ...cluded with each valve HEADLOSS EQUIVALENT LENGTH OF PIPE Valve Size Pipe O D Equivalent Feet of Pipe C 120 Sch 10 Sch 30 Sch 40 In mm In mm Ft m Ft m Ft m 2 2 375 5 8 4 7 50 60 3 1 8 1 4 21 2 2 875 5...

Страница 122: ...0 5 1 3 3 0 3 3 5 5 7 7 10 9 21 2 2 875 9 14 34 78 84 142 196 280 65 73 0 0 6 1 0 2 3 5 4 5 8 9 8 13 5 19 3 3 3 500 14 20 50 112 128 215 285 400 80 88 9 1 0 1 4 3 4 7 7 8 8 14 8 19 7 27 6 4 4 500 29 4...

Страница 123: ...SUPERVISORY SWITCH AUXILIARY SWITCH Notes 1 Single Pole Double Throw Switch wired Normally Closed supplied with Single Wire leads 2 Switch Schematic shown with Valve in the Full Open Position and Swi...

Страница 124: ......

Страница 125: ......

Страница 126: ...s NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3201 90 Elbow For Listings Approval Details and Limitations vis...

Страница 127: ...es Dimensions Style Approx Wt Each Male M x Female F A B C In mm PSI kPa In mm In mm In mm Lbs kg 1 x 1 2 500 0 75 0 25 1 42 Outside 0 22 25 x 15 3450 19 05 6 35 36 06 0 10 1 x 3 4 500 0 75 0 25 1 42...

Страница 128: ...Threads NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3224 Cap For Listings Approval Details and Limitations vi...

Страница 129: ...01R REDUCING 90 ELBOW Nominal Size Max Working Pressures Dimensions Approx Wt Each 1 x 2 A B In mm PSI kPa In mm In mm Lbs kg 1 x 1 2 500 1 26 1 36 0 44 25 x 15 3450 32 00 34 54 0 20 1 x 3 4 500 1 37...

Страница 130: ...inish Black Threads NPT per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3221R Reducing Coupling For Listings Approval...

Страница 131: ...0 32 00 34 54 0 32 1 x 1 x 3 4 500 1 37 1 37 1 45 0 76 25 x 25 x 20 3450 34 80 34 80 36 83 0 34 1 x 1 x 11 4 500 1 67 1 67 1 58 0 98 25 x 25 x 32 3450 42 41 42 41 40 13 0 44 1 x 1 x 11 2 500 1 80 1 80...

Страница 132: ...NG TEE Nominal Size Max Working Pressures Dimensions Approx Wt Each 1 x 2 x 3 A B C In mm PSI kPa In mm In mm In mm Lbs kg 11 4 x 11 4 x 2 500 2 10 2 10 1 90 1 75 32 x 32 x 50 3450 53 34 53 34 48 26 0...

Страница 133: ...per ASME B1 20 1 Agency Approvals All ductile iron threaded fittings are UL ULC Listed and FM Approved MATERIAL SPECIFICATIONS FIG 3205 Straight Tee For Listings Approval Details and Limitations visi...

Страница 134: ...ter supply Exposed design provides an economical method of satisfying Fire Department Inlet requirements STANDARD EQUIPMENT Cast brass two way inlet body only with double drop clappers and pin lug swi...

Страница 135: ...s cULus Max Rec Load Lbs FM Approx Wt 100 A C D Bolt Size 2 5 3 8 2 1 16 2 1 16 1 2 2015 247 2 1 2 6 7 16 2 1 2 2 3 4 1 2 2015 3000 253 3 7 2 3 4 3 1 16 1 2 2015 1550 268 4 8 1 2 3 3 8 3 11 16 1 2 201...

Страница 136: ...ials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association NFPA Finish Plain Contact Cooper B Line for alternative finishes and materials Order By...

Страница 137: ...is recommended Finish Plain Contact Cooper B Line for alternative finishes and materials Order By Order by figure number pipe size to be braced followed by pipe size used for bracing 1 25mm or 11 4 3...

Страница 138: ...ed Brace pipe can be installed on top or bottom of pipe to be braced Approvals Underwriters Laboratories Listed in the USA UL and Canada cUL Approved by Factory Mutual Engineering FM Included in our S...

