If you have electrical power, check the following:

1.  The time clock must be moved to the "ON" posi-

tion.

2.  Your  pump  strainer  basket  may  be  full.  If  so

remove debris.

3.  Your filter may be dirty. If so, backwash or clean fil-

ter. (If your filter is dirty, the gauge pressure will be
higher than usual).

4.  The pump may have lost its prime and be running

dry. Check the pressure gauge on the filter. If there
is  no  pressure;  the  water  is  not  moving  (or  your
gauge is broken). Try to get the pump to run at its
normal flow rate.

Pool & Spa Water 

Chemistry

Chemical  imbalance  can  cause  severe  damage  to
your heater and associated equipment. Maintain your
water  chemistry  according  to  the  chart  on  page  5.  If
the mineral content and dissolved solids in the water
become  too  high,  scale  forms  inside  the  heat
exchanger tubes, reducing heater efficiency and also
damaging the heater. 

If the pH drops below 7.2, the heater will be severely
damaged.  This  will  result  in  corrosion  of  the  heat
exchanger.  Heat  exchanger  damage  resulting  from
chemical imbalance is not covered by the warranty.

Cold Weather Operation

Heater operation can continue during short term cold
spells.  When  temperatures  are  below  freezing,  flow
(continuous pump operation) must be maintained.

Prolonged  operation  with  water  temperatures  below
50°F  is  not  recommended.  When  starting  the  heater
with pool temperatures below 50°F, operate the heater
continuously  until  higher  temperatures  are  reached.
Operating the heater for prolonged periods with pool

water  below  50°F  can  seriously  damage  the  heater,
and will void the warranty.

For  cold  climate  areas  please  follow  the  winterizing
procedures listed below.

Winterizing the Spa Heater

When  heaters  installed  outdoors  in  freezing  climate
areas are to be shut down for the winter, observe the
following procedure:

1.  Turn off gas valve, manual gas valve, and electri-

cal supply to the heater.

2.  Open drain cock located on the return header.

3.  Disconnect compression fittings from the pressure

switch and header that connect to the 1/4" copper
tube and allow the tube to drain.

INTRODUCTION

Receiving Equipment

On receipt of your equipment it is suggested that you
visually check for external damage to the carton. If the
carton is damaged, a note should be made on the Bill
of  Lading  when  signing  for  the  equipment.  Remove
the heater from the carton and if it is damaged, report
the damage to the carrier immediately.

On occasion, we ship some items loose. Be sure that
you receive the number of packages indicated on the
Bill of Lading.

When  ordering  parts,  you  must  specify  model  and
serial number of heater. When ordering under warran-
ty  conditions,  you  must  also  specify  the  date  of
installation.

The  manufacturer  recommends  that  this  manual  be
reviewed  thoroughly  before  installing  your  pool/spa
heater.  If  there  are  any  questions  that  this  manual
does  not  answer,  please  contact  the  factory  or  your
local representative.

CAUTION:

Do not use the heater to maintain water

temperatures  just  above  freezing,  or  for  freeze
protection.  When  heaters  are  used  during  freezing
weather,  care  must  be  taken  to  avoid  freeze-ups.
Continuous  pump  operation  is  a  must.  Additional
protection  may  be  required.  The  heater  is  not
warranted against freeze-ups.

Содержание 055B

Страница 1: ...r appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediate...

Страница 2: ...2 Rev 24 reflects the following Changes to Water Chemistry Table A on page 5 Wiring Diagram on page 20...

Страница 3: ...10 Receiving Equipment 10 General Specifications 11 INSTALLATION 11 Code Requirements 11 Base Installation 11 Clearances 11 Outdoor Heaters 13 Indoor Heaters 13 Combustion Air Indoor Units Only 13 Ven...

Страница 4: ...to the heater WARNING CALIFORNIA PROPOSITION 65 This product contains chemicals known to the State of California to cause cancer birth defects or other reproductive harm CAUTION Verify proper operatio...

Страница 5: ...atic chemical dosing devices and salt chlo rinators are usually more efficient in heated water unless controlled they can lead to excessive chlo rine level which can damage your heater Further advice...

Страница 6: ...and burner The flame should be blue with a well defined pattern A yellow or floating flame indicates restricted air openings or incorrect orifice size Should this occur shut the heater off and contact...

Страница 7: ...way and hold in Immediately place flame to pilot to light Continue to hold control knob in for about 1 minute after the pilot is lighted release knob and it will pop back up Pilot should remain lighte...

