![Vertiv Liebert EXL Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/vertiv/liebert-exl/liebert-exl_user-manual_1008219063.webp)
Liebert EXL S1
Installation
User Manual 10H52226UM60 - Rev. 1 - 01/2017
62
3.8. Connecting the batteries
UPS are supplied without the battery switch. It is mandatory that the Customer provides an external
battery protection device, ensuring that they are correctly rated.
Auxiliary signal contacts shall be assigned to a programmable input of XP11, so that the status of the
switch can be monitored during the normal operation.
Before connecting the batteries, please read the notice and warning label on the
UPS or battery compartment.
Notice
Full safety instructions on the use and maintenance of UPS batteries are provided in the
appropriate battery manufacturers' manuals. The battery safety information contained in
this section consists of key considerations which must be taken into account when
designing the installation and may affect its outcome, depending on local conditions.
Warning
Special care should be taken when working with the batteries associated with the Liebert
EXL S1. When all batteries are connected together the overall voltage exceeds 500V.
It is very important to make sure that the batteries are separately installed in a specially
designed, lockable, dedicated battery cabinet or battery room.
Battery cabinet specifications can be found in para 8.3. on page
98
of this manual.
Warning
In the event of malfunction, the battery shelves and/or cabinet or battery holders may
become live!
Notice
The requirements of EC directives are met when battery compartments with original
accessories are used. If other batteries are used, make sure that the applicable EC
directives are met and that conformance is declared. The UPS must still be parameterized
with the service software and equipped with an all-pole disconnecting device and fuses,
as per Table 1 on page
38
. When dimensioning your battery cables, note the connection
tolerances at ter/-.
Warning
ENSURE CORRECT POLARITY!
Содержание Liebert EXL
Страница 1: ...Liebert EXL User Manual...
Страница 2: ...Liebert EXL UNINTERRUPTIBLE POWER SUPPLY USER MANUAL 10H52226UM60 rev 1...
Страница 7: ...Liebert EXL S1 6 User Manual 10H52226UM60 Rev 1 01 2017...
Страница 36: ...Preparation For Use Liebert EXL S1 35 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 74: ...CONNECTIVITY PANELS Liebert EXL S1 73 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 84: ...Normal and safe operation Liebert EXL S1 83 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 86: ...Maintenance Liebert EXL S1 85 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 94: ...PARALLEL CONFIGURATION Liebert EXL S1 93 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Страница 102: ...Options Liebert EXL S1 101 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...