Страница 139: ...SFRVJSFE EFQUI JO PSEFS UP PCUBJO UIF EFTJSFE GJSF SBUJOH BLF TVSF 4 0 DPOUBDUT BMM TVSGBDFT UP QSPWJEF NBYJNVN BEIFTJPO PS BQQMJDBUJPO PG 4 0 VTF B TUBOEBSE DBVMLJOH HVO GPJM QBDL HVO CVML MPBEFS BOE...

Страница 140: ...R indicates as respirable fraction A indicates as an aerosol mppcf million particles per cubic foot PHYSICAL DATA Appearance Red paste Odor Odorless Vapor Density air 1 Not determined Vapor Pressure...

Страница 141: ...onfined space without an appropriate air supplied respirator PRECAUTIONS FOR SAFE HANDLING AND USE Handling and Storing Precautions Store in a cool dry area preferably between 40 and 77 F Keep from fr...

Страница 142: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...

Страница 143: ...Switch Assembly stock no 1029030 Waterflowswitchesthataremonitoringwetpipesprinklersystemsshall not be used as the sole initiating device to discharge AFFF deluge or chemical suppression systems Wate...

Страница 144: ...t false alarms Flowing water activates device in one direction only DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION...

Страница 145: ...sions DWG 1146 14 3 50 in 89 0 mm 2 34 in 59 4 mm PIPE DIA 5 25 in 133 4 mm 5 56 in 141 2 mm 2 00 in 50 8 mm U BOLT NUT U BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U BOLT NOMINAL PIPE DIA 1 75 in 44...

Страница 146: ...waterflow switch 4 Remove the 2 mounting screws holding retard switch assembly to the base Do not remove the 2 retard housing screws 5 Remove the retard assembly by lifting it straight up over the tr...

Страница 147: ...install using the Sammy Nut Driver with a no load speed 2000 2500 rpm minimum 6 amps drill driver Installs into steel structures easily and quickly Available in Vertical Horizontal and Swivel Head DES...

Страница 148: ...3 8 or 1 2 portable drill 2 Insert the SAMMYS into the 14 black nut driver p n 8113910 Drill should be in a vertical position 3 Push the face of the nut driver tight to the member When the nut driver...

Страница 149: ...QTY NUT DRIVER 1 4 8024957 DSTR 100 1 4 20 x 1 TEKS 3 1510 20 ga 036 20 ga 3 16 25 125 Part 8113910 1 4 8025957 DST 100 1 4 14 x 1 TEKS 3 446 20 ga 036 20 ga 3 16 25 125 1 4 8030957 TEK 500 12 24 x 1...

Страница 150: ...2 5 3270 3593 DSTR 1 1 4 3 1510 DSTR 516 5 16 3 2200 SPECIAL NUT DRIVER SYSTEM The nut drivers were designed with a unique spin off feature which provides a fast and safe installation each time When t...

Страница 151: ...attachment for installation of branch end of line restraint using 1 2 all thread 405 OD or end thread rod 500 OD Designed for use in bar joist I beam rectangular square and circular hollow structural...

Страница 152: ...1 7 2 5 3 4 Rods threaded at ends only 3 8 in 0 11 0 094 0 8 1 6 2 4 3 1 1 2 in 0 196 0 125 1 0 2 1 3 1 4 2 Reference NFPA 13 2007 Reference NFPA 13 2010 SWDR 1 1 2 AND SWDR 516 FOR 3 8 ROD Structura...

Страница 153: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...

Страница 154: ...x n n x x x x x n x x n n V iV v V 7 7 i V 7 v 7 v 7 v x L L v L L L n x x nx x nx x n x x x n x n n x x n n x x x x n n n x x x n x n x x n x n x x n n n n n n x n n xxn x n n x x x x x n x x x x x...

Страница 155: ...designated in accordance with ASTM D 2000 q Pre Lubricated Grade E EPDM Type A Gasket Violet color code 40 F to 150 F Service Temperature Range 40 C to 65 C Recommended for wet and dry oil free air p...

Страница 156: ...M10 x 50 40 60 0 6 11 2 1 900 300 851 0 1 32 0 57 0 20 3 41 2 13 4 2 3 8 x 21 4 30 45 1 5 40 48 3 20 7 3 78 0 0 79 16 5 76 117 44 M10 x 50 40 60 0 7 2 2 375 300 1 329 0 1 32 0 45 0 16 33 8 5 17 8 2 3...

