Vertiv™ eSure™ Rectifier Module User Manual 

Proprietary and Confidential © 2022 Vertiv Group Corp. 

 

Power Derating Based on Input Voltage:  The rectifier power varies with changes in input voltage and output voltage.  It uses 
an advanced power limitation method.  The lower input threshold is 85 VAC.  The rectifier can provide its maximum rated 
power (1000 W) as long as the input voltage is within the range of 176 VAC to 300 VAC.  Below 176 VAC, and down to 85 
VAC, the rectifier will continue to operate normally but will be in a power derating mode.  The relationship between the output 
power and input voltage is illustrated in 

Figure 1.2

Figure 1.2  

Power Derating Based on Input Voltage 

 

 

NOTE!

 

Blue Line: 

Linear derating from 85 VAC to 176 VAC; 

   

 

Green Line:

  Keeping constant power from 90 VAC to 132 VAC, the output power is 500W. 

 

Power Derating Based on Temperature:  The rectifier delivers full power when operating at an ambient temperature of +45 °C 
(+113 °F) or below.  Each rectifier continuously monitors the ambient temperature surrounding the power conversion circuit.  
If this temperature for any reason (such as a high ambient temperature) increases above approxi45 °C (+113 °F), the 
rectifier will not shut down.  Rather, the rectifier limits its maximum output power to maintain the temperature of the power 
conversion circuit within design parameters.  Operation b45 °C (+113 °C) and +75 °C (+167 °F) will result in output 
power being decreased.  Full power capability is restored when the temperature decreases to below approxi45 °C 
(+113 °F).  Refer to 

Figure 1.3

 to view the relationship between the output power and the ambient temperature. 

Other power rating values are as follows (refer to 

Figure 1.3

)

a)

 

At an ambient temperature of +55 °C (+131 °F), the power delivered by the rectifier is 1000 W. 

b)

 

At an ambient temperature of +65 °C (+149 °F), the power delivered by the rectifier is 825 W. 

c)

 

At an ambient temperature of +70 °C (+158 °F), the power delivered by the rectifier is 720 W. 

Additional conditions:  

When operating in ambient between 65C to 70C the rectifier can provide 825W of power if the AC input voltage is 200VAC to 
250VAC and the DC output voltage setting of the rectifier module is 52VDC to 58VVDC.  When operating in an ambient between 65C 
to 70C the rectifier module will linearly derate to 800W if the AC input is 200VAC to 250Vac and the DC output voltage setting of the 
rectifier module is 50VDC to 56VDC. 

 

0.0%

20.0%

40.0%

60.0%

80.0%

100.0%

120.0%

0

50

100 150 200 250 300 350

%

 o

f o

ut

pu

t p

ow

er

Input Voltage (VAC)

Output Power vs. Input Voltage and

Vo > 48 VDC at Temp 

≤ 4

Содержание eSure R48-1000e3

Страница 1: ...eSure Rectifier Module User Manual Specification Number 1R481000e3 Model Number R48 1000e3...

Страница 2: ...ally described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary...

Страница 3: ...d Regulatory Statements v D clarations de S curit et de R glementation v 1 Introduction 1 1 1 Overview 1 1 2 Specifications 1 2 Operation 11 2 1 AC Input Protection Device Requirements Recommendations...

Страница 4: ...jury if not avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards...

Страница 5: ...nts used in this document are listed under Admonishments Used in this Document on page iv Safety and Regulatory Statements Refer to Section 4154 provided with your customer documentation for Safety an...

Страница 6: ...Vertiv eSure Rectifier Module User Manual Proprietary and Confidential 2022 Vertiv Group Corp vi This page intentionally left blank...

Страница 7: ...ate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately 1000 W Constant Power Mode As load increases above approximate...

Страница 8: ...ifier will not shut down Rather the rectifier limits its maximum output power to maintain the temperature of the power conversion circuit within design parameters Operation between 45 C 113 C and 75 C...

Страница 9: ...s of load from no load to full load input voltage and input frequency at a constant ambient temperature The associated system controller may provide increased regulation b Dynamic Response time 200 mi...

Страница 10: ...t Current Refer to Table 1 4 Efficiency Curve Refer to Figure 1 4 Table 1 1 Typical Input Data in 50Hz Input Nominal Input Voltage Percent of Full Load Input Current Amperes Input VA Input Watts Power...

Страница 11: ...995 92 77 62 17 50 2 644 528 83 527 55 0 998 94 45 95 74 75 3 975 794 62 793 52 0 999 94 23 152 82 100 5 359 1070 26 1069 10 0 999 93 25 242 50 110 5 555 1109 39 1108 06 0 999 92 97 261 59 208 VAC 0...

Страница 12: ...t 50 of full load and nominal input Percent of Full Load refers to percent of 18 69 amperes Table 1 4 Maximum Input Current in 60Hz Input Nominal Input Voltage Input Voltage Input Current Amperes 200...

Страница 13: ...bution System TN TT IT NOTE The rectifier is recommended to be used in an environment with Pollution of Degree 2 or less Pollution Degree 2 applies where there is only non conductive pollution that mi...

Страница 14: ...he rectifier can be plugged into or pulled out of a shelf while operating without damage or opening the fuse b Current Limiting The rectifier has a current limit function The current limit point can b...

Страница 15: ...d This feature can be disabled via the controller allowing the fan to run at full speed regardless of temperature Paralleling Up to 16 rectifiers can be connected in parallel in one system Communicati...

Страница 16: ...e Regulation Input Voltage Output Voltage Output Current Current Limit Setting Temperature Over Voltage Setting On Off Status Fault Alarms such as HVSD Fan Fail Protection Alarms such as Input Voltage...

Страница 17: ...Green On Off No input voltage Internal input fuse open Flashing The rectifier is being identified by the controller Protection Yellow Off On AC input under over voltage PFC output under over voltage M...

Страница 18: ...ctifier 2 5 Installing Rectifiers Rectifiers can be inserted or removed with power applied hot swappable NOTE Each rectifier module locks into a module mounting shelf by means of a latch located on th...

Страница 19: ...ng Imbalance When multiple rectifiers are operating in parallel and the load is greater than 20 if the current sharing imbalance among them is greater than 5 check if the rectifier is properly seated...

Страница 20: ...the fan Ventilation blocked inlet or outlet remove any object that may be blocking the inlet or outlet Ambient temperature too high or rectifier inlet too close to a heat source lower the ambient temp...

Страница 21: ...regard any alarms associated with this system while this procedure is performed 2 On the rectifier to be removed loosen the captive screw on the rectifier s handle Pull the handle down out from the re...

Страница 22: ...Vertiv eSure Rectifier Module User Manual Proprietary and Confidential 2022 Vertiv Group Corp 16 This page intentionally left blank...

Страница 23: ...User Manual Proprietary and Confidential 2022 Vertiv Group Corp Connect with Vertiv on Social Media https www facebook com vertivI https www instagram com vertiv https www linkedin com company vertiv...

Страница 24: ...or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness here Vertiv Group Corp assumes no responsibility and disclaims all liabili...

Отзывы: