2/4
G
IF SMI KNX 16
4. Technical data
General
Operating temperature:
°C
dry rooms
(free of condensation)
+5 °C (41 °F) to +45 °C (106 °F)
pollution index 2
Mounting:
DIN rail 35 mm
or equivalent
Dimensions (W × H × D):
mm
72 × 90.5 × 62 (4 SU)
Weight:
g
200
Binary inputs:
8
Motor outputs:
4
Connection data
Supply voltage:
VAC 230 ± 10 %
Hz
50
Cable:
2 wires (single or fine wire)
Wire crosssection:
mm
2)
2.5
Terminal tightening torque:
Nm
0.4
Fuse protection:
A
10
IP class:
IP
20
Electrical protection class:
III
NOTE!
The connection and the wiring of the local operation units and
the KNX bus must be carried out according to the current SELV
requirements.
I
Motor connection (outputs)
Motor type:
VAC SMI 230
VDC SMI LoVo 24
Leitung:
2 wires (single or fine wire)
Wire crosssection:
mm
2)
2.5
Terminal tightening torque:
Nm
0.4
5. Installation / Mounting
To mount the actuator proceed as follows:
– Place the module on the DIN rail in the desired position and lock in.
Local operation (inputs)
Voltage:
VDC 8
Current:
mA
2
Cable:
3 wires (single or fine wire)
Wire crosssection:
mm
2)
1.5
Terminal tightening torque:
Nm
0.25
Cable length:
m
max. 100
Operation via:
push button or
switch potentialfree contact
KNX
Bus connector:
mm
Ø 0.5 ... 0.8 (single wire)
Bus cable:
according to KNX standard
5.1 Electrical connection – Overview
Wiring diagram
X Power
NOTE!
The drives are not supplied via the actuator. The data sheets and
information of the drives are to be considered. Mixed operation
between AC and LoVo drives is not permitted.
I
Motor
Connect motors as follows:
Motor connection terminals
Destination
I+ / I
I+ and I of SMI line
I+ / I
I+ and I of SMI line
I+ / I
I+ and I of SMI line
I+ / I
I+ and I of SMI line
NOTE!
Communication to the SMI drives only works properly when
I+ and I are connected correct.
I
KNX-Bus
Connect the KNX bus connector to the KNX bus.
Supply voltage
Connect supply voltage to the motor control unit as follows:
Power
L
Phase 230VAC
N
Neutral conductor
Local operation
Several push buttons can be connected to one local operation input.
NOTE!
It is possible to connect one push button to several local oper
ation inputs.
This push button may only be connected to one SMI actuator.
I
Local operation inputs
Destination
Push button “UP”
Push button “DOWN”
+
Push button