Страница 157: ...halves over the gasket making sure the housing keys engage the grooves Insert the bolt and turn the nuts finger tight 5Tighten nuts Tighten the nuts alternately and equally to the specified bolt torq...

Страница 158: ...DN mm In mm In mm Lbs Kg 1 1 315 11 4 0 3 25 33 4 25 0 1 11 4 1 660 1 0 4 32 42 2 25 0 2 11 2 1 900 1 0 5 40 48 3 25 0 2 2 2 375 1 0 7 50 60 3 25 0 3 21 2 2 875 1 1 0 65 73 0 25 0 4 3 O D 3 000 1 0 9...

Страница 159: ...k head bolts made of carbon steel with mechanical properties per ISO 898 1 Class 8 8 Hex nuts and bolts are zinc electroplated followed by a yellow chromate dip COATINGS q Rust inhibiting paint Color...

Страница 160: ...150 2 2 5 5 563 300 7 292 0 3 32 615 16 91 16 21 16 2 1 2 x 3 80 100 4 5 125 141 3 20 7 32 44 0 2 38 176 230 52 M12 x 76 110 150 2 0 61 2 O D 6 500 300 9 955 0 3 32 81 8 103 8 21 8 2 1 2 x 3 80 100 5...

Страница 161: ...alternately and evenly until fully tightened Caution Use of an impact wrench is not recommended because the torque output can vary significantly due to many variables including air pressure supply ba...

Страница 162: ...le RAL3000 or RAL9000 Series K 9 DRAIN CAP Nominal Size O D End to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 0 83 50 60 3 0 38 21 2 2 875 1 06 65 73 0 0 48 3 O D 2 996 1 06 76 1 76 1 0 48 3...

Страница 163: ...e NPT Outlet per ASME B1 20 1 E 9 DRAIN ELBOW Nominal Size O D Max Working Pressure s Center to End H Approx Wt Ea In DN mm In mm PSI bar In mm In mm Lbs Kg 11 4 1 660 300 23 4 13 4 0 7 32 42 2 20 7 6...

Страница 164: ...SAE J429 Grade 5 with a minimum tensile strength of 120 000 psi and heavy hex nuts of carbon steel conforming to ASTM A 563 Grade A or J995 Grade 2 Bolts and nuts are provided zinc electroplated as s...

Страница 165: ...6 1 20 7 21 22 0 4 8 20 8 159 225 51 M16 x 95 135 175 3 5 51 2 O D x 4 5 500 4 500 300 7 128 0 3 16 1 58 0 20 71 4 105 8 21 8 2 3 4 x 41 2 100 130 11 4 139 X 114 139 7 114 3 20 7 31 71 0 4 8 10 8 184...

Страница 166: ...ional q Other available options Example RAL3000 or RAL9000 Series ST 1 TEE Nominal Size O D Center to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 23 4 2 9 50 60 3 70 1 3 21 2 2 875 3 4 6 65 7...

Страница 167: ...Other available options Example RAL3000 or RAL9000 Series SE 1 90 ELBOW Nominal Size O D Center to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 23 4 1 5 50 60 3 70 0 7 21 2 2 875 3 2 1 65 73 0...

Страница 168: ...SA UL and Canada cUL for steel and CPVC plastic pipe and Factory Mutual Engineering Approved 3 4 thru 8 Conforms to Federal Specifications WW H 171E Type 10 and Manufacturers Standardization Society S...

Страница 169: ...tallation practice of a retaining strap requires that the strap be held tightly and securely to all component parts of the assembly Therefore a locking mechanism of some kind such as the beveled locki...

Страница 170: ...bed herein must be installed and maintained in compliance with this document as well as with the applicable standards of the National Fire Protection Association in addition to the standards of any ot...

Страница 171: ...the wrench flats Torque sprinklers 7 to 14 ft lbs 9 5 to 19 0 Nm Recessed Pendent Sprinklers The Series TY FRB Recessed Pendent Sprinklers must be installed in accor dance with the following instruct...

Страница 172: ...their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Asso ciation e g NFPA 25 in addition to the standards...

