Subject to modifications.
© Vestamatic GmbH
Art.-Nr.:
3060 002 GB 0319 A03 • Vestamatic GmbH • Dohrweg 27 • D-41066 Mönchengladbach
• www.vestamatic.com
4/4
G
IF SMI KNX 16
The disposal of electrical equipment and batteries in household
waste is strictly forbidden.
The symbol (dustbin crossed out, in line with WEEE Appendix IX)
indicates separate collection of electrical and electronic products in
EU countries. Do not dispose of the device or battery in your house
hold waste. Ask your town or local council about the return and
collection systems available in your area to dispose of this product.
É
12. Disposal of waste
11. Warranty
Principally, the General Terms and Conditions of the manufacturer, Vestamatic
GmbH apply. The terms and conditions are part of the sales documents
and handed over to the operator upon delivery. Liability claims for personal
or material damages are excluded when they can be attributed to one or
more of the following causes:
– Unintended use of the product.
– Opening of the product by the customer.
– Improper installation, commissioning, or operation of the product.
– Noncompliance with the technical specifications.
– Nonobservance of the safety provisions and instructions of the Oper
ating Instructions.
– Operation of the product with improperly installed connections, defective
safety devices or improperly installed safeguards.
– Modifications to the product.
13. Service
/
Contact
Vestamatic GmbH
Dohrweg 27
D41066 Mönchengladbach / Germany
Tel.: +49 2161 / 29 4080
8. Troubleshooting
Fault
Rectification
Motor error –
Status LED for the corresponding
motor lights continuously “RED”.
– Check motor connection, motor cable, and motor.
Device does not communicate via
KNX.
– Check supply voltage
(LED ready for operation must light continuously „GREEN“).
– Check KNX bus voltage
(programming LED can be switched on and off via the programming button).
No local / manual commands are
executed.
– Check whether the corresponding output is in test mode (status LED for the output lights continuously
“GREEN”) – press the “M” button several times to exit the test mode (all status LEDs of the outputs do
not light continuously “GREEN”).
– Check whether a security lock is active (status LED for the output flashes “RED”); the triggering and
reset conditions for a security lock are defined in the ETS configuration by the system integrator.
– Check local operation inputs and / or KNX communication.
No central / automatic commands are
executed.
– Check whether the corresponding output is in test mode (status LED for the output lights continuously
“GREEN”) – press the “M” button several times to exit the test mode (all status LEDs of the outputs do
not light continuously “GREEN”).
– Check whether a security lock is active (status LED for the output flashes “RED”); the triggering and
reset conditions for a security lock are defined in the ETS configuration by the system integrator.
– Check whether an automatic lock is active (status LED for the output flashes “GREEN”) –; the triggering
and reset conditions for an automatic lock are defined in the ETS configuration by the system integrator.
– Check the KNX communication.
NOTE!
If the listed troubleshooting procedures do not lead to the desired result,
please contact the customer service.
I
9. Re-learn motor addresses
If the motor addresses shall be relearned (e.g. by a motor change), the
stored addresses can be deleted and relearned.
– Switch motor output to test mode by pressing test button “M” (status
LED of the output is permanently “GREEN”).
– Press test buttons “UP” and “DOWN” simultaneously for at least 5 s.
– New motors get a new address this way.
Reset the device to the factory setting
A reset must be carried out for resetting the device to the factory setting.
NOTE!
The reset will clear the entire configuration.
I
– Press test button “M” for at least 10 s (all status displays of the motor
outputs flash alternately “RED” and “GREEN”.
– Press test button “M” again within 10s and keep it pressed for at least
10 more seconds (all status LEDs of the motor outputs light continously
“RED”).
– Press test button “M” again within 10s and keep it pressed for at least
10 more seconds (the device is reset to factory settings).
– The restart of the device is shown by flashing the status LEDs of inputs
and motor outputs.
10. Maintenance
The device is maintenance free.