Appendix 3 Parameter Setting Of The Controller 51
NetSure 531 AC1 Power Supply System User Manual
Item
Parameter
Range
Factory setting
Value description
DC
Shunt Coeff
Current
1A ~
5000A
-
They can be reset when the shunt options are
‘SET’ in the system with load shunt
Shunt Coeff
Volt
1mV ~
500mV
-
Rectifier
Position En
Y, N
Y
‘Y’: The controller will prompt you to set rectifier
position before the rectifier and controller are
powered on.
‘N’: You need not to set rectifier position
R-Posi
1 ~ 30
-
R-Posi: represented in two figures, the first figure
represents the rectifier number, the next figure
reprents position number. Press ENT to select the
rectifier, press
◄ or ► to change position number.
When the controller communicates with the
rectifier, the green indicator on the corresponding
rectifier will blink
HVSD
56V ~
59V
59V
Rectifier over-voltage alarm point
Default V
48V ~
58V
53.5V
Default output voltage when communication
interrupted. Must be lower than the HVSD voltage
Walk-in On
Y, N
N
The output soft start function means the rectifier
voltage will rise from 0V to the Default Volt after the
Walk-in time
Walk-in
8s ~ 128s
8s
Interval T
0 ~ 10s
0s
The controller can set the DCDC Interval Start of
the rectifiers.
Start time = module address × interval time
AC OverV On
Y, N
N
If you set AC OverV On to
‘Y’, the rectifier can start
forcibly when the AC input overvoltage occurs in
the rectifier. The rectifier with least address has this
function. If the overvoltage persist for 60s, the
function will be canceled automatically
ACCurrLim
1A ~ 50A
30A
The controller limits the input current of the rectifier
in the AC current limiting
System
Lang
Chinese,
English
Chinese
Set according to your need
Tzone
-
-
Set according to actual instance
Date
2000 ~
2099
-
Set the time according to the current actual time,
regardless of whether it is a leap year or not
System Type
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
48V/SET
The system type of the controller has been set
according to the actual instance before the
controller is delivered with power supply system.
You need not to change the value except that the
controller is replaced with a new one.
After changing the type, the controller will restart
automatically and the other parameters will resume
the default. You need to reset and change some
parameters according to the battery and equipment
configured with system
ComDownLoad
Y, N
N
Reset PWD
Y, N
N
Whether resetting the password to the default
Reset Para
Y, N
N
Whether resetting the parameter to the default
Op1 PWD
-
-
The password can be 6 digits long at most. If it is
shorter than 6 digits, end it with a #
Op2 PWD
-
-
Adm PWD
-
-
Communication
Address
1 ~ 254
1
The addresses of power systems that are at the
same monitored office should be different
Comm Mode
MODEM
RS232
The system only supports RS232 mode
communication
MODEM: use the Modem to communicate in
telecom protocol