Vexar 368STM-1 Скачать руководство пользователя страница 8

www.fmiproducts.com

56149J

8

VenTing inSTallaTion

Continued

Note: If there is a second story in the home, 

firestop spacer 30FS-8DM will be required. 

See Firestop Spacers on page 9.

PENETRATING ROOF

To maintain a 2" clearance to the pipe on a 

roof with a pitch, a rectangular opening must 

be cut.
1.  Determine center point through which pipe 

will penetrate roof.

2.  Determine  center  point  of  roof.  Pitch  is 

the distance the roof drops over a given 

span, usually 12". A 6/12 pitch means that 

the roof drops 6" for each 12" measured 

down from roof rafters.

3.  Use  roof  opening  chart  (Figure  10)  to 

determine  correct  opening  length  and 

flashing required.

4.  Remove shingles around opening mea

-

sured. Cut out this section.

5.  Add next sections of pipe until end pen

-

etrates roof line. Check to see that proper 

clearances are maintained. Extend chimney 

by adding sections of double wall pipe until 

pipe is minimum of 30" above highest point 

of roof cutout. Termination and chimney 

must extend a minimum of 36" above high

-

est point where it passes through roof.

16 

3

/

8

" Min.

(48.3 cm)

30" Min.

(76 cm)

2" Min.

(5.1 cm)

2" Min.

(5.1 cm)

2" Min.

(5.1 cm)

Opening "A"

PITCH

SLOPE

OPENING 

"A" MAx

FLASHING 

MODE NO.

Flat

17"

6F-8

0 - 6/12

26.6°

19

 1

/

8

 "

6F-8

6/12 - 

12/12

45°

24 

1

/

4

"

12F-8

Figure 10 - Determine Roof Opening

Figure 11 - Typical Offset Terminations (For Systems with 2 Elbow Sets, Minimum 

Height is 25 ft., Maximum Height for Any System is 40 ft.)

Return 

Elbow

Offset 

Elbow

Return 

Elbow

Offset 

Elbow

6' Max.

6' Max.

6' Max.

6' Max.

6' Max.

6' Max.

Return 

Elbow

Offset 

Elbow

Offset 

Elbow

Return 

Elbow

A

B

C

Offset 

Elbow

Ceiling 

Support Pipe

12S-8DM

Return 

Elbow

USING ELBOW OFFSETS (30E-8DM)

1.  To achieve desired offset, you may install 

combinations of 12", 18", 24", 36" and 48" 

length of double wall pipe (see offset chart 

and Figure 11).

IMPORTANT:

 If an exposed portion of chim

-

ney  is  greater  than  4  feet  above  roofline, 

use support wires to keep chimney secured. 

Support wires may be attached to outer pipe 

of chimney with screws provided screws do 

not penetrate inner flue pipe.

2.  Chimney  weight  above  offset  rests  on 

return  elbow.  Straps  must  be  securely 

nailed to rafters or joists (see Figure 12, 

details A and B, page 9).

Содержание 368STM-1

Страница 1: ...free log can only be installed in an aftermarket completion of sale not for purpose of resale from the manufacturer permanently located manufactured mobile home where not prohibited by local codes A...

Страница 2: ...or local distributor IMPORTANT Check HUD re quirementsbeforeinstallingthis fireplace Model 368STM is specifically designed for use in manufactured mobile homes This fireplace includes a manual contro...

Страница 3: ...ill make installation easier 4 An outside air kit is available with this fireplace see Outside Air Kit on page 5 WARNING Donotinstallthis appliance in a bedroom 24 37 1 2 20 1 2 10 1 4 53 1 2 17 1 2 4...

Страница 4: ...the full width and depth of fireplace 3 Set fireplace directly in front of opening and slide unit back until nailing flanges touch side framing 4 Check level of fireplace and shim with sheet metal if...

Страница 5: ...means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material see Figure 3 WARNING Hearthextension is to be installed only a...

Страница 6: ...tion air is accessed through mobile home floor using air kit modelAK 6 or a side wall using air kit model AK 6WI see Accessories on page 14 CAUTION Combustion air inlet ducts shall not terminate in a...

Страница 7: ...mble to firestop spacer An opening large enough to allow insertion of firestop thimble assembly will be required in the ceiling Attach firestop thimble assembly to ceiling ceiling joist using screws o...

Страница 8: ...mum of 36 above high est point where it passes through roof 16 3 8 Min 48 3 cm 30 Min 76 cm 2 Min 5 1 cm 2 Min 5 1 cm 2 Min 5 1 cm Opening A PITCH SLOPE OPENING A MAX FLASHING MODE NO Flat 0 17 6F 8 0...

Страница 9: ...4 46 1 4 1 23 3 4 49 1 4 1 1 27 3 4 56 3 4 1 30 60 3 4 1 1 33 66 1 1 36 71 1 1 38 1 4 75 2 41 1 4 80 1 4 1 1 1 45 86 3 4 2 46 3 4 89 1 2 1 1 1 51 97 1 1 53 1 4 101 2 1 56 1 4 106 1 4 2 59 1 4 111 1 2...

Страница 10: ...ions with slip sections Note Storm collar is required but can be installed after home is sited Figure 16 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Terminations Spark Arrestor Th...

Страница 11: ...al distance of 10 feet see Figure 19 10 2 Min 10 3 Min 2 Min 3 Min Level of Flue Gas Outlet Figure 19 10 Foot Rule Chimney Support Bracket Kit CSK 8DM If exposed portion of chimney is greater than fiv...

Страница 12: ...nt free appliance available through your local distributor Use only a 1 2 black iron pipe and appropriate fittings When installing a gas line a shutoff valve designed for installation outside the appl...

Страница 13: ...place When fireplace is in operation doors must be FULLY OPENED or FULLY CLOSED position only or a fire hazard may be created see Figure 23 A fireplace equipped with glass doors operates much differen...

Страница 14: ...ll to close and push to open Always open both handles before starting a fire This provides adequate outside combus tion air Close both handles when not in use to prevent cold air from entering the roo...

Страница 15: ...144 96 12 30 AccessorIES Continued SQUARE CHASE TOP TERMINATION ETL 8DM Optional OUtside air kit for side wall installation AK 6WI Hearth extension he 36 Thimble extensions TXL 8DM 43 TX 8DM 26 Vent...

Страница 16: ...have further questions about installation operation or troubleshooting If so contact Style Crest Inc at 1 800 231 4822 or write to Style Crest Service P O Box 19110 Wichita KS 67204 When calling or wr...

Отзывы: