Vertiv™ NetSure™ IPE Series -48 VDC Outdoor Rectifier Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
85
Table 7.2 Settings Value
Number
Parameter Name
Default Value
Value Range
1
Float Voltage
53.5V
42 - 58V
2
ECO Mode
1 - Enable
0 – Disable, 1 - Enable
3
Alarm Block
0 - No
0 – No, 1 - YES
4
Baud Rate
0 - 9600
0 – 9600, 1 - 19200
5
System
Rectifier
Rectifier
6
Rect Lost
1 - Clear
1 - Clear
7
NB Latitude
66.0
0 - 90°
8
NB Longitude
44.0
-180° - 180°
Description of Settings
Float Voltage: Sets the value of float voltage.
ECO Mode: Enables or disables the ECO Mode.
Alarm Block: When the outgoing alarms are blocked, the alarms shall not trigger relay outputs. The active alarms are continued
to be displayed in the mobile app and in the Web pages. Select ‘Yes’ to block alarm from being transmitted or ‘No’ to allow
notification.
Baud Rate: Selects the baud rate for the RS-485: 9600 or 19200 (data bit, parity, and stop bit of 8, n, 1 are fixed).
System: The only system is rectifier.
Rect Lost: Clears the Rectifier Lost Alarm (i.e., when rectifier is removed and replaced).
NB Latitude: Sets the latitude value for NB.
NB Longitude: Sets the longitude value for NB.
Swap Controller Icon
In the Menu Navigation area, click on the Swap Controller Icon (
) to go to the Swap Controller screen.
Figure 7.12 Swap Controller Screen