Servicing
44
11.5
Pressure Losses of Chimney Flue Elements in Case of VIADRUS K4 Boiler Usage
Maximal pressure of fan 150Pa
Multi-piece Chimney Flue - Burnt Gases
K4GXH24XX
K4GXH33XX
VIADRUS Code
Code
DN
Name
Loss in Pa
20105
PPSB48
80
Angle piece 45°
1,1
2,0
20107
PPSB98
80
Angle piece 87°
1,7
2,8
20133
PPRM18
80
Tube 1m
3,4
5,7
20111
PPSAS8
80
Chimney plastic head - starr (a set]
2,5
4,2
Multi Piece Chimney Flue - Suction
VIADRUS Code
Code
DN
Name
Loss in Pa
20105
PPSB48
80
Angle piece 45°
0,8
1,3
20107
PPSB98
80
Angle piece 87°
1,2
1,9
20133
PPRM18
80
Tube 1m
2,5
3,6
Concentric Chimney Flue
VIADRUS Code
Code
DN
Name
Loss in Pa
20158
LPBK45
60/100
Angle piece 45°
5,3
7,8
20160
LPBK95
60/100
Angle piece 87°
7,5
11,1
20199
LPRK15
60/100
Tube 1m
21,9
32,8
20197
LPZTK5
60/100
LIK T-piece for air inlet
5
7,5
20235
LPASK5
60/100
LIK tube piece for façade chimney flue
10,5
17,1
20221
DPDS45
60/100
Roof extension (a set)
29,8
45,1
20159
LPBK48
80/125
Angle piece 45°
1,5
2,5
20161
LPBK98
80/125
Angle piece 87°
2,1
3,5
20202
LPRK18
80/125
Tube 1m
5,4
8,3
20198
LPZTK8
80/125
LIK T-piece for air inlet
1,5
2,4
20236
LPASK8
80/125
LIK tube piece for façade chimney flue
3,5
5,4
20225
DPDS48
80/125
Roof extension (a set)
9,1
14,0
20169
FVIA01
60/100-80/125
LIK boiler reducer
2
3,2
12
Commissioning
The entire installation shall comply with the regulations that are applicable for this equipment. The boiler shall be compatible with the local
connecting conditions (checking the parameters of the boiler with the information on the name plate). The boiler can only be commissioned
by organizations that are authorized and trained for this purpose by the manufacturer. The minimum pressure in the heating system is
0,8 bar. It is necessary to open all closing valves and make sure that no gas is leaking. Connect the boiler to the electric power mains. Check
the gas distribution line after the gas valve. Check the safety valve function. Then check the pump operation. During the operation of the boiler it
is necessary to check removal of the condensate from the boiler and also from the chimney lining, if applicable.
During the first start of operation of the boiler it is necessary to train the user in accordance with this manual and to hand over this
manual to the user.
Then it is necessary to perform:
-
inspection revision before commissioning,
-
inspection for any water leakages,
-
inspection of instrumentation and safety controls.