Product Overview  

 

 

 

The VT76x7 PI thermostat family is specifically designed for single stage 
and multi-stage control of heating/cooling equipment such as rooftop and 
self-contained units with humidifier and/or dehumidifier. The product 
features an embedded complete humidity solution with an intuitive, menu-
driven, backlit LCD display that walks users through the programming steps, 
making the process extremely simple. Accurate temperature & relative 
humidity control is achieved due to the product’s PI time proportional control 
algorithm, which virtually eliminates temperature offset associated with 
traditional, differential-based thermostats. 

 

All models contain one digital input, which can be set by the user to monitor 
filter status, activate a remote temporary occupancy switch, and/or used as 
a general purpose service indicator. The two models contain a SPST auxiliary switch, which can be used to 
control lighting or disable the economizer function and a discharge air sensor input. 

 

The thermostats are also compatible with the new Viconics PIR cover accessories. Thermostats equipped 
with a PIR cover provide advanced active occupancy logic, which will automatically switch occupancy levels 
from Occupied to Stand-By and Unoccupied as required by local activity being present or not. This advanced 
occupancy functionality provides advantageous energy savings during occupied hours without sacrificing 
occupant comfort. All thermostats can be ordered with or without a factory installed PIR cover. 

 

 
The additional following documentation is available on 

www.viconics.com

 

Detailed information on the thermostat (VT76x7X5x00) is available in document 

LIT-VT76x7-PIR-Exx

 

PIR application information and examples, are available on document: 

APP-VT76-PIR-Guide-Exx

 

PIR cover installation information is available on document: 

PIR Cover Installation-Exx 

 

Contents 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• 

PID History Revision Table 

• 

Thermostat Objects 

• 

SNVTs and SCPTs Table Per Model 

• 

Input Network Variables (nvi’s) Description 

• 

Output Network Variables (nvo’s) Description 

• 

Configuration Properties (nci’s) Description 

• 

Integration - Global Commands 

• 

Integration - Graphic User Interface (GUI) Objects 

• 

Integration - Configuration Objects 

• 

Wiring Guide 

Overview 

Network Configuration 

Maximum Number Of Devices 

Maximum Cable Length 

Repeaters 

Terminators 

• 

Network Adapter 

• 

Software Files 

• 

RoHS and Non-RoHS APB and NXE Files 

• 

Device Identification 

• 

Tips And Things You Need To Know 

• 

Troubleshooting Section 

• 

Document Control 

 

Fig.1 VT76x7B Thermostat

 

Содержание PIR Ready7 VT76x7 Series

Страница 1: ...1 PIR Ready7 VT76x7 Series Programmable Non Programmable Thermostats For Commercial HVAC Applications LonWorks Integration Manual ITG VT760x7 PIR LON E01 028 6007 R1 Issue Date May 30 2008...

Страница 2: ...ic which will automatically switch occupancy levels from Occupied to Stand By and Unoccupied as required by local activity being present or not This advanced occupancy functionality provides advantage...

Страница 3: ...v 3 0 80 00 C5 55 00 04 04 13 Thermostat Objects VT76x7 Space Comfort Object Type nvoSpaceTemp SNVT_temp_p Configuration Properties Send Heartbeat Temperature Setpoints Minimum Send Time Receive Heart...

Страница 4: ...occupied_timer Unsigned Short x x 3 anticycle Unsigned Short x x 4 power_up_delay Unsigned Short x x 5 temporary_occ_time Unsigned Short x x 6 heating_stages_CPH Unsigned Short x x 7 cooling_stages_CP...

Страница 5: ...ation_setpoint SNVT_lev_percent x x 17 dehumidification_lockout_function Enumeration Set Used off_on_state_t x x 16 nciHvacType SNVT_hvac_type X X 17 nciSccModel UNVT_model_info_2 X X Associate with U...

Страница 6: ...midity_level SNVT_lev_percent x x effective_reset_humid_setpoint SNVT_lev_percent x x pi_humid_demand_output SNVT_lev_percent x x dehumid_output_active Enumeration Set Used off_on_state_t x x 24 nvoEf...

Страница 7: ...node to manually control occupancy modes or to override the scheduled occupancy Default Null Value OC_NUL 0xFF Valid Range 0 OC_OCCUPIED 1 OC_UNOCCUPIED 2 OC_BYPASS Not Used 3 OC_STANDY Not Used Occu...

Страница 8: ...he minimum deadband configuration value 2 F and nviSetpoint 70 F The resulting Occupied heating setpoint will equal 69 F which is derived from 70 F minus the minimum deadband configuration value of 2...

Страница 9: ...a sensor failure This output network variable is available to report the Space Comfort Controller status It combines the operating mode the capacity of heating and cooling used and an indication if a...

Страница 10: ...tion of the ToccTime nciGenOpts until reinitiated by either a transition of the local input or an update to nviOccManCmd This network variable output is used to report the Space Comfort Controller inp...

Страница 11: ...ctSetpt This output network variable is used to monitor the effective temperature setpoint which may depend on nciSetpoints nvoEffectOccup nviSetpoint and any local setpoint adjustment For example if...

Страница 12: ...100 F 12 to 37 5 C 73 5 F 23 C 02 standby_cool Not Used Not Used 03 unoccupied_cool 54 to 100 F 12 to 37 5 C 82 5 F 28 C 04 occupied_heat 40 to 90 F 4 5 to 32 C 70 F 21 C 05 standby_heat Not Used Not...

Страница 13: ...PEN number of events 2 or 4 2 progressive recovery enable 0 Off 1 Active 0 Off number of heating stages 1 1 Stage 2 2 Stages 2 number of cooling stages 1 1 Stage 2 2 Stages 2 rh frontal display 0 Off...

Страница 14: ...e the specified network variable outputs will automatically be updated Valid Range 0 sec To 6553 4 sec Setting nciSendHrtBt to 0 disables the Send Heartbeat mechanism Default Null Value 0 0 sec no aut...

Страница 15: ...ration Global Commands The following figure shows which objects from the thermostat can be monitored and commanded from the BAS front end Figure 1 Global commands from a BAS front end to a VT76x7 seri...

Страница 16: ...SccStatus cool_1 nvoSccStatus cool_2 nvoSccStatus heat_1 nvoSccStatus heat_2 nvoSccStatus Local_RH_level nvoRHStatus supply_RH nvoRHStatus effect_reset_RH_setpt nvoRHStatus PI_demand_humid_output nvoR...

Страница 17: ...vice distance 1600 feet 500 meters in free topology Polarity Polarity insensitive Multi drop Free Topology Termination for Free Topology Network Segment One RC network with Ra 52 3 1 1 8W Termination...

Страница 18: ...18 Maximum Number Of Devices Up to 64 transceivers are allowed per network segment If your network requires more than 64 transceivers a repeater is then required to extend your network...

Страница 19: ...ections describe the various terminators and terminations procedure Free Topology Network Segment In a free topology segment only one termination is required and may be placed anywhere on the free top...

Страница 20: ...unning Table 2 Status LED condition Software Files XIF When binding a node onto the network an XIF file is needed The XIF file has information that is used by the network management tool to help ease...

Страница 21: ...ltaneously the Yes button and the No button located on the keypad interface of a VT7600 device the program ID and the Neuron ID LonWorks Unique ID contained in the device are transmitted to the commis...

Страница 22: ...sh everyday or on power up Viconics recommend to use the provided Viconics format files as stipulated in the snivet per model table view Troubleshooting Section Error Trouble Condition Possible Cause...

Отзывы: