Heatline - Duct mounted Heater with controls
Installation, Operation and Maintenance Manual
VES Andover Ltd. Eagle Close, Chandlers Ford Ind. Est, Eastleigh, Hampshire, SO53 4NF
Tel: 08448 15 60 60 Fax: 02380 26 12 04 E-mail: [email protected] Web: www.ves.co.uk
9.15 Technical
data
Operating voltage
AC 230 V +10/ -15%
Frequency
50/ 60 Hz
Power consumption
Max. 18 VA
Fan control rating
Q1, Q2, Q3-N
AC 230 V, max.5(4) A
Control outputs
Y1, Y2, Y3, Y4-N
AC 230 V, max.1 A
Multifunctional inputs
X1 - M/X2 - M
Temperature sensor input
Type
Digital input
Operating action
Contact sensing
Insulating against mains
D1-GND
Operating action
Contact sensing
Insulating against mains
Function input
External temperature sensor, fault contact
Selectable
/ !! *
Heating mode
(P30)
2 K (0.5...6 K)
Set point setting and setting range
Comfort mode
Energy saving mode
Protection
(P08)
(P11-P12)
(P65-P66)
21 °C (5...40 °C)
15 °C /30 °C (OFF, 5...40 °C)
8 °C/ OFF (OFF, 5...40 °C)
Built - in room temperature sensor
Measuring range
Accuracy at 25°C
Temperature calibration range
0...49 °C
< + 0.5 K
+ 3.0 K
Settings and display resolution
Setpoints
Current temperature value displayed
0.5 °C
0.5 °C
Operation
Climatic controls
Temperature
Humidity
As per IEC 721-3-3
Class 3K5
0...50 °C
< 95% r.h
Transport
Climatic controls
Temperature
Humidity
Mechanical conditions
As per IEC 721-3-2
Class 2K3
-25...60 °C
< 95% r.h
Class 2M2
Storage
Climatic controls
Temperature
Humidity
Class 1K3
25...60 °C
< 95% r.h
As per IEC 721-3-1
CPEL2011 (NTC)
Selectable (NO/NC)
DC 0...5 V, max 5 mA
N/A, mains potential
Selectabe (NO/NC)
SELV DC 6...15V, 3...6 mA
3.75 kV, reinforced insulation
Controls
9
Continued