5.3.5 Setting the anti-cycling period (PR10)
This parameter is used to prevent frequent starting of the boiler to the heating system. This is the minimum
period of time for which the requirement for heating to the system will be ignored. The default setting is 3
min.
This value does not have any impact on executing the requirement for starting the boiler in case of a
requirement for heating of hot water.
The setting range is 0 – 600 s. The shown value needs to be multiplied by 6, i.e., 10 x 6 = 60 s
Screen
Button
pressing
time
Description
or
Switching to the servicing mode shall be done when the
boiler is turned on
10 s
Switch the boiler to the parameter setting mode by
simultaneous pressing of buttons 3, 4 and 5 for a period of
10 s
/
The screen will show PR / 01
Set the required parameter on the screen using button
3 or 4
/
Set the parameter PR / 10 on the screen using button 3 or 4
2s
Switch the boiler to the value setting mode by simultaneous
pressing of buttons 3 and 5 for a period of approx. 2 s .
The default setting for anti-cycling period is 3 min.
The setting range is 0 – 600 s. The shown value needs to
be multiplied by 6, i.e., 10 x 6 = 60 s
For switching back without changing the parameters
simultaneously press down buttons 4 and 5.
Press
shortly
To confirm the set value press shortly button 5 on the main
switch
10 s
To exit the setting mode simultaneously press down buttons
3, 4 and 5 for 10 s