REV : 1
REV DATE : 1/17
DPN003964
Page :1 /1
3 FAN CW340 MODEL
F
or
m
N
o.
: D
P
N
00
10
40
_R
E
V
4
FAN SECTION DIMENSIONAL DATA
LIEBERT CW
RIGHT SIDE
PANELS REMOVED FOR CLARITY
60"
1524mm
OVERALL
BOTTOM VIEW
FANS REMOVED FOR CLARITY
1"X1"X3" long steel tube
Typ. (6) places
Attachment
Point
58 7/8"
1495mm
Typ.
Attachment
Point
58 7/8"
1495mm
Typ.
Attachment
Point
10 1/2"
267mm
Typ.
Attachment
Point
Attachment
Point
Attachment
Point
TOP VIEW
FRONT VIEW PANELS REMOVED FOR CLARITY
NOTE:
1. This fan section is designed for 36" (914mm) raised floor height and can accomodate floors between 34" - 43" (864mm - 1092mm) high..
3. The fan section is not symmetrical and its orientation to the Liebert CW is critical for proper installation.
3. The EC fans must be field wired into connectors inside of the unit.
4. The EC fans are removed out the front of the fan section, and there must be clearance in front of fan section to be able to service fans (See DPN003561).
5. The fan section may be ordered with the piping access area at the opposite end, and the fans oriented accordingly.
Piping access area
(See Note 5)
138 11/16"
3523mm
43"
1092mm
10"
254mm
38 1/4"
972mm
38 1/4"
972mm
38 1/4"
972mm
Содержание Liebert CW340
Страница 1: ...Liebert CW Thermal Management System Installer User Guide 340 kW to 440 kW Capacity 60 Hz...
Страница 4: ...Vertiv Liebert CW Installer User Guide 4...
Страница 8: ...Vertiv Liebert CW Installer User Guide 8 This page intentionally left blank...
Страница 28: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Страница 34: ...Vertiv Liebert CW Installer User Guide 34 This page intentionally left blank...
Страница 36: ...Vertiv Liebert CW Installer User Guide 36 This page intentionally left blank...
Страница 54: ...Vertiv Liebert CW Installer User Guide...