Страница 173: ...d 175 F 79 C Yellow 200 F 93 C Green Notes 1 Listed by Underwriters Laboratories Inc UL as Quick Response Sprinklers 2 Listed by Underwriters Laboratories Inc for use in Canada C UL as Quick Response...

Страница 174: ...e into plaster board or ceiling tiles by gently pushing the ceiling product against the Pro tective Cap When ceiling installa tion is complete the Protective Cap is removed and the Cover Plate Retaine...

Страница 175: ...o shatter the glass bulb activating the sprinkler and allowing water to flow Installation The TYCO Series RFII 5 6 K factor Royal Flush II Concealed Pendent Sprinklers must be installed in accor dance...

Страница 176: ...d and the Deflector does not move up and down freely replace the entire Sprinkler Do not attempt to modify or repair a damaged sprinkler Step 7 When installing an Air and Dust Seal refer to Figure 5 o...

Страница 177: ...st liquid from its bulb Ref Installa tion Section Exercise care to avoid damage to sprin klers before during and after instal lation Replace sprinklers damaged by dropping striking wrench twist ing wr...

Страница 178: ...install using the Sammy Nut Driver with a no load speed 2000 2500 rpm minimum 6 amps drill driver Installs into steel structures easily and quickly Available in Vertical Horizontal and Swivel Head DES...

Страница 179: ...3 8 or 1 2 portable drill 2 Insert the SAMMYS into the 14 black nut driver p n 8113910 Drill should be in a vertical position 3 Push the face of the nut driver tight to the member When the nut driver...

Страница 180: ...QTY NUT DRIVER 1 4 8024957 DSTR 100 1 4 20 x 1 TEKS 3 1510 20 ga 036 20 ga 3 16 25 125 Part 8113910 1 4 8025957 DST 100 1 4 14 x 1 TEKS 3 446 20 ga 036 20 ga 3 16 25 125 1 4 8030957 TEK 500 12 24 x 1...

Страница 181: ...2 5 3270 3593 DSTR 1 1 4 3 1510 DSTR 516 5 16 3 2200 SPECIAL NUT DRIVER SYSTEM The nut drivers were designed with a unique spin off feature which provides a fast and safe installation each time When t...

Страница 182: ...attachment for installation of branch end of line restraint using 1 2 all thread 405 OD or end thread rod 500 OD Designed for use in bar joist I beam rectangular square and circular hollow structural...

Страница 183: ...1 7 2 5 3 4 Rods threaded at ends only 3 8 in 0 11 0 094 0 8 1 6 2 4 3 1 1 2 in 0 196 0 125 1 0 2 1 3 1 4 2 Reference NFPA 13 2007 Reference NFPA 13 2010 SWDR 1 1 2 AND SWDR 516 FOR 3 8 ROD Structura...

Страница 184: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...

Страница 185: ...x n n x x x x x n x x n n V iV v V 7 7 i V 7 v 7 v 7 v x L L v L L L n x x nx x nx x n x x x n x n n x x n n x x x x n n n x x x n x n x x n x n x x n n n n n n x n n xxn x n n x x x x x n x x x x x...

Страница 186: ...designated in accordance with ASTM D 2000 q Pre Lubricated Grade E EPDM Type A Gasket Violet color code 40 F to 150 F Service Temperature Range 40 C to 65 C Recommended for wet and dry oil free air p...

Страница 187: ...M10 x 50 40 60 0 6 11 2 1 900 300 851 0 1 32 0 57 0 20 3 41 2 13 4 2 3 8 x 21 4 30 45 1 5 40 48 3 20 7 3 78 0 0 79 16 5 76 117 44 M10 x 50 40 60 0 7 2 2 375 300 1 329 0 1 32 0 45 0 16 33 8 5 17 8 2 3...

Страница 188: ...halves over the gasket making sure the housing keys engage the grooves Insert the bolt and turn the nuts finger tight 5Tighten nuts Tighten the nuts alternately and equally to the specified bolt torq...

Страница 189: ...DN mm In mm In mm Lbs Kg 1 1 315 11 4 0 3 25 33 4 25 0 1 11 4 1 660 1 0 4 32 42 2 25 0 2 11 2 1 900 1 0 5 40 48 3 25 0 2 2 2 375 1 0 7 50 60 3 25 0 3 21 2 2 875 1 1 0 65 73 0 25 0 4 3 O D 3 000 1 0 9...

Страница 190: ...k head bolts made of carbon steel with mechanical properties per ISO 898 1 Class 8 8 Hex nuts and bolts are zinc electroplated followed by a yellow chromate dip COATINGS q Rust inhibiting paint Color...

Страница 191: ...150 2 2 5 5 563 300 7 292 0 3 32 615 16 91 16 21 16 2 1 2 x 3 80 100 4 5 125 141 3 20 7 32 44 0 2 38 176 230 52 M12 x 76 110 150 2 0 61 2 O D 6 500 300 9 955 0 3 32 81 8 103 8 21 8 2 1 2 x 3 80 100 5...

Страница 192: ...alternately and evenly until fully tightened Caution Use of an impact wrench is not recommended because the torque output can vary significantly due to many variables including air pressure supply ba...

Страница 193: ...le RAL3000 or RAL9000 Series K 9 DRAIN CAP Nominal Size O D End to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 0 83 50 60 3 0 38 21 2 2 875 1 06 65 73 0 0 48 3 O D 2 996 1 06 76 1 76 1 0 48 3...

Страница 194: ...e NPT Outlet per ASME B1 20 1 E 9 DRAIN ELBOW Nominal Size O D Max Working Pressure s Center to End H Approx Wt Ea In DN mm In mm PSI bar In mm In mm Lbs Kg 11 4 1 660 300 23 4 13 4 0 7 32 42 2 20 7 6...

Страница 195: ...SAE J429 Grade 5 with a minimum tensile strength of 120 000 psi and heavy hex nuts of carbon steel conforming to ASTM A 563 Grade A or J995 Grade 2 Bolts and nuts are provided zinc electroplated as s...

Страница 196: ...6 1 20 7 21 22 0 4 8 20 8 159 225 51 M16 x 95 135 175 3 5 51 2 O D x 4 5 500 4 500 300 7 128 0 3 16 1 58 0 20 71 4 105 8 21 8 2 3 4 x 41 2 100 130 11 4 139 X 114 139 7 114 3 20 7 31 71 0 4 8 10 8 184...

Страница 197: ...ional q Other available options Example RAL3000 or RAL9000 Series ST 1 TEE Nominal Size O D Center to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 23 4 2 9 50 60 3 70 1 3 21 2 2 875 3 4 6 65 7...

Страница 198: ...Other available options Example RAL3000 or RAL9000 Series SE 1 90 ELBOW Nominal Size O D Center to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 23 4 1 5 50 60 3 70 0 7 21 2 2 875 3 2 1 65 73 0...

Страница 199: ...SA UL and Canada cUL for steel and CPVC plastic pipe and Factory Mutual Engineering Approved 3 4 thru 8 Conforms to Federal Specifications WW H 171E Type 10 and Manufacturers Standardization Society S...

Страница 200: ...tallation practice of a retaining strap requires that the strap be held tightly and securely to all component parts of the assembly Therefore a locking mechanism of some kind such as the beveled locki...

Страница 201: ...bed herein must be installed and maintained in compliance with this document as well as with the applicable standards of the National Fire Protection Association in addition to the standards of any ot...

Страница 202: ...the wrench flats Torque sprinklers 7 to 14 ft lbs 9 5 to 19 0 Nm Recessed Pendent Sprinklers The Series TY FRB Recessed Pendent Sprinklers must be installed in accor dance with the following instruct...

Страница 203: ...their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Asso ciation e g NFPA 25 in addition to the standards...

Страница 204: ...d 175 F 79 C Yellow 200 F 93 C Green Notes 1 Listed by Underwriters Laboratories Inc UL as Quick Response Sprinklers 2 Listed by Underwriters Laboratories Inc for use in Canada C UL as Quick Response...

Страница 205: ...e into plaster board or ceiling tiles by gently pushing the ceiling product against the Pro tective Cap When ceiling installa tion is complete the Protective Cap is removed and the Cover Plate Retaine...

Страница 206: ...o shatter the glass bulb activating the sprinkler and allowing water to flow Installation The TYCO Series RFII 5 6 K factor Royal Flush II Concealed Pendent Sprinklers must be installed in accor dance...

