Vertiv
™
NetSure
™
-48 VDC Power System
System Application Guide
Spec. No: 582140001
Proprietary and Confidential © 2022 Vertiv Group Corp.
SAG582140001
Model No: 801
NLDB
, 801
NLEB
, 801
NL
-
B
Page 71
Revision T, September 28, 2022
•
Between the DC output and the ground: the leakage current is
<
1 mA, with no breakdown within 1
minute using an applied voltage of 1500 V (with the varistor and filter capacitors removed before
doing the test).
3.3.7
Surge Protection: Complies with IEEE C62 41-1991 Class B3, 6kV/3kA (1.2/50
µ
s surge voltage and 8/20
µ
s
surge current).
3.3.8
Compliance Information
(A)
Safety and EMC: The rectifier has been recognized to meet the UL/EN/IEC 60950-2000 safety standard
and is CE marked. The rectifier also meets the latest EMC requirements, as listed in the following table.
Item
Standard
Class
Surge Immunity
EN61000-4-5
AC Port: 4kV/2
Ω
6kV/12
Ω
for com.
DC Port: 800V/2
Ω
CAN Bus: 1kV diff. / 2kV
com.
GR-1089-CORE
R4-8, R4-9,
R4-24, R-25
EFT
EN 61000-4-4
AC and DC Port: 4kV
CAN Bus: 1kV
GR-1089-CORE
O2-8
ESD
EN 61000-4-2 and
8kV/15kV
GR-1089-CORE
R2-1, R2-2,
R2-3, O2-4
Conducted
immunity
EN 61000-4-6
3Vrms 0.15-80MHz
GR-1089-CORE
R3-15,
CO3-16, R3-17
Radiated
immunity
EN 61000-4-6
10V 80-2GHz
GR-1089-CORE
R3-11, CR3-12
Mains
frequency
Magnetic fields
immunity
EN 61000-4-8
30A/m
Conducted
emissions
EN 55022
Class B
CFR 47 Part 15
GR-1089-CORE
R3-5 (Class B)
Conducted
current
emissions
GR-1089-CORE
R3-6
Radiated
emissions
EN 55022
Class B
CFR 47 Part 15
GR-1089-CORE
R3-1,
R3-4 (Class B)