Vertiv™ |
Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |
36
5.0 OPTION INSTALLATION
5.1
Liebert
®
IntelliSlot Communication
The Liebert
®
EXM has three Liebert
®
IntelliSlot ports to allow field-installation of optional communication cards.
Liebert
®
IntelliSlot cards communicate via Liebert’s proprietary Velocity protocol to cards that translate the
information into such protocols as SNMP and Modbus. Other cards provide dry contact signals for external
signaling of operating status.
The Liebert
®
IntelliSlot communication ports may be installed or removed while the Liebert
®
EXM is operating.
5.2
Liebert
®
IntelliSlot Web Card—SNMP/HTTP Network Interface Card
This network interface card provides all real-time data and status information as SNMPv1 traps for connection to
a 10/100-baseT Ethernet connection. The same card also will transmit the same status information and all
measured parameters for display via a Web browser. The Liebert
®
IntelliSlot bays are on the right side of the
control module and labeled as IntelliSlot1, IntelliSlot2 and IntelliSlot3.
5.2.1
Liebert
®
IntelliSlot Unity Cards—IS-UNITY-LIFE, IS-UNITY-S, IS-UNITY-DP
•
IS-UNITY-LIFE: This standard card is used for communication between the Liebert
®
EXM and Vertiv’s Trellis
®
NMS and LIFE
services.
•
IS-UNITY-DP: This card can be used instead of the standard card if communication to two third-party platforms is required.
Third-party platforms include SNMP and 485 (Modbus/BACnet) protocols. This card would still be used for communication
between the Liebert
®
EXM and Vertiv’s Trellis NMS and LIFE Services. All communication protocols are active simultaneously.
•
Liebert
®
IntelliSlot Dry Contact Card (IS-RELAY): Provides dry contact alarm information, including: On Battery, On Bypass,
Low Battery, Summary Alarm, UPS Fault and On UPS signals for communication to a remote monitoring system.
•
IS-485EXI: The Liebert
®
IntelliSlot 485 EXI Card provides connection to a Liebert
®
SiteLink-E allowing Liebert
®
SiteScan
Web 4.0 monitoring and control of your Liebert
®
equipment.
Table 9
Liebert
®
EXM communication options
Port Type
and Location
Labeled ID
Name of Port
Monitoring
Devices Supported
Left
Liebert
®
IntelliSlot
IntelliSlot 1
IS-Relay
IS-Unity-DP
IS-Unity-LIFE
IS-485EXI
Center
Liebert
®
IntelliSlot
IntelliSlot 2
IS-Relay
IS-Unity-DP
IS-Unity-LIFE
IS-485EXI
Right
Liebert
®
IntelliSlot
IntelliSlot 3
IS-Relay
IS-Unity-DP
IS-Unity-LIFE
IS-485EXI