background image

98MANAL350   Rev. 

E

   1

0

/

10/

14

 

Connection Diagram: 

Electrical Connections: 

Red: + Signal 

Black: - Signal 

Green Wire: Case Ground 

Note: If the unit is certified for hazardous locations as Intrinsically Safe, use the enclosed connection diagram. 

INSTALLATION REQUIREMENTS & CAUTIONS 

1.

Care should be taken when removing the product with a packing knife or other sharp instrument.  Functional damage will occur
if the knife slices the connection wiring or sensing diaphragm.

2.

Each transmitter is supplied with a protective cover that should be on the sensing area at all times when the transmitter is not
installed.

3.

Internal damage may occur if the transmitter receives a serious shock due to being dropped or struck by a foreign object.

4.

Never stand the Model 350 Transmitter up or place it on a rough surface without a protective cover on the sensing area (cap,
boot, clean rubber mat, soft cloth, or foam).

5.

Cleaning in place is the recommended process that should be performed as the system or process permits.

6.

When shipped in quantities, units should be packaged individually to eliminate possible damage.

7.

All electrical & pressure connections should be compatible with the model specifications as outlined in the product installation
datasheet.

8.

Installation should occur only after electrical (input power) and line pressure is verified as being off and at zero.

9.

The product’s internal electrical circuitry is isolated from case ground. It is not recommended that the case or ground of the unit
be connected to the input, output or calibrate pins of the product or wiring system.  Ground loops and line noise will affect the
product’s performance.

10. At no time should an object be pressed against the sensing area to deflect the sensor (to test or simulate pressure), as on

some models permanent damage to the sensing diaphragm may occur.

11. This product cannot be used in sterilization systems as described in the 3A Sanitary Standard 7

4-06, Section E1.9

12. During product installation, the customer shall supply and verify that all o-rings, gaskets, or seals meet or exceed the

requirements of the 3A Sanitary Standard 74-0

6

.

ACCESSORIES - OPTIONAL EQUIPMENT 

  White Polypropylene Conduit Connection Box .......................................................... 004033.002 
  Polypropylene Conduit Connection Box with 8 Ft Cable Assy. ................................. 003667.003 
  Hinged Tri-Clamp - Size - 1.5 ” .................................................................................. 041513MHHM 
  Gasket (Buna-N) - Size - 1.5 ” ....................................................................................04140MP-U0 
  Gasket(Teflon) - Size - 1.5 ” ....................................................................................... 04140MP-GI 
  Hinged Tri-Clamp - Size - 2.0 ” .................................................................................. 042013MHHM 
  Gasket (Buna-N) - Size - 2.0 ” .................................................................................... 04240MP-U0 
  Gasket (Teflon) - Size - 2.0 ” ...................................................................................... 04240MP-GI 
  Hinged Tri-Clamp - Size - 2.5 ” .................................................................................. 042513MHHM 
  Gasket (Buna-N) - Size- 2.5 ” .....................................................................................04340MP-U0 
  Gasket(Teflon) - Size - 2.5 ” ........................................................................................04340MP-GI 
  Digital Indicator (Direct Mount) ………………..................…………..……....………… Consult Factory 

Содержание 350

Страница 1: ... 10 14 MODEL 350 SANITARY PRESSURE TRANSMITTER INSTALLATION MANUAL 3829 Forest Parkway Suite 500 Wheatfield NY 14120 Toll Free 1 800 688 0030 International 716 629 3800 Fax 716 693 9162 www viatran com solutions viatran com ...

Страница 2: ...ION The Model 350 has been pre set at the factory for the required output and is referenced to absolute zero full vacuum Once factory set the product should perform as indicated by the performance certificate and product labeling In all cases the zero and span cannot be externally adjusted hence any deviation from the factory settings would indicate damage to the sensor electronics model dependent...

Страница 3: ...allation datasheet 8 Installation should occur only after electrical input power and line pressure is verified as being off and at zero 9 The product s internal electrical circuitry is isolated from case ground It is not recommended that the case or ground of the unit be connected to the input output or calibrate pins of the product or wiring system Ground loops and line noise will affect the prod...

Страница 4: ...stomer disassembly would result in a loss of coverage under the warranty policy All Viatran products are able to be repaired at minimal cost if simple cleaning and precautions are taken in the handling and application of the product Older products returned for repair are updated to current specifications unless the repair cost would outweigh the cost of a new replacement model Products returned fo...

Отзывы: