Vertiv™ eSure™ Rectifier Module User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
11
2
Operation
2.1
AC Input Protection Device Requirements/Recommendations
Refer to the system documentation supplied with the system the rectifier is installed in.
2.2
Local Indicators
Location and Identification: Refer to
Description: There are three (3) indicators located on the rectifier’s front panel. The functions of these indicators are as shown in
NOTE!
DC voltage must be present at the rectifier output terminals (from battery or an operating rectifier) or AC voltage at
the input terminals.
Figure 2.1
Local Indicator Locations
Table 2.1
Rectifier Indicators
Indicator
Normal State
Alarm State
Alarm Cause
Power
(Green)
On
Off
No input voltage.
Internal input fuse open.
Flashing
The rectifier is being identified by the controller.
Protection
(Yellow)
Off
On
AC input under/over voltage.
PFC output under/over voltage.
Moderate load sharing imbalance.
Rectifier not inserted into the slot completely.
Rectifier over-temperature protection.
Rectifiers are operating in an output power derating mode (rectifiers
derate when rectifier temperature rises above or input voltage falls
below acceptable values).
Rectifier in ECO Standby Mode when ECO Mode is active in
controller.
Flashing
Loss of communication with the controller (the rectifier can provide
power).
Alarm
(Red)
Off
On
Severe load sharing imbalance.
Rectifier output disabled for any reason, including overvoltage
shutdown and internal output fuse open.
Rectifier addresses contradictory.
Flashing
Fan not operating (rectifier shuts down).
Power Indicator (Green)
Protection Indicator (Yellow)
Alarm Indicator (Red)