LaserSCANNER Installation Manual 

VESDA

®

 

20 

Version 1.3 

8. Preliminary 

System 

Checks 

Perform the following preliminary system Setup and checks before commissioning. 

 

(a)  Logging onto the system with a PC or a LCD Programmer. See Section 8.1. 

 

(b)  VESDAnet communication checks.  See section 8.2 

 

(c)  Normalise the airflow. See section 8.3 

 

(d)  Basic pass/fail smoke test. See section 8.4 

 

8.1  Logging On to the System 

 

Check with your distributor for the default User Levels and PIN numbers to log on to the system. 

Fault code 25 or 26

 is generated when a LCD Programmer or a PC-Link HLI device is 

connected to the VESDAnet socket. This fault clears when the programming device is 
disconnected from the detector. 

 

Procedure 

LCD Programmer 

Module 

Hand Held LCD 

Programmer 

PC Programmer 

Connecting the 
programming 
device to a 
Detector or to a 
VESDAnet 
socket. 

No physical connection 
required 

Plug the LCD 
Programmer cable into 
the VESDAnet socket on 
the Termination card or 
to a remote terminal. 
Refer to Figure 5 for 
location of the VESDAnet 
socket on the 
Termination Card. 

Connect the PC via a 
PC-Link HLI device to 
the VESDAnet socket on 
the Termination Card or 
to a remote terminal. 
Refer to Figure 5 for 
location of the VESDAnet 
socket on the 
Termination Card. 

Logging onto 
the system. 

Press any programmer 
key to display the Logon 
screen.  

Press any programmer 
key to display the Logon 
screen. 

Run VConfig Basic or 
VConfig Pro program 
from the PC. 

Enter your 
Access Level 
and PIN 
Number. 

Use the Programmer 
keys to enter your 
access level and PIN 
number. Press 

 when 

completed. 

Use the Programmer 
keys to enter your 
access level and PIN 
number. Press 

 when 

completed.  

Enter your Access Level 
and PIN Number when 
the Logon screen 
appears. 

 

8.2  VESDAnet Communication Check  

 

Note:   

This test verifies the VESDAnet system is functioning correctly and all devices 
connected on VESDAnet

 

are communicating. Write down the VESDAnet number for 

each detector, programmer and display module. The location of the VESDAnet number 
for the detector is shown in Figure 5. The programmer and display modules have this 
number located at the bottom left hand side of the front face.  

 

If any of the listed VESDAnet numbers and devices are incorrect, check the 
VESDAnet wiring to all devices.

 

 

Procedure 

LCD Programmer 

PC Programmer 

Display the 
VESDAnet numbers. 

• 

Select Show Wiring Order 

• 

Read the displayed devices and 
VESDAnet numbers. 

• 

Check the details with your list. 

 

• 

Select the Device Tree command 
from the View menu. 

• 

From the Device Tree window, 
click on all the + signs to expand 
the tree. 

• 

Check all the listed devices and 
VESDAnet numbers against your 
list. 

Содержание LaserSCANNER VLS-200

Страница 1: ...V VE ES SD DA A LaserSCANNER INSTALLATION MANUAL VLS Models VLS 200 VLS 204 VLS 214 VLS 300 VLS 304 VLS 314 VLS 600 VLS 700 October 2005 Version 1 3 ...

Страница 2: ...not installed and used in accordance with the instruction may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception the user is encouraged to try to correct the interference by one or more of the following measures Reorientate o...

Страница 3: ...the Air Sampling Pipe 13 6 10 Cabling Using Glands and Conduits 13 6 10 1 Using Glands 13 6 10 2 Using Conduits 13 6 11 Termination Card Details 14 6 12 Procedure to Terminate Wires to the Termination Card 14 6 13 Terminating the Power Wires to the Termination Card 15 6 14 Connecting the VESDAnet Wires to the Termination Card If required 15 6 15 Terminating the Relay Wires to the Termination Card ...

Страница 4: ...ly be installed by VESDA accredited personnel The performance of the system depends on the pipe network designed for the site Any alteration to the pipe network may alter the performance of the system The ASPIRE design tool is to be used to verify the suitability of any pipe network design and subsequent alterations ASPIRE is available from your distributor or local Vision office The IP rating for...

Страница 5: ...SCANNER with Blank Plates 3000rpm 5 76 7 44 240 310 LaserSCANNER with Blank Plates 3500rpm 6 96 8 64 290 360 LaserSCANNER with Blank Plates 4000rpm 7 68 9 12 320 380 LaserSCANNER with Blank Plates 4200rpm 8 16 9 6 340 400 Programmer Module 1 08 Backlight Off 1 44 Backlight On 45 Backlight Off 60 Backlight On Display Module Only 1 44 2 64 60 110 Table 1 Power and Current Consumption for LaserSCANNE...

Страница 6: ...x NO NC contacts Alert Action Fire 1 Fire 2 Maintenance Urgent Fault and Isolate First Alarm Sector 1 to 4 and Scan 10 x NO 2 x NO NC contacts IP Rating IP30 Cable Access 8 x 25mm 1in knockouts in various positions Cable Termination Screw terminal blocks 0 2 2 5sq mm 30 12 AWG Sensitivity Range 0 005 to 20 00 obs m 0 0015 to 6 25 obs ft Threshold Setting Range Alert 0 005 1 990 obs m 0 0015 0 6218...

Страница 7: ... in mm in of LaserSCANNER with Mounting Bracket Rear View Normal Orientation Note Remove the centre pages of this manual for installation template We strongly recommend the use of this mounting bracket 51 0 2 0 35 0 1 37 21 0 0 83 CE 350 13 8 209 8 24 EP 77 5 3 05 12 0 0 47 207 8 15 28 5 1 12 Mounting Bracket Bridge and Lance 225 8 9 200 7 87 319 12 56 ...

Страница 8: ...gure 2 Dimensions in mm in for the LaserSCANNER 26 0 1 02 34 1 33 26 0 1 02 350 13 8 35 1 37 45 0 1 77 34 1 33 34 1 33 34 0 1 33 Inlet Air Ports CE TOP VIEW RIGHT HAND SIDE VIEW LEFT HAND SIDE VIEW FRONT VIEW 28 5 1 12 CP CE 225 8 9 26 0 1 02 25 4 1 0 125 4 9 BOTTOM VIEW 141 4 5 58 26 0 1 02 CE Exhaust Air Port 35 1 37 45 0 1 77 20 2 0 88 ...

Страница 9: ...mption details NORMAL LOAD 24 V DC FULL ALARM LOAD 24 VDC EQUIPMENT LOAD mA QTY TOTAL ma LOAD mA QTY TOTAL ma LaserSCANNER No display programmer Display Module Programmer Module Remote Display Other 24V loads TOTAL mA TOTAL mA X X STANDBY HOURS ALARM HOURS X 1 06 STANDBY CAPACITY mAHr ALARM CAPACITY mAHr TOTAL CAPACITY STANDBY ALARM mAHr DIVIDE BY 1000 MULTIPLY BY BATTERY FACTOR 1 25 AHr Table 2 C...

Страница 10: ...e selected mounting location is suitable to fit the detector by test fitting the LaserSCANNER onto the actual mounting position or use the drilling template supplied with this manual Ensure there is 150mm of clear space around the air inlet exhaust and cable entry ports to allow for pipe and cable entry e Verify that the cable entry points and the sampling air pipes are at its correct locations f ...

Страница 11: ...front cover is to be separated from the enclosure do the following i On the rear of the front cover or on the enclosure side twist the plastic strap 90 and slip strap out through slot ii Locate the cable loom that connects the central processor card to the back of a display or programmer module that is located on the front cover On the back of the programmer or display module disconnect this cable...

Страница 12: ... 1mm flat blade screwdriver into gap between module and front cover E Refer to Figure 4 d Gently lever screwdriver to lift out modules e Rotate modules 180 and gently re insert into the same compartment until modules are flush with the front cover Refer to Figure 3 for orientation Ensure the metal fingers are located on the exterior of the Display Programmer f Re connect the cable loom to the sock...

Страница 13: ...on and remove the appropriate plug with a screwdriver If the side exhaust is to be used perform the following a Punch out the knockout hole located on the left side of the enclosure with the ball end of a small hammer or a screwdriver A b To remove the plug B insert a screwdriver into the slot on the plug and turn c Run a 25mm 1in pipe through the side hole and insert the pipe into the exhaust por...

Страница 14: ...the required orientation for the LaserSCANNER Refer to Figure 3 for orientation b Place the three bridges located on the rear of the detector onto the three lances located on the mounting bracket Refer to Figure 8 c Push the detector downwards until it locks onto the lances and engages the fitting dimples d Check the unit does not slip off its bracket e To remove push the detector upwards and pull...

Страница 15: ... Do not remove the plugs from the inlet ports if the ports are not used c Insert the pipes into the inlet and or exhaust ports ensuring a firm fit DO NOT glue these pipe connections d Pipe the exhaust air where necessary Caution DO NOT GLUE THE AIR INLET AND EXHAUST PIPE CONNECTIONS Glued connections make disconnecting the sampling air pipes from the LaserSCANNER extremely difficult during mainten...

Страница 16: ...2 NO 4 VESDAnet B 4 Minor Fault NO 4 Fire 1 NC 5 VESDAnet B 5 Minor Fault C 5 Fire 1 C 6 Shield 6 Minor Fault NC 6 Fire 1 NO 7 Power 7 Urgent Fault NO 7 Action NC 8 Power 8 Urgent Fault C 8 Action C 9 Power 9 Urgent Fault NC 9 Action NO 10 Power 10 Alert NO 10 GPI 11 Alert C 11 GPI 12 Alert NC GPI General Purpose Input FOK LED Connector Terminal A Terminal B Terminal C 1 VESDAnet A 1 Urgent Fault ...

