38
Table 1: Currents and maximum cable sizes
The following table lists the tightening torque for the hex-head terminal connection screws supplied
with the UPS.
Table 2: Tightening torque
UPS devices (kVA)
300
400
500
600
800
1000
1200
Primary Power line
Max. current (A)
1)
2)
Max. number of conductors
connectable to BUS-BAR & cross
section (mm
2
)
Screw size
1)
For a nominal voltage of 380V, multiply the current value by 1.05; for 415V, multiply by 0.96
2)
Overload current specified in chap. 9. on page 1
02
must be considered
473
2x240
M12
630
2x240
M12
788
2x300
M12
945
4x300
M12
1250
4x300
M12
1575
6x300
M12
1880
6x300
M12
Bypass Power line/Load
Nominal current (A)
2)
Max. number of conductors
connectable to BUS-BAR & cross
section (mm
2
)
Screw size
433
2x240
M12
577
2x240
M12
722
2x300
M12
866
4x300
M12
1155
4x300
M12
1443
6x300
M12
1732
6x300
M12
Battery, ex, -
Max. current (at 1.8V/cell - 240 cells)
(A)
3)
Max. number of conductors
connectable to BUS-BAR & cross
section (mm
2
)
Screw size
3)
To select the cross section, see the actual installation data and national and local codes.
651
3x240
M12
868
3x240
M12
1085
4x300
M12
1302
6x300
M12
1736
6x300
M12
2170
8x300
M12
2604
8x300
M12
Neutral (N) from line power/ to load N
Coefficient for oversizing the neutral
line conductor when non-linear load is
supplied
1
Max. number of conductors
connectable to BUS-BAR & cross
section (mm
2
)
Screw size
4x240
M12
4x240
M12
4x300
M12
8x300
M12
8x300
M12
12x300
M12
12x300
M12
Ground
Max. number of conductors
connectable to PE BUS-BAR (mm
2
)
Screw size
1x240
M12
1x240
M12
1x300
M12
2x300
M12
2x300
M12
4x300
M12
4x300
M12
Type of connector
BUS-BAR
Screw size
Nm (+/-20
)
M10
39
M12
68
Содержание Liebert EXL
Страница 1: ...Liebert EXL User Manual...
Страница 2: ...Liebert EXL UNINTERRUPTIBLE POWER SUPPLY USER MANUAL 10H52226UM60 rev 1...
Страница 7: ...Liebert EXL S1 6 User Manual 10H52226UM60 Rev 1 01 2017...
Страница 36: ...Preparation For Use Liebert EXL S1 35 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 74: ...CONNECTIVITY PANELS Liebert EXL S1 73 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 84: ...Normal and safe operation Liebert EXL S1 83 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 86: ...Maintenance Liebert EXL S1 85 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 94: ...PARALLEL CONFIGURATION Liebert EXL S1 93 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 102: ...Options Liebert EXL S1 101 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...