Manual Identification 

 
Neuron ID of a device can also be entered manually through a commissioning or service tool. Neuron ID 
should be located on the Echelon chip of the device being commissioned. 
 
Figure 8 shows an example of a Manual Neuron ID request made through a commissioning tool. 
 

 

Figure 8: Manual Neuron ID request 

 

Tips And Things You Need To Know 

   

 

 

 

 

 

 

 

 

 

 

If the heartbeat is lost, the module will release the network sensor value for the Room Temperature 
(nviSpaceTemp) and the Outdoor Temperature (nviOutdoorTemp); 

 

The heartbeat parameter of a Tridium front-end should be set at the slowest configuration possible so 
that nviTimeStamp updates correctly; 

 

With any LNS Tools, nviTimeStamp should be set to refresh everyday or on power-up; 

 

Viconics recommend to use the provided Viconics format files as stipulated in the snivet per model table 
view 

 

 

Troubleshooting Section 

 

 

 

 

 

 

 

 

 

 

 

 

Error / Trouble 
Condition 

Possible Cause 

Solution 

The LON network has too many 
devices. 

Do not exceed the maximum number of 
devices and maximum length allowed 
by the EIA-485 specifications. 

Too many devices were installed 
without any repeaters. 

Repeaters need to be installed as 
specified in this document. 

The LON cable runs are broken 

Locate the break and correct wiring 

Thermostat does not 
come online

 

The thermostat does not have power 

Apply power to the thermostat 

 
Document Control 

 

 

 

 

 

 

 

 

 

 

 

 

 
Document Name: 

ITG-VT76x7-PIR-LON-E01 

Document Filename: 

ITG-VT76x7-PIR-LON-E01.pdf 

 

Revision 

Date 

Changes 

00 

May 30, 2008 

Initial release 

02 

Feb 06, 2009 

Added changes for new PID supported 80:00:C5:55:00:04:04:22 
Added revision history table for all VT76x7 PID’s 

 

 

 

 

 

 

 

 

 

 
 

Содержание PIR Ready7 VT76x7 Series

Страница 1: ...1 PIR Ready7 VT76x7 Series Programmable Non Programmable Thermostats For Commercial HVAC Applications LonWorks Integration Manual ITG VT760x7 PIR LON E01 028 6007 R1 Issue Date May 30 2008...

Страница 2: ...ic which will automatically switch occupancy levels from Occupied to Stand By and Unoccupied as required by local activity being present or not This advanced occupancy functionality provides advantage...

Страница 3: ...v 3 0 80 00 C5 55 00 04 04 13 Thermostat Objects VT76x7 Space Comfort Object Type nvoSpaceTemp SNVT_temp_p Configuration Properties Send Heartbeat Temperature Setpoints Minimum Send Time Receive Heart...

Страница 4: ...occupied_timer Unsigned Short x x 3 anticycle Unsigned Short x x 4 power_up_delay Unsigned Short x x 5 temporary_occ_time Unsigned Short x x 6 heating_stages_CPH Unsigned Short x x 7 cooling_stages_CP...

Страница 5: ...ation_setpoint SNVT_lev_percent x x 17 dehumidification_lockout_function Enumeration Set Used off_on_state_t x x 16 nciHvacType SNVT_hvac_type X X 17 nciSccModel UNVT_model_info_2 X X Associate with U...

Страница 6: ...midity_level SNVT_lev_percent x x effective_reset_humid_setpoint SNVT_lev_percent x x pi_humid_demand_output SNVT_lev_percent x x dehumid_output_active Enumeration Set Used off_on_state_t x x 24 nvoEf...

Страница 7: ...node to manually control occupancy modes or to override the scheduled occupancy Default Null Value OC_NUL 0xFF Valid Range 0 OC_OCCUPIED 1 OC_UNOCCUPIED 2 OC_BYPASS Not Used 3 OC_STANDY Not Used Occu...

Страница 8: ...he minimum deadband configuration value 2 F and nviSetpoint 70 F The resulting Occupied heating setpoint will equal 69 F which is derived from 70 F minus the minimum deadband configuration value of 2...

Страница 9: ...a sensor failure This output network variable is available to report the Space Comfort Controller status It combines the operating mode the capacity of heating and cooling used and an indication if a...

Страница 10: ...tion of the ToccTime nciGenOpts until reinitiated by either a transition of the local input or an update to nviOccManCmd This network variable output is used to report the Space Comfort Controller inp...

Страница 11: ...ctSetpt This output network variable is used to monitor the effective temperature setpoint which may depend on nciSetpoints nvoEffectOccup nviSetpoint and any local setpoint adjustment For example if...

Страница 12: ...100 F 12 to 37 5 C 73 5 F 23 C 02 standby_cool Not Used Not Used 03 unoccupied_cool 54 to 100 F 12 to 37 5 C 82 5 F 28 C 04 occupied_heat 40 to 90 F 4 5 to 32 C 70 F 21 C 05 standby_heat Not Used Not...

Страница 13: ...PEN number of events 2 or 4 2 progressive recovery enable 0 Off 1 Active 0 Off number of heating stages 1 1 Stage 2 2 Stages 2 number of cooling stages 1 1 Stage 2 2 Stages 2 rh frontal display 0 Off...

Страница 14: ...e the specified network variable outputs will automatically be updated Valid Range 0 sec To 6553 4 sec Setting nciSendHrtBt to 0 disables the Send Heartbeat mechanism Default Null Value 0 0 sec no aut...

Страница 15: ...ration Global Commands The following figure shows which objects from the thermostat can be monitored and commanded from the BAS front end Figure 1 Global commands from a BAS front end to a VT76x7 seri...

Страница 16: ...SccStatus cool_1 nvoSccStatus cool_2 nvoSccStatus heat_1 nvoSccStatus heat_2 nvoSccStatus Local_RH_level nvoRHStatus supply_RH nvoRHStatus effect_reset_RH_setpt nvoRHStatus PI_demand_humid_output nvoR...

Страница 17: ...vice distance 1600 feet 500 meters in free topology Polarity Polarity insensitive Multi drop Free Topology Termination for Free Topology Network Segment One RC network with Ra 52 3 1 1 8W Termination...

Страница 18: ...18 Maximum Number Of Devices Up to 64 transceivers are allowed per network segment If your network requires more than 64 transceivers a repeater is then required to extend your network...

Страница 19: ...ections describe the various terminators and terminations procedure Free Topology Network Segment In a free topology segment only one termination is required and may be placed anywhere on the free top...

Страница 20: ...unning Table 2 Status LED condition Software Files XIF When binding a node onto the network an XIF file is needed The XIF file has information that is used by the network management tool to help ease...

Страница 21: ...ltaneously the Yes button and the No button located on the keypad interface of a VT7600 device the program ID and the Neuron ID LonWorks Unique ID contained in the device are transmitted to the commis...

Страница 22: ...sh everyday or on power up Viconics recommend to use the provided Viconics format files as stipulated in the snivet per model table view Troubleshooting Section Error Trouble Condition Possible Cause...

Отзывы: