LaserSCANNER Installation Manual
VESDA
®
14
Version 1.3
6.11 Termination Card Details
Figure 9 Termination Card Details for 7 Relays
Figure 10 Termination Card Details for 12 Relays
6.12 Procedure to Terminate Wires to the Termination Card
Use the appropriate local wiring standards or use the following suggested procedure listed
below. Check Sections 6.13, 6.14 and 6.15 for specific information on terminal connections.
(a) Strip off 5 to 7mm (0.2 to 0.3in) of outer insulation from each wire.
(b) For multi-stranded wire only - Twist wire strands together.
Terminal A
Terminal B
Terminal C
Pin 1
Pin 11
Pin 1
Pin 1
Pin 10
Pin 12
VESDAnet
Socket
Terminal A
Terminal B
Terminal C
1 VESDAnet A+
1 Isolate (NO)
1 Fire 2 (NC)
2 VESDAnet A-
2 Isolate (C)
2 Fire 2 (C)
3 Shield
3 Isolate (NC)
3 Fire 2 (NO)
4 VESDAnet B+
4 Minor Fault (NO)
4 Fire 1 (NC)
5 VESDAnet B-
5 Minor Fault (C)
5 Fire 1 (C)
6 Shield
6 Minor Fault (NC)
6 Fire 1 (NO)
7 Power (+)
7 Urgent Fault (NO)
7 Action (NC)
8 Power (-)
8 Urgent Fault (C)
8 Action (C)
9 Power (+)
9 Urgent Fault (NC)
9 Action (NO)
10 Power (-)
10 Alert (NO)
10 GPI -
11 Alert
(C)
11
GPI
+
12 Alert
(NC)
GPI = General Purpose Input
FOK LED
Connector
Terminal A
Terminal B
Terminal C
1 VESDAnet A+
1 Urgent Fault (NO)
1 Fire 1 (NO)
2 VESDAnet A-
2 Urgent Fault (C)
2 Fire 1 (C)
3 Shield
3 Urgent Fault (NC)
3 Fire 1 (NC)
4 VESDAnet B+
4 Relay 1 (NO)
4 Relay 12 (NO)
5 VESDAnet B-
5 Relay 1 (C)
5 Relay 12 (C)
6 Shield
6 Relay 2 (NO)
6 Relay 11 (NO)
7 Power (+)
7 Relay 2 (C)
7 Relay 11 (C)
8 Power (-)
8 Relay 4 (NO)
8 Relay 10 (NO)
9 Power (+)
9 Relay 4 (C)
9 Relay 10 (C)
10 Power (-)
10 Relay 5 (NO)
10 Relay 9 (NO)
11 Relay 5 (C)
11 Relay 9 (C)
12 Relay 7 (NO)
12 Relay 8 (NO)
13 Relay 7 (C)
13 Relay 8 (C)
14
GPI
-
15
GPI
+
Terminal A
Terminal B
Terminal C
Pin 1
Pin 1
Pin 1
Pin 10
Pin 13
Pin 15
VESDAnet
Socket
GPI = General Purpose Input
FOK LED
Connector