Страница 207: ...d and the Deflector does not move up and down freely replace the entire Sprinkler Do not attempt to modify or repair a damaged sprinkler Step 7 When installing an Air and Dust Seal refer to Figure 5 o...

Страница 208: ...st liquid from its bulb Ref Installa tion Section Exercise care to avoid damage to sprin klers before during and after instal lation Replace sprinklers damaged by dropping striking wrench twist ing wr...

Страница 209: ...install using the Sammy Nut Driver with a no load speed 2000 2500 rpm minimum 6 amps drill driver Installs into steel structures easily and quickly Available in Vertical Horizontal and Swivel Head DES...

Страница 210: ...3 8 or 1 2 portable drill 2 Insert the SAMMYS into the 14 black nut driver p n 8113910 Drill should be in a vertical position 3 Push the face of the nut driver tight to the member When the nut driver...

Страница 211: ...QTY NUT DRIVER 1 4 8024957 DSTR 100 1 4 20 x 1 TEKS 3 1510 20 ga 036 20 ga 3 16 25 125 Part 8113910 1 4 8025957 DST 100 1 4 14 x 1 TEKS 3 446 20 ga 036 20 ga 3 16 25 125 1 4 8030957 TEK 500 12 24 x 1...

Страница 212: ...2 5 3270 3593 DSTR 1 1 4 3 1510 DSTR 516 5 16 3 2200 SPECIAL NUT DRIVER SYSTEM The nut drivers were designed with a unique spin off feature which provides a fast and safe installation each time When t...

Страница 213: ...attachment for installation of branch end of line restraint using 1 2 all thread 405 OD or end thread rod 500 OD Designed for use in bar joist I beam rectangular square and circular hollow structural...

Страница 214: ...1 7 2 5 3 4 Rods threaded at ends only 3 8 in 0 11 0 094 0 8 1 6 2 4 3 1 1 2 in 0 196 0 125 1 0 2 1 3 1 4 2 Reference NFPA 13 2007 Reference NFPA 13 2010 SWDR 1 1 2 AND SWDR 516 FOR 3 8 ROD Structura...

Страница 215: ...PDF Created with deskPDF PDF Writer Trial http www docudesk com...

Страница 216: ...x n n x x x x x n x x n n V iV v V 7 7 i V 7 v 7 v 7 v x L L v L L L n x x nx x nx x n x x x n x n n x x n n x x x x n n n x x x n x n x x n x n x x n n n n n n x n n xxn x n n x x x x x n x x x x x...

Страница 217: ...designated in accordance with ASTM D 2000 q Pre Lubricated Grade E EPDM Type A Gasket Violet color code 40 F to 150 F Service Temperature Range 40 C to 65 C Recommended for wet and dry oil free air p...

Страница 218: ...M10 x 50 40 60 0 6 11 2 1 900 300 851 0 1 32 0 57 0 20 3 41 2 13 4 2 3 8 x 21 4 30 45 1 5 40 48 3 20 7 3 78 0 0 79 16 5 76 117 44 M10 x 50 40 60 0 7 2 2 375 300 1 329 0 1 32 0 45 0 16 33 8 5 17 8 2 3...

Страница 219: ...halves over the gasket making sure the housing keys engage the grooves Insert the bolt and turn the nuts finger tight 5Tighten nuts Tighten the nuts alternately and equally to the specified bolt torq...

Страница 220: ...DN mm In mm In mm Lbs Kg 1 1 315 11 4 0 3 25 33 4 25 0 1 11 4 1 660 1 0 4 32 42 2 25 0 2 11 2 1 900 1 0 5 40 48 3 25 0 2 2 2 375 1 0 7 50 60 3 25 0 3 21 2 2 875 1 1 0 65 73 0 25 0 4 3 O D 3 000 1 0 9...

Страница 221: ...k head bolts made of carbon steel with mechanical properties per ISO 898 1 Class 8 8 Hex nuts and bolts are zinc electroplated followed by a yellow chromate dip COATINGS q Rust inhibiting paint Color...

Страница 222: ...150 2 2 5 5 563 300 7 292 0 3 32 615 16 91 16 21 16 2 1 2 x 3 80 100 4 5 125 141 3 20 7 32 44 0 2 38 176 230 52 M12 x 76 110 150 2 0 61 2 O D 6 500 300 9 955 0 3 32 81 8 103 8 21 8 2 1 2 x 3 80 100 5...

Страница 223: ...alternately and evenly until fully tightened Caution Use of an impact wrench is not recommended because the torque output can vary significantly due to many variables including air pressure supply ba...

Страница 224: ...le RAL3000 or RAL9000 Series K 9 DRAIN CAP Nominal Size O D End to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 0 83 50 60 3 0 38 21 2 2 875 1 06 65 73 0 0 48 3 O D 2 996 1 06 76 1 76 1 0 48 3...

Страница 225: ...e NPT Outlet per ASME B1 20 1 E 9 DRAIN ELBOW Nominal Size O D Max Working Pressure s Center to End H Approx Wt Ea In DN mm In mm PSI bar In mm In mm Lbs Kg 11 4 1 660 300 23 4 13 4 0 7 32 42 2 20 7 6...

Страница 226: ...SAE J429 Grade 5 with a minimum tensile strength of 120 000 psi and heavy hex nuts of carbon steel conforming to ASTM A 563 Grade A or J995 Grade 2 Bolts and nuts are provided zinc electroplated as s...

Страница 227: ...6 1 20 7 21 22 0 4 8 20 8 159 225 51 M16 x 95 135 175 3 5 51 2 O D x 4 5 500 4 500 300 7 128 0 3 16 1 58 0 20 71 4 105 8 21 8 2 3 4 x 41 2 100 130 11 4 139 X 114 139 7 114 3 20 7 31 71 0 4 8 10 8 184...

Страница 228: ...ional q Other available options Example RAL3000 or RAL9000 Series ST 1 TEE Nominal Size O D Center to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 23 4 2 9 50 60 3 70 1 3 21 2 2 875 3 4 6 65 7...

Страница 229: ...Other available options Example RAL3000 or RAL9000 Series SE 1 90 ELBOW Nominal Size O D Center to End Approx Wt Ea In DN mm In mm In mm Lbs Kg 2 2 375 23 4 1 5 50 60 3 70 0 7 21 2 2 875 3 2 1 65 73 0...

Страница 230: ...SA UL and Canada cUL for steel and CPVC plastic pipe and Factory Mutual Engineering Approved 3 4 thru 8 Conforms to Federal Specifications WW H 171E Type 10 and Manufacturers Standardization Society S...

Страница 231: ...tallation practice of a retaining strap requires that the strap be held tightly and securely to all component parts of the assembly Therefore a locking mechanism of some kind such as the beveled locki...

Страница 232: ...bed herein must be installed and maintained in compliance with this document as well as with the applicable standards of the National Fire Protection Association in addition to the standards of any ot...

Страница 233: ...the wrench flats Torque sprinklers 7 to 14 ft lbs 9 5 to 19 0 Nm Recessed Pendent Sprinklers The Series TY FRB Recessed Pendent Sprinklers must be installed in accor dance with the following instruct...

Страница 234: ...their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Asso ciation e g NFPA 25 in addition to the standards...

Страница 235: ...d 175 F 79 C Yellow 200 F 93 C Green Notes 1 Listed by Underwriters Laboratories Inc UL as Quick Response Sprinklers 2 Listed by Underwriters Laboratories Inc for use in Canada C UL as Quick Response...

Страница 236: ...e into plaster board or ceiling tiles by gently pushing the ceiling product against the Pro tective Cap When ceiling installa tion is complete the Protective Cap is removed and the Cover Plate Retaine...

Страница 237: ...o shatter the glass bulb activating the sprinkler and allowing water to flow Installation The TYCO Series RFII 5 6 K factor Royal Flush II Concealed Pendent Sprinklers must be installed in accor dance...

Страница 238: ...d and the Deflector does not move up and down freely replace the entire Sprinkler Do not attempt to modify or repair a damaged sprinkler Step 7 When installing an Air and Dust Seal refer to Figure 5 o...

Страница 239: ...st liquid from its bulb Ref Installa tion Section Exercise care to avoid damage to sprin klers before during and after instal lation Replace sprinklers damaged by dropping striking wrench twist ing wr...