![Vertiv NetSure 801NL-B Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/vertiv/netsure-801nl-b/netsure-801nl-b_system-application-manual_1008114019.webp)
Vertiv
™
NetSure
™
-48 VDC Power System
System Application Guide
Spec. No: 582140001
Proprietary and Confidential © 2022 Vertiv Group Corp.
SAG582140001
Model No: 801
NLDB
, 801
NLEB
, 801
NL
-
B
Page 19
Revision T, September 28, 2022
List 0C: 24 Position Bullet-Nose Circuit Breaker/Fuse Panel
Features
♦
Provides twenty-four (24) Bullet Nose
Device positions.
♦
Accepts a choice of TLS/TPS-type
fuseholders, Bullet Nose-Type circuit
breakers, or Bullet Nose-Type GMT Fuse
Modules.
♦
The List C Fuse/Circuit Breaker Panel is
equipped with one (1) shunt for all
distribution positions for MCA load
current measurements.
♦
Breakers and Bullet Nose-Type
Fuseholders e/w TLS/TPS Fuses
and
Optional Bullet Nose-Type 10-Position
GMT Fuse Module for List C
Restrictions
Each Distribution Bay can be equipped with
only one (1) List C panel.
The List C Circuit Breaker/Fuse Panel
requires distribution position #12 in the Bus
#1 Distribution Panel.
Current monitoring for the List C Fuse/Circuit
Breaker Panel is for the complete panel.
Circuit Breakers and/or fuses are not
individually monitored.
When installed, the bay can be loaded with up
to (47) 218 Circuit Breakers or (23) TPL Fuses
and (24) Bullet Nose Circuit Breakers or TLS/TPS Fuses.
The List C Circuit Breaker/Fuse Panel is rated for a maximum continuous load of 500 amps.
The total load combination of List C and Distribution Panel #1 cannot exceed 1500A.
Ordering Notes
1)
Order as required.
2)
Also order distribution fuses, circuit breakers, and/or Bullet Nose-Type 10-Position GMT Fuse Modules as required per
in the
ACCESSORY DESCRIPTIONS
section.
Optional List C
Bullet Nose Device Panel
Front door removed in
illustration for clarity.