Страница 8: ...ance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next...

Страница 9: ...s advice before using pools or hot tubs 6 Persons taking medications which induce drowsi ness such as tranquilizers antihistamines or anticoagulants should not use spas or hot tubs MAINTENANCE AND CA...

Страница 10: ...F can seriously damage the heater and will void the warranty For cold climate areas please follow the winterizing procedures listed below Winterizing the Spa Heater When heaters installed outdoors in...

Страница 11: ...accordance with local codes or in the absence of local codes with the latest editions of the National Fuel Gas Code ANSI Z223 1 and the National Electrical Code ANSI NFPA 70 for Canada the latest edi...

Страница 12: ...and at least 18 on the left side of the heater to inspect and de lime the heat exchang er Heaters must not be installed under an overhang of less than three 3 feet from the top of the heater Three 3...

Страница 13: ...llation when equipped with the approved drafthood For Canada indoor installation is restricted to an enclosure that is not occupied and does not directly communicate with occupied area Refer to the la...

Страница 14: ...should be securely guyed or braced to withstand snow and wind loads We recommend use of insulated vent pipe spacer through the roofs and walls For protection against rain or blockage by snow the vent...

Страница 15: ...testing of that system at test pressures in excess of 1 2 psig 3 45 kPa Dissipate test pressure in the gas supply line before reconnecting the heater and its manual shut off valve to gas supply line F...

Страница 16: ...installation is plumbed as follows 1 The inlet side of the filter is plumbed directly to the discharge side of the filter pump 2 The outlet side of the filter is then plumbed to the inlet of the heate...

Страница 17: ...er High chemical concen trations will result when the pump is not running e g overnight Chlorinators must feed downstream of the heater and have an anti siphoning device to prevent chemical backup int...

Страница 18: ...ittent Ignition Device IID System The Electronic Intermittent Ignition Device automati cally lights the pilot and main burners upon a call for the heat The heater is supplied with a dual voltage trans...

Страница 19: ...0V operation 120V ATMOSPHERIC HEATER 120V LOW NOx HEATER SUPPLY SIDE RETURN or NEUTRAL HEATER 4 WIRES H GROUND L L1 RED BLACK B HOT BLACK GREEN GREEN WHITE WHITE Fig 20 120V Wiring 240V ATMOSPHERIC HE...

Страница 20: ...20 Wiring Diagram Millivolt Units with Mechanical Thermostat...

Страница 21: ...21 Wiring Diagram IID Units BL BL BL...

Страница 22: ...ng the knobstop ring to the desired location and retightening the set screw Drain Valve Solid State Thermostat Ignition Control Pressure Switch Burner Pilot Thermal Fuse HIGH LIMITS Located in the Inl...

Страница 23: ...flow on the low speed is insuffi cient to operate the heater This is apparent when the pressure switch cannot be further adjusted or if the heater makes banging noises In these cases the pump must be...

Страница 24: ...emove burner tray See Burner Tray Removal procedure 2 Disconnect pilot tubing from gas valve 3 Remove gas valve with manifold from burner tray 4 Remove manifold from gas valve 5 Reverse above procedur...

Страница 25: ...tely from between fins Avoid excessive water against refractory Combustion Chamber Removal 1 Remove heat exchanger See Heat Exchanger Removal procedure 2 Lift up and remove front and rear refractory s...

Страница 26: ...nlet Inlet Outlet Header Retainer Spring Fig 31 Unitherm Governor Location To test the operation of the Unitherm Governor place in hot water over 110 F and watch for movement against spring If there i...

Страница 27: ...heat exchanger g n i t o o S Highflowrates Reduce by adding manual bypass valve and adjust by putting thermometer in header 1 4 NPT drain opening Set bypass so thermom eter reads between 105 and 110...

Страница 28: ...emain lit attach millivolt meter and read pilot output If below 500millivolt check gas pressure Also check for insects or debris in the pilot burner If main burner fires remove jumper Replace gas valv...

Страница 29: ...nd wire Clean flame rod Check electrical connections between flame rod and module Check for cracked ceramic flame rod insulator Check that pilot flame covers flame rod and is steady and blue Adjust pi...

Страница 30: ...21 5 28 5 V Check transformer 120 V supply correct as necessary TEMPERATURE 105 106 F Control ok RESISTANCE 0 OHMS SHORT CIRCUIT Check system for shorted wires or open circuits Replace sensor if neces...

Страница 31: ...er standard company warranties must be properly tagged with return parts tag completely filