8

ORIGINAL INSTRUCTIONS

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est. Eastleigh Hampshire SO53 4NF
Tel: 023 8046 1150  Fax: 023 8026 1204  E-mail: [email protected] Web: www.ves.co.uk

    EVHR Hybrid Ventilation Unit

Installation, Operation and Maintenance Manual

Continued

Ecovent

®

 EVHR 

units are offered in a LPHW heating varient. The Coil section is secured to the fan

section using self-locating joining brackets. The coil section is square in profile and can be
reconfigured to allow alternate coil connection positions relative to the fan section should that
be required.

Coils should be piped according to any relevant local codes of practice. As standard EVHR coils
are supplied with a 1” BSP connection. All external piping is to be supported independently from
the coil. The flow connection is nearest the bottom of the unit.

It is important the connecting pipework route does not obscure any of the fan section access.

It is important that coils are protected against damage from extreme weather conditions during
the winter season. If the water is allowed to freeze in the coil system,
damage may occur potentially bursting pipes and resulting in emergency problems.
EVHR LPHW units are fitted with a coil temperature sensor as standard, ensuring that boilers
run continuously in low ambient temperatures can help to prevent this.

On 

Ecovent® EVHR/ -W

 units, a Low Pressure Hot Water (LPHW) coil will be installed. The coils

are normally suitable for low pressure hot water with a range of between 80 ~ 60 °C flow and
between 70 ~ 40 °C return temperature. The coil should be regularly vented so as to avoid
potential air locks, resulting in a fall off of duty.

It is recommended that a check be made as to whether any treatment is required to the water
supply for prevention of corrosion and scaling of the equipment. Information regarding the
necessary action to be taken can be obtained from the relevant Local Water Supply Authority.

Repositioning the coil section is best done 

BEFORE 

installing the unit at roof/ceiling level.

When repositioning the coil section the casework for both sections 

MUST 

be fully supported.

A supply temperature sensor is positioned within the coil section and hardwired to the control
panel, separating the sections too far apart may result in damage to critical components.
A service loop has been provided to aid rework. Ensure the sensor cable is stowed within the
coil section when reassembling the sections so as not to trap the cable between the joints.

Installation

4

EVHR/W

LPHW Coil Units

Important

Caution

Important

Caution

Содержание Ecovent EVHR

Страница 1: ...lectric current and high voltages Indicates hazards that require safety advice for personnel or potential unit property damage Indicates important information page Introduction 1 Nomenclature 2 Receip...

Страница 2: ...5 Fan Size 3 4 Sequential 6 Phase 1 230V 50Hz Single Phase 7 Main Heating Null No Heating W LPHW Coil E Electric Heater Battery 8 Main Filter Null No filter 9 Control Panel Section Null No Controls CP...

Страница 3: ...fitted or steps taken to prevent this It is the installer s responsibility to ensure that access panels are not obstructed in any way Safe working access for maintenance must be provided in accordance...

Страница 4: ...ontinued Ecovent EVHR units are designed to be mounted flush against the underside of the ceiling slab connected to a purpose made terminal or turret The connecting duct needs to be split so as to dif...

Страница 5: ...46 1150 Fax 023 8026 1204 E mail vesltd ves co uk Web www ves co uk EVHR Hybrid Ventilation Unit Installation Operation and Maintenance Manual Continued Installation 4 Key installation components Fan...

Страница 6: ...uded as part of the unit sealing only When moving assembled units ensure that ALL sections are fully supported Bracket Fixings Finishing Flange Moun ng Bracket Ecovent EVH units feature fresh air supp...

Страница 7: ...pendently supported by structural trimmers in accordance with local building regulations in order to protect plant weight and support any service personnel The EVHR turret is designed to be mounted ho...

Страница 8: ...W units are fitted with a coil temperature sensor as standard ensuring that boilers run continuously in low ambient temperatures can help to prevent this On Ecovent EVHR W units a Low Pressure Hot Wat...

Страница 9: ...ng care with the supply sensor cable separate the sections If rotating the coil section 90 reposition the coil section joing bracket to the next face as shown in fig 12 This bracket repositioning is n...

Страница 10: ...tions to match the required configurationas shown in fig 13 again take care with the sensor cable If at floor level this is eassiest to acheive by lifting and rotating the fan section Installation 4 C...

Страница 11: ...ough the building installation device and a dedicated isolated power supply with overload protection to account for motor start up currents Do not connect any unit to an electrical supply voltage outs...

Страница 12: ...Eastleigh Hampshire SO53 4NF Tel 023 8046 1150 Fax 023 8026 1204 E mail vesltd ves co uk Web www ves co uk EVHR Hybrid Ventilation Unit Installation Operation and Maintenance Manual Standard Wiring F...

Страница 13: ...t Eastleigh Hampshire SO53 4NF Tel 023 8046 1150 Fax 023 8026 1204 E mail vesltd ves co uk Web www ves co uk EVHR Hybrid Ventilation Unit Installation Operation and Maintenance Manual Standard Wiring...

Страница 14: ...Healthy indication will stop illuminating until the unit resumes normal operation The Open windows indication shall illuminate when the external temperature reaches a suitable level to encourage manu...

Страница 15: ...as the wind and elements may cause moving parts to windmill In general this series of units require little maintenance In the unlikely event of component failure spares are available from stock at VES...

Страница 16: ...using 4No M6 fixings To remove the fans ensure the unit is fully isolated and that any moving components have come to a halt Remove both side access panels Separate the connecting fan plug and socket...

Страница 17: ...be switched ON for minimum of two hours every month to remove any moisture that may have condensed within the motor The fan motors are maintenance free due to the use of ball bearings with life long...

Отзывы: