Vertiv™ NetSure™ IPE Series -48 VDC Outdoor Rectifier Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
74
6
Operation
6.1
Local Indicators
There are three (3) indicators located inside the rectifier enclosure (visible from the outside through a window located on the left
side of the rectifier). See Figure 6.1 for location and Table 6.1 for indicator functions.
NOTE!
AC voltage must be present at the rectifier input terminals for indicators to be functional.
Figure 6.1: Local Indicator Locations
Table 6.1: Local Indicators
Indicator
Color
Normal State
Fault State
Fault Cause
Status
Green
On
Off
No operation power supply.
Observation Alarm
Yellow
Off
On
There is an observation alarm.
Critical or Major Alarm
Red
Off
On
There is a major or critical alarm.
6.2
Battery Local Indicators
Three (3) LED indicators are located on the bottom side of the battery. These indicate the battery operating status.
•
Green LED: Normal operation.
•
Yellow LED: Communication failure or battery alarm issued.
•
Red LED: Battery protected or battery fault.
Left Side Panel
Critical or Major
Alarm Indicator
(Red)
Observation Alarm
Indicator (Yellow)
Status
Indicator
(Green)