LIEBERT® PSP

TM

Quick Installation Guide

590-1631-501A\SLI-23285_REV1_11-17

   

3

REPLACING THE BATTERY

Servicing of batteries should be 

performed or supervised by 

personnel knowledgeable about 

batteries and required precautions.
When replacing batteries, replace 

with the same type and size battery.

CAUTION: 

Do not dispose of 

batteries in a fire. The batteries may 

explode.

CAUTION: 

Do not open or mutilate 

batteries. Released electrolyte is 

harmful to the skin and eyes. It is 

toxic.
This product is designed for IT 

power systems with 230V.

1.  Opening the PSP outer 

case

Turn off all connected loads, then 

turn off the UPS and unplug the 

input power cord. (Batteries are 

NOT hot-swappable.)
Carefully lay the UPS on its left 

side, as shown in the illustration 

to the right.
Use a #1 Phillips head 

screwdriver to remove the four 

screws from the right-side cover, 

then pull up the right-side cover 

and remove it.

2.  Removing the old battery

CAUTION: 

Risk of electric 

shock. 

Remove the black wire from the 

negative (-) terminal and the red 

wire from the positive (+) 

terminal.
Gently remove the battery from 

the UPS.

3.  Connecting the 

replacement battery

Verify that the replacement 

battery matches the dimensions 

and battery specifications.
Connect the PSP battery leads to 

the new battery. Be sure to 

reconnect the red wire to the 

positive (+) terminal and the black 

wire to the negative (-)terminal.

NOTE: 

Small sparks may occur 

at the battery connectors during 

reconnection. Take care not to 

short-circuit the positive and 

negative battery terminals while 

replacing the battery.

Place the battery in the UPS.

4.  Reassembling the PSP 

outer case

Ensure correct alignment of 

front panel, then reattach the 

right-side cover.
Evenly tighten the four screws 

from Step 1. (DO NOT 

overtighten the screws.)
Dispose of the old battery 

properly at an appropriate 

recycling facility.

TROUBLESHOOTING

FAULT

POSSIBLE CAUSES

SOLUTIONS

Mains is normal, but LED 1 is not 
illuminated.

The UPS may not be turned on.
The power cord may not be connected 
properly.
The upstream mains circuit breaker may be 
tripped.

• Press the On/Off button to turn on 

the UPS.

• Connect the power cord securely into 

a wall socket.

• Reset the circuit breaker.

LED 1 flashes (green) every 3 seconds, 
but there is no output power.

Battery voltage may be too low.

• Recharge the UPS for 8 hours.

Alarm buzzer beeps continuously 
although mains is normal.

The UPS may be overloaded (check LED 2).

• Disconnect some equipment from 

the UPS.

UPS does not provide expected 
backup time.

The UPS battery reached end of life.

• Replace the internal battery.

The UPS is on and connected to 
mains, but fails to operate properly.

Mains power may be outside the unit’s 
operating range.

• If mains is normal, try reconnecting 

mains and restarting the UPS.

If the UPS detects a fault, consult the table below for possible causes and solutions. For further assistance, please 

contact your local Vertiv representative.

Содержание PSP500MT3-230U

Страница 1: ...ther electronic components Any component that is removed must be taken to specialized collection and disposal centers If this unit must be dismantled this must be done by specialized personnel who are properly trained and qualified The unit must be taken to a center specialized in collection and disposal of dangerous substances For technical support visit www vertivco com SETUP 1 Inspecting the pa...

Страница 2: ...Liebert MultiLink software Install the software See the Liebert MultiLink quick start guide or user manual for installation instructions Connect one end of the USB cable supplied to the USB port on the rear of the UPS Connect the other end to a USB port on the computer See the Liebert MultiLink user manual for operating instructions NOTE Vertiv recommends connecting the USB cable directly to the c...

Страница 3: ...o the negative terminal NOTE Small sparks may occur at the battery connectors during reconnection Take care not to short circuit the positive and negative battery terminals while replacing the battery Place the battery in the UPS 4 Reassembling the PSP outer case Ensure correct alignment of front panel then reattach the right side cover Evenly tighten the four screws from Step 1 DO NOT overtighten...

Страница 4: ...ve Form Stepped sine wave VRLA Battery Type VDC x Ah x Quantity 12V x 7 2Ah x 1 12V x 7 2Ah x 1 Typical Recharge Time 6 8 hours to 90 Battery Run Time See Load Autonomy table below Audible and Visual Audible alarm LED Backup Sockets IEC 320 C13 3 Surge Sockets IEC 320 C13 1 Operating Temperature C F 0 to 40 32 to 104 Storage Temperature C F 15 to 40 5 to 104 Storage Temperature C F 15 to 40 5 to 1...

Отзывы: