Chapter 4 Use Of The Controller 39
NetSure 731 CC2, NetSure 731 C62 Series Power Supply System User Manual
4.7.6 System Settings
At the Settings screen, press
▲ or ▼ to select the ‘Sys Settings’ menu, then press the ENT key to enter the
password confirmation screen. After inputting the correct password (user level password, default: 1), the three
screens shown in Figure 4-34 are displayed.
Lang: Chinese
Tzone GMT+08: 00
Date: 2000-01-15
System Type:
48V/SET
ComDownLoad: N
Reset PWD: N
Reset Para: N
Op1 PWD: ******
Op2 PWD: ******
Adm PWD: ******
Figure 4-34 Settings screen upon user level
If the
‘Rest Para’ is set to ‘Y’, press the ENT key and prompt a screen shown in Figure 4-35.
Notice:
ENT Continue
ESC Quit
Figure 4-35 Prompt screen for resetting system
Press the ESC key to cancel the resetting. Press the ENT key to execute the resetting. At this time, all the
parameters will return to the default value. It is recommended to execute system re setting when the controller cannot
work normally through the method of powering off or restoration.
Press
▲ or ▼ to select the parameter you need, and press ◄ or ► to select the parameter value, then press the
ENT key to confirm.
The value description of the system parameters is listed in Table 4-15.
Table 4-15 Description of the system parameter setting
Parameter
Range
Factory setting
Value description
Lang
Chinese, English
English
Set it according to your need
Tzone
-
-
Set it according to actual instance
Date
2000 ~ 2099
-
Set the time according to the current actual time, regardless of
w hether it is a leap year or not
System Type
24V/100
24V/300
24V/500
24V/1000
24V/SET
48V/100
48V/300
48V/500
48V/1000
48V/SET
PS48300-3B/1800:
48V/300
The system type of the controller has been set according to the
actual instance before the controller is delivered w ith pow er
system. You do not need to change the value except that the
controller needs to be replaced w ith a new one.
After changing the type, the controller w ill restart and other
parameters w ill resume the default. You need to change some
parameters according to the battery and other equipment
configured w ith the system
ComDow nLoad
Y, N
N
Reset PWD
Y, N
N
Whether resetting the passw ord to the default
Reset Para
Y, N
N
Whether resetting the parameters to the defaults
Op1 PWD
-
-
The passw ord can be six digits long at most. If it is shorter than
six digits, end it w ith a #. Use
▲ or ▼ to change the number, and
◄ or ► to move the cursor left or right. Press the ENT key to
confirm. You should input the same number tw ice to validate the
setting
Op2 PWD
-
-
Adm PWD
-
-
4.7.7 Communication Settings
At the Settings screen, press
▲ or ▼ to select the ‘Comm Settings’ menu, then press the ENT key to enter the
screen shown in Figure 4-36.