33
4.0 INSTALLATION DRAWINGS
The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert
®
EXM UPS
system cabinets (UPS, Liebert
®
BDC and battery).
Figure 21
UPS dimensions
Power Cable
Entry 21.1" x11"
(536 x 279mm)
Power Cable
Entry 4.7 x 11.8"
(119 x 300mm)
Control Cable
Entry 4.1" x 3.5"
(104 x 89mm)
Control Cable
Entry 2.8" x 1.6"
(71 x 41mm)
TOP
20.6"
(523mm)
20.4"
(518mm)
28.3"
(719mm)
Casters
34.3"
(872mm)
BOTTOM
See Detail A
1.6"
(41mm)
1.6"
(41mm)
1.5"
(38mm)
4"
(102mm)
39.1" (993mm)
RIGHT SIDE
Z
EXM12002A
Rev. 5
1. 24" (610mm) minimum clearance above unit
for air exhaust.
36" (914mm) front access required for service.
No clearance required in rear except when
using seismic anchoring: allow 5" (127mm)
clearance.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry available through
removable access plates. Remove, punch to suit
conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in
separate conduits.
6. Vertiv recommends using only copper cables.
7. All wiring is to be in accordance with national
and local electrical codes.
8. Overall dimensions are shown with side panels.
Leveler
DETAIL A
Caster
UPS Rating
kVA
Center of Gravity, in. (mm)
X
Y
20
40
60
80
100
18.9 (480)
22.04 (560)
33.66 (855)
31.49 (800)
29.53 (750)
23.6"
(600mm)
23.9" (608mm)
Overall
78.7"
(2000mm)
X
11.8"
(300mm)
FRONT