Страница 17: ...VESDAnet Wires to the Termination Card If required a Refer to Figure 9 or 10 for the VESDAnet terminal location on the termination card b Connect the VESDAnet wires as shown in Figure 12 This diagram is only an example for five detectors This wiring method is similar for two or more detectors c Maintain the wiring polarity throughout the network Do not leave any VESDAnet terminals unconnected NOTE...

Страница 18: ...for the relay terminals location on the termination card b Connect the relay wires to the terminals as per Figure 14 and your site requirements Detector 3 Terminal A 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 Shield A A Shield B B Detector 1 Terminal A Detector 2 Terminal A Detector 4 Terminal A Shield B B Shield A A Shield A A B Shield Shield B B Shield Shield A A B B Detector 5 ...

Страница 19: ...7 6 5 4 3 NC NO NO NC C 2 1 C NO Minor Fault Relay 2 Urgent Fault Relay 3 NC Terminal Pins location for 12 Relays Default Relay Assignments Minor Fault Relay 2 Terminal B C Alert Relay 4 11 10 C NO NO 9 8 7 6 5 4 3 NO NO C NC C 2 1 C NO Urgent Fault Relay 3 Isolate Relay 1 12 NO Action Relay 5 Fire 2 Relay 7 13 C Terminal C First Alarm Sector 4 Relay 11 Scan Relay 12 7 6 5 4 3 NO NO C NC C 2 1 C N...

Страница 20: ...ection 8 d Close up the LaserSCANNER and secure the cover with the four screws e Re attach the blank plate and screw covers to its location 6 17 Pipe Bonding Check a Check all the pipe joints are fully sealed and bonded to eliminate unwanted air leaks b Check the pipe joints at the air inlet ports of the LaserSCANNER ARE NOT bonded and the pipe fits firmly into the air inlet socket c Check all pip...

Страница 21: ...all power wires are secured to its terminals Check the polarities of the power wires are correctly terminated h On power up The aspirator starts up and air is felt flowing out of the exhaust port If a Programmer module is fitted the VESDA name will appear on the LCD screen If a Display module is fitted the following indicators are lit Fire Alarm Threshold indicators Smoke Threshold Levels on Bar G...

Страница 22: ...e VESDAnet socket on the Termination Card Logging onto the system Press any programmer key to display the Logon screen Press any programmer key to display the Logon screen Run VConfig Basic or VConfig Pro program from the PC Enter your Access Level and PIN Number Use the Programmer keys to enter your access level and PIN number Press when completed Use the Programmer keys to enter your access leve...

Страница 23: ... the value as per the ASPIRE calculation for that site In the same window that displays the Airflow tab click on the Aspirator tab Change the Aspirator RPM to the value as per the ASPIRE calculations Click on the Apply button Normalise the Airflow Wait for 11 minutes to complete Normalising Select Setup by Zone Zone Number Detector Air Flow Normalise Normalise Start Select the Normalise Airflow co...

Страница 24: ...ront panel lights up Smoke bar graph indicator lights up showing smoke level 2 digit indicator shows smoke intensity level when Smoke Level is selected Select Setup by Zone Zone Number Detector Status and check the smoke level value Alarms reported in Status menu Sounding device on the Detector beeps Smoke alarm displays on the Active Events List window After the smoke has cleared Reset the Detect...

Страница 25: ...let ports Note The pipes must not be glued 4 Have the power wires been connected to the correct terminals on the termination card 5 Have the alarm signalling wires been terminated to the correct terminals on the termination card 6 Have the VESDAnet wires been connected to the correct terminals on the termination card 7 Has the plug at the exhaust port been removed and the exhaust pipe if fitted no...

Страница 26: ...d replacement product covered under this warranty will be furnished on an exchange basis and will at the option of Vision Systems either be new equivalent to new or reconditioned Returned parts and products to Vision Systems becomes the property of Vision Systems 5 This warranty does not cover the repair or damage to the product resulting from negligence or misuse improper storage or handling of t...

Страница 27: ... 3149 Australia Ph 61 3 9211 7200 Fax 61 3 9211 7201 Free Call 1 800 700 203 Vision Fire Security 700 Longwater Drive Norwell MA 02061 USA Ph 781 740 2223 Toll Free 800 229 4434 Fax 781 740 4433 Vision Fire Security Vision House Focus 31 Mark Road Hemel Hempstead Herts HP2 7BW UK Ph 44 1442 242 330 Fax 441442 249 327 Part Number 19148 Revision 05 ...

Отзывы: