Final Positioning
When the equipment has been finally positioned, ensure that the adjustable stops are set so that the UPS will
remain stationary and stable (see
).
The Liebert
®
EXM and its auxiliary cabinets must be installed on a concrete or equivalent, non-resilient floor.
2.5
Mechanical Considerations
The Liebert
®
EXM is constructed with a steel frame and removable panels. Top and side panels are secured to
the chassis by screws. The doors may be opened for access to power connection bars, auxiliary terminal blocks
and power switches.
The UPS comes with an Operator Control Panel that provides basic operational status and alarm information.
The cabinet houses the power components. Cooling is provided by internal fans. The unit sits on four casters.
Adjustable stops are provided to prevent the UPS from moving once it has been moved to its final position.
2.5.1
Dimensions
Figure 1
UPS dimensions
WARNING
Risk of heavy units tipping over while being moved. Can cause property damage, injury and death.
23.6"
(600mm)
23.9" (608mm)
Overall
39.1" (993mm)
78.7"
(2000mm)
RIGHT SIDE
FRONT
EXM12002A
Rev. 5
Table 1
Weights for Liebert
®
EXM 20-100kVA
frame
kVA Rating
Weight, lb (kg)
Unit
Shipping
20
684 (320)
784 (356)
40
758 (344)
858 (389)
60
844 (383)
944 (428)
80
918 (416)
1018 (462)
100
992 (450)
1092 (495)