DC Inverter Duct Type Unit
21
①
. The vertical height of the drain hose should be 75mm or less so that it is
unnecessary for the drain port to withstand additional force.
Fig. 4.29
②
. When multiple drain hoses are used, their installation should be performed
as shown in the Figure below.
Fig. 4.30
4.5.2 Testing of Drain Piping
After piping work is finished, check if drainage flows smoothly.
As shown in the Figure, add approximately 1liter of water slowly into the drain
pan and check drainage flow during COOL running.
Fig. 4.31