Vertiv
|
Liebert
®
PPC
™
User Manual | Rev. 6 | 03/18 |
29
Figure 19
Control wiring for units without low-voltage control box
Building Interface Relay
Remove jumper when 5th customer
alarm is used.
Remove jumper when Normally
Closed (N.C.) REPO is used
Green
TB1
Summary Alarm NO
N.C.
REPO
Summary Alarm NC
Summary Alarm Common
W200
Customer Alarm Common
Customer Alarm #1 (N.O.)
Customer Alarm #2 (N.O.)
Customer Alarm #3 (N.O.)
Customer Alarm #4 (N.O.)
Customer Alarm #5 (N.C.)
To Liebert
SiteScan
®
System
N.O. REPO
Black
White
Customer Alarms
Summary
Alarm
Auto-Manual
Restart Switch
Auto
Manual
#1 NO
#2 NO
#3 NO
#4 NO
#5 NC
RS-485
EPO
Remote
Common
NO
NC
NO
REPO
COM
REPO
COM
NC
REPO
24VDC
24VDC
P1
K1
TB1
K1
P2
P38
P2
-24+
J1
J2
J3
J3
E1
J1
TB2
P1
P1
TO I
NT
EL
LIS
LO
T O
NL
Y
S1
9
7
6
4
1
3
B
A
LDM13009
Rev. 1
NOTES
1.
All switching devices are to be suitable for switching low current 24VDC. Minimum recommended wire size is 18AWG
stranded copper with 300V insulation.
All wiring and devices are field-supplied except where noted. See installation manual for detailed installation procedures.
2.
The total load on the 24VDC supply (both N.O. and N.C. REPO circuits) must be limited to 1A.
3.
Multiple Normally Open (N.O.) REPO switches may be paralleled.
Multiple Normally Closed (N.C.) REPO switches may be connected in series. All lamps (if used) are connected in parallel.
4.
The summary alarm contacts are rated for 0 to 30VAC or VDC, 0.5A, 10W maximum.
5.
Customer Alarms 1 through 4 are Normally Open (indicates alarm on contact closure). Customer Alarm 5 is Normally
Closed (indicates alarm on contact opening).
6.
For Liebert SiteScan connection, use #22AWG shielded cable; maximum distance 1000ft (300m).