3. Select the access level (
Read Only
or
Read/Write
).
4. Select the Modbus interface, (
Modbus TCP
or
Modbus RTU
).
5. Click
Save
to confirm the changes or
Cancel
to discard them.
6. Configure the Modbus interface chosen.
See
below or
For descriptions of the settings, see
Configure Modbus TCP
1. On the Communications tab, select
Protocols
>
Modbus
>
Modbus TCP
.
2. Click
, and enter a user name and password if necessary.
3. Set the Limit Network Access Type by choosing from the drop-down list:
•
•
•
See
on page 55 for additional details.
4. Enter the Port that the Modbus server will use to listen-for and respond-to Modbus protocol
requests based on the selected Limit Network Access Type.
5. Enter the Maximum Client Connection Count.
6. Click
Save
7. Restart the card:
a. On the Communications tab, click
b. Click
c. Click
Configure Modbus RTU
1. On the Communications tab, select
2. Click
Edit
, and enter a user name and password if necessary.
3. Enter the Node ID and the Baud Rate.
•
The Node ID defaults to 1, but must have a value from 1 to 247 that is unique among
devices connected through the RS-485 interface.
•
The default baud rate is 9600. 19200 and 38400 are also available.
For additional description of the settings, see
NOTE: Contact your system administrator if you are uncertain about the settings.
4. Click
Save
to confirm the changes or
Cancel
to discard them.
5. Restart the card:
a. On the Communications tab, click
Support
.
b. Click
Enable
.
c. Click
Restart
.
Vertiv™ | Liebert® IntelliSlot Unity Card Installer/User Guide