To contact Vertiv Technical Support: visit www.VertivCo.com
© 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names,
trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no
responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
LIEBERT® PSP
TM
Quick Installation Guide
4
590-1631-501A\SLI-23285_REV1_11-17
SPECIFICATIONS
MODEL NUMBER
PSP500MT3-230U
PSP650MT3-230U
Capacity (VA/W)
500/300
650/390
Net Weight, kg (lb.)
3.9 (8.6)
Shipping Weight, kg (lb.)
4.8 (10.6)
Dimensions - W x D x H, mm (in.)
87 x 215 x 251 (3.4 x 8.5 x 9.9)
Mains Voltage
160-287VAC
Frequency
50/60Hz ±5Hz
Output Voltage (Mains Normal)
Typical 160-287VAC
Output Voltage (Battery Operation)
230VAC ±5%
On-Battery Wave Form
Stepped sine-wave
VRLA Battery Type - VDC x Ah x Quantity
12V x 7.2Ah x 1
12V x 7.2Ah x 1
Typical Recharge Time
6-8 hours to 90%
Battery Run Time
See Load Autonomy table below
Audible and Visual
Audible alarm / LED
Backup Sockets
IEC 320 C13 (3)
Surge Sockets
IEC 320 C13 (1)
Operating Temperature, °C (°F)
0 to 40 (32 to 104)
Storage Temperature, °C (°F)
-15 to 40 (5 to 104)
Storage Temperature, °C (°F)
-15 to 40 (5 to 104)
Operating / Storage Relative Humidity
0%-90%, non-condensing
EMI Classification
Class B
AGENCY
Safety
IEC/EN/AS 62040-1-1
EMC
EN 62040-2:2005 Class B
IEC 61000-4-2 Electrostatic discharge
IEC 61000-4-3 Radiated E-RFI fields
IEC 61000-4-4 Fast E transients
IEC 61000-4-5 Surges/Lightning
IEC 61000-4-6 Conducted RFI
Transportation
ISTA Procedure 1A Certification
LOAD AUTONOMY
Liebert PSP 230V 500VA-650VA
LOAD (WATTS)
500VA
650VA
50
55
56
100
18
19
150
12
12
200
8
8
250
5
5
300
N/A
4
350
N/A
3
NOTE:
The Liebert PSP is compliant with the Restriction
of Hazardous Substances Directive (ROHS), prohibiting
use of six hazardous materials manufacturing
of electronics, including lead-free solder.
NOTE:
: All run times are in minutes, assume fully
charged batteries and are typical at 25°C (77°F) with
resistive loads.