IF SMI KNX 16

4. Technical data

General

Operating temperature: 

 

°C 

 

dry rooms 

(free of condensation)

+5 °C (41 °F) to +45 °C (106 °F) 

pollution index 2

Mounting:

DIN rail 35 mm 

or equivalent

Dimensions (W × H × D):

mm

72 × 90.5 × 62 (4 SU)

Weight:

g

200

Binary inputs:

8

Motor outputs:

4

Connection data

Supply voltage:

VAC 230 ±  10 %
Hz

50

Cable:

2 wires (single or fine wire)

Wire cross­section:

mm

2)

2.5 

Terminal tightening torque:

Nm

0.4

Fuse protection:

A

10

IP class:

IP

20

Electrical protection class:

III

NOTE!

The connection and the wiring of the local operation units and 

the KNX bus must be carried out according to the current SELV 

requirements.

I

Motor connection (outputs)

Motor type:

VAC SMI 230
VDC SMI LoVo 24

Leitung:

2 wires (single or fine wire)

Wire cross­section:

mm

2)

2.5 

Terminal tightening torque:

Nm

0.4

5.  Installation / Mounting

To mount the actuator proceed as follows:

 

– Place the module on the DIN rail in the desired position and lock in.

Local operation (inputs)

Voltage:

VDC 8

Current:

mA

2

Cable:

3 wires (single or fine wire)

Wire cross­section:

mm

2)

1.5 

Terminal tightening torque:

Nm

0.25

Cable length:

m

max. 100

Operation via:

push button or 

switch potential­free contact

KNX

Bus connector:

mm

Ø 0.5 ... 0.8 (single wire)

Bus cable:

according to KNX standard

5.1 Electrical connection – Overview

Wiring diagram

X Power

NOTE!

The drives are not supplied via the actuator. The data sheets and 

information of the drives are to be considered. Mixed operation 

between AC and LoVo drives is not permitted.

I

Motor

Connect motors as follows:

Motor connection terminals

Destination

I+ / I­

I+ and I­ of SMI line

I+ / I­

I+ and I­ of SMI line

I+ / I­

I+ and I­ of SMI line

I+ / I­

I+ and I­ of SMI line

NOTE!

Communication to the SMI drives only works properly when 

I+ and I­ are connected correct.

I

KNX-Bus

Connect the KNX bus connector to the KNX bus.

Supply voltage

Connect supply voltage to the motor control unit as follows:

Power

L

Phase 230VAC

N

Neutral conductor

Local operation

Several push buttons can be connected to one local operation input.

NOTE!

It is possible to connect one push button to several local oper­

ation inputs.

This push button may only be connected to one SMI actuator.

I

Local operation inputs

Destination

Push button “UP”
Push button “DOWN”

+

Push button