background image

028-5009-04_LIT-R851V-E06-EN 

Sep-19 

RATIO SETTING 

( See also slave application section at the end ) 

First adjust the vernier stage ratio potentiometer. This will insure a smooth capacity rise of the total load. 
Example 1: 

The total unit has 100 kW divided in 10 equal stage of 10 kW. 

If only 10 kW is used as the modulating stage, then the heater would have 9 on/off mechanical stage plus 

one modulating stage. This modulating stage has the same value as all the other stage. 

Adjust the vernier stage ratio 

potentiometer to 100%. 

Example 2: 

The total unit still has 100 kW divided in 10 equal stage of 10 kW. 

If 20 kW are used as the modulating stage, then the heater would have 8 on/off mechanical stage plus one 

modulating stage. The modulating stage has twice the value as all the other stage. 

Adjust the vernier stage ratio 

potentiometer to 200%. 

 

 

TYPE OF VERNIER STAGE SETTING

 

The vernier stage output can be configured to operate either as a: 

 

Vdc pulsed output to activate an R810 power module 

 

0 to 10 Vdc analog output to activate an R820 SCR power controller. 

 

VERNIER STAGE WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not wire more than six R810 power module on the 

vernier stage output 

 

Respect the polarity between the R851 step controller 

board an the R810 power modules 

 

Connect 

to 

Connect 

COM 

to 

R810 

Vdc pulsed to activate R810 power modules 

-  + 

The green status LED on the master unit will cycle at 

the same rate as the time proportioning vernier output 

For more information, please refer to the R810 service 

manual 

Set the 

R820 SCR 

power controller to accept a 0 to 10 Vdc control signal input 

Switch 

#1, #2 & #3  O

ff 

Switch 

#4 On 

The intensity of the green status LED on the master unit is proportional to vernier output 
For more information, please refer to the R820 service manual 

R820 

SCR Power Controller 

ON 

ON

 

 

 

 

 

1  2  3   

I  NPUT CONT ROL

 

1       2       3       4              1       2       3       4       5     6

 

1 2 3 

 

 

 

150

 

 

 

VR2 

100 

200

 

RATIO(%)

 

Control Switch #2 Off 

Control Switch #2 On 

S

 

V

 

COM

 

0 to 10 Vdc analog output to activate R820 SCR power controller 

Отзывы: