Vertiv
| Liebert
®
NXL
™
500-750kVA UPS Installation Manual |
32
Figure 20 Outline drawing, Liebert
®
NXL
™
500kVA UPS SMS and 1+N multi-module unit with static bypass
Inverter Split (Part B)
LEFT SIDE VIEW
FRONT VIEW
Rectifier Split (Part A)
RIGHT SIDE VIEW
.0
.0
DETAIL B
SECTION A-A
BOTTOM VIEW
A
A
TOP VIEW
25.5"
[647mm]
32.3"
[820mm]
49.2" [1250mm]
62.4" [1585mm]
111.6" [2835mm]
39.6"
[1005mm]
76.8"
[1950mm]
35.7"
[906mm]
14.9"
[379mm]
69.8"
[1773mm]
25.8"
[654mm]
10.8"
[273mm]
96.8" [2458mm]
10.8"
[274mm]
14.6"
[370mm]
1.25"
[31.9mm]
10.8" [275mm]
2.92" [74mm]
15.6"
[396mm]
10.6
[269mm]
Rectifier / DC
Cable Entry
Control Cable
Entry/Exit
Bypass/Output
Cable Entry/Exit
Cable
Entry
Bypass/Output
Cable Entry/Exit
Rectifier
Center
of Gravity
Inverter
Center
of Gravity
0.6" [15mm]
Panel Width
Front-Most
Edge of Frame
Outer Edge
Corner Post
NOTES
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit required for air exhaust
and maintenance.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. All wiring is to be in accordance with national and local electrical codes.
7. Depth dimension includes front door and rear panel.
8. Width dimensions include side panels. Subtract 1.4" (35mm) when
removing both side panels.
Содержание Liebert NXL 500kVA
Страница 73: ...Vertiv Liebert NXL 500 750kVA UPS Installation Manual 67 NOTES...
Страница 74: ...Vertiv Liebert NXL 500 750kVA UPS Installation Manual 68...
Страница 75: ......