7.3 Condensate-pump High- and Low-voltage Connections
The coil and fan sections are factory-wired with a quick-connect connector for the condensate pump.
After the coil section is lowered and secured to the fan section, connect the pump harness from the fan
section to the plug provided in the under-side of the coil section, see Figure 6.5 below.
Figure 6.5 Condensate-pump harness connection
Item
Description
1
High-voltage power connection
2
Wire harness from EP
3
Low-voltage alarm connection
4
Condensate pump
5
Rear-side view
7 Electrical Connections in the Unit
27