52 Appendix 3 Parameter Setting Of The Controller
NetSure 531 AC1 Power Supply System User Manual
Item
Parameter
Range
Factory setting
Value description
Communication
BaudRate
1200bps
~
9600bps
9600bps
Make sure the baud rates of both the sending and
receiving parties are the same
IP/Subnet/Gate
-
-
Set according to actual instance
CallbackTime
-
-
Phone Number
-
-
Energy saving
Save Enable
Y, N
N
It can be set to
‘Y’ when the battery is configured
and load current without instantly shocks
Cyc Period*
1h ~
8760h
48h
Time of rectifier under power-on state and
power-off state, it can be set according to actual
requirement
Rect Work
30% ~
90%
80%
Output capacity percentage. More rectifiers will
startup to work when larger than this setting
percentage
Rect Limit
1 ~ 30
1
Minimum number of the rectifier
Fast settings
System Type
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
48V/SET
The system type of the controller has been set
according to the actual instance before the
controller is delivered with power supply system.
You need not to change the value except that the
controller is replaced with a new one.
After changing the type, the controller will restart
automatically and the other parameters will resume
the default. You need to reset and change some
parameters according to the battery and equipment
configured with system
Capacity
50Ah ~
5000Ah
300Ah
The capacity of the total battery strings. You should
set this parameter according to the actual battery
configuration
Note*: Cyc Period, Rect Work and Rect Limit are available when
‘Save Enable’ is set to ‘Y’