Parameter Variable
Name
Function
This configuration property helps the user identify the type of
equipment being monitored.
Valid Range:
Value
Identifier Name
HVAC Unit-
Type
Identifier
network input config
SNVT_hvac_type
nciHvacType
0
1
2
3
4
5
6
7
8
9
HVT_GENERIC –
Not Used
HVT_FAN_COIL
HVT_VAV –
Not Used
HVT_HEAT_PUMP
HVT_ROOFTOP
HVT_UNIT_VENT –
Not Used
HVT_CHIL_CEIL –
Not Used
HVT_RADIATOR –
Not Used
HVT_AHU –
Not Used
HVT_SLF_CONT –
Not Used
Generic
Fan Coil
Variable Air Volume Terminal
Heat Pump
Rooftop Unit
Unit Ventilator
Chilled Ceiling
Radiator
Air Handling Unit
Self-Contained Unit
This configuration property defines model number and software
version of the thermostat
Valid Range and Default values:
Sub
Name
Valid Range
Default value
01
Thermostat Model 00 = VT7657B1000E
17 = VT7607B1000E
Depend on model
being used
Thermostat’s
model number
network input config
UNVT_model_number
nciSccModel
02
Software Version
Unsigned short
Thermostat dependent
Maximum
Send Time
network input config
SNVT_time_sec
nciSendHrtBt
This configuration property defines the maximum period of time that
expires before the specified network variable outputs will automatically
be updated
Valid Range: 0 sec. To 6553.4 sec.. Setting nciSendHrtBt to 0
disables the Send Heartbeat mechanism.
Default Null Value : 0.0 sec (no automatic update)
Minimum
Send Time
network input config
SNVT_time_sec
nciMinOutTm
This configuration property defines the minimum period of time
between automatic network variable outputs transmissions.
Valid Range: 0 sec. to 6553.4 sec.. Setting nciRcvHrtBt to 0 disables
the Minimum Send Time mechanism.
Default Null Value : 0.0 sec (no minimum send time)
Minimum
Receive Time
network input config
SNVT_time_sec
nciRcvHrtBt
This configuration property is used to control the maximum time that
elapses after the last update to a specified network variable input
before the Space Comfort Controller starts to use its default values.
Valid Range: 0 sec. to 6553.4 sec.. Setting nciRcvHrtBt to 0 disables
the Receive Heartbeat mechanism.
Default Null Value : 0.0 sec (no failure detected)
Hardware or
Software
revisions
network input config
SCPT_maj_ver
nciMajVer
This configuration property defines the major module software
revisions.
Valid Range: 0 to 255
Hardware or
Software
revisions
network input config
SCPT_min_ver
nciMinVer
This configuration property defines the minor module software
revisions.
Valid Range: 0 to 255