Aux. power fault
UPS internal auxiliary power voltage fault. Contact Vertiv Technical Support.
Battery cabinet
connect abnormal
More than 10 external battery cabinets are connected to the UPS. Disconnect excess battery cabinets.
Battery EOD
The battery has reached the end of discharge and mains/utility power is unavailable. Restore the mains
power. The UPS will power off if it is not restored.
Battery low
prewarning
This alarm occurs when the battery approaches the EOD. After the pre-warning, the battery capacity allows
two minutes discharge at full load. The user can set the time with the Low Battery Time setting in Battery
settings from 2 min - 30 min, (2 min by default). This allows for any loads to be shut down before the system
powers off if utility power cannot be restored.
Battery mode
The UPS operating in battery mode. The alarm will clear when utility power is restored.
Battery overtemp
Battery ambient temperature too high. Ensure that the battery ambient temperature is not higher than
setting value 40 ~ 60 °C (default: 50 °C)
Battery replacement
timeout
The system time is past the time set for the batteries to be replaced. If you have disabled the “Batt. note
duration” or have no batteries installed, the alarm will not occur.
Battery reversed
The battery positive and negative are reversed. Reconnect the battery and check the battery cable
connections.
Battery test fail
The voltage of the battery was low when the periodic or manual self-test was run. Battery replacement is
Recommended.
Battery test started
The battery periodic self-test or manual self-test has finished. This will display in the log whenever the event
occurs.
Battery test stopped
The battery periodic self-test or manual self-test has finished. This will display in the log whenever the event
occurs.
Battery to utility
transition
The UPS has transferred the load to the mains power from the battery. This will display in the log whenever
the event occurs.
Battery voltage
abnormal
The battery voltage exceeds the normal range. Check if the battery terminal voltage exceeds the normal
range.
Battery to utility
transition
The UPS has transferred the load to the mains power from the battery. This will display in the log whenever
the event occurs.
Battery voltage
abnormal
The battery voltage exceeds the normal range. Check if the battery terminal voltage exceeds the normal
range.
Bypass abnormal
May be caused by bypass voltage and frequency outside of range, bypass power-off and incorrect bypass
cables connection. Check that the bypass voltage and frequency are within the setting range. Check the
bypass cables connection
Table 4.2 Alarm Messages table
4 Operations
30
Liebert® EDGE Installer/User Guide
Содержание EDGE-1000IMT
Страница 1: ...Vertiv Liebert EDGE Installer User Guide...
Страница 6: ...1 Important Safety Instructions 2 This page intentionally left blank Liebert EDGEInstaller User Guide...
Страница 10: ...2 EDGE Description 6 This page intentionally left blank Liebert EDGEInstaller User Guide...
Страница 18: ...3 Installation 14 This page intentionally left blank Liebert EDGEInstaller User Guide...
Страница 42: ...4 Operations 38 This page intentionally left blank Liebert EDGEInstaller User Guide...
Страница 46: ...5 Maintenance and Battery Replacement 42 This page intentionally left blank Liebert EDGEInstaller User Guide...
Страница 64: ...6 Specifications 60 This page intentionally left blank Liebert EDGEInstaller User Guide...
Страница 66: ...Appendices 62 This page intentionally left blank Liebert EDGEInstaller User Guide...
Страница 67: ...Liebert EDGEInstaller User Guide...