64 Appendix 3 Parameter Setting Of The Controller
NetSure 731 CC2, NetSure 731 C62 Series Power Supply System User Manual
Item
Parameter
Range
Factory
setting
Value description
System
System Type
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
NetSure 731
C62
:
48V/300
NetSure 731
CC2
:
48V/500
The system type of the controller has been set
according to the actual instance before the
controller is delivered w ith pow er system. You
need not to change the value except that the
controller is replaced w ith a new one.
After changing the type, the controller w ill
restart and the other parameters w ill resume
the default. You need to reset and change
some parameters according to the battery and
equipment configured w ith system
ComDow nLoad
Y, N
N
Whether resetting the passw ord to the default
Reset PWD
Y, N
N
Reset Para
Y, N
N
Whether resetting the parameter to the default
Op1 PWD
-
-
The passw ord can be 6 digits long at most. If it
is shorter than 6 digits, end it w ith a #
Op2 PWD
-
-
Adm PWD
-
-
Communication
Address
1 ~ 254
1
The addresses of pow er systems that are at
the same monitored office should be different
Comm Mode
Modem
RS232
The pow er system only supports RS232 mode
communication
BaudRate
1200bps ~
9600bps
9600bps
Make sure the baud rates of both the sending
and receiving parties are the same
IP/Subnet/Gate
-
-
Set according to actual instance
CallbackTime
-
-
Phone Number
-
-
Energy saving
Save Enable
Y, N
N
It can be set to
‘Y’ w hen the battery is
configured and load current w ithout instantly
shocks
Cyc Period*
1h ~ 8760h
48h
Time of rectifier under pow er-on state and
pow er-off state, it can be set according to
actual requirement
Rect Work
30% ~ 90%
80%
Output capacity percentage. More rectifiers w ill
startup to w ork w hen larger than this setting
percentage
Rect Limit
1 ~ 30
1
Minimum number of the rectifier
Fast settings
System Type
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
NetSure 731
C62
:
48V/300
NetSure 731
CC2
:
48V/500
The system type of the controller has been set
according to the actual instance before the
controller is delivered w ith pow er system. You
need not to change the value except that the
controller is replaced w ith a new one.
After changing the type, the controller w ill
restart and the other parameters w ill resume
the default. You need to reset and change
some parameters according to the battery and
equipment configured w ith system
Capacity
50Ah ~ 5000Ah
300Ah
The capacity of the total battery strings. You
should set this parameter according to the
actual battery configuration
Note*: Cyc Period, Rect Work and Rect Limit are available w hen
‘Save Enable’ is set to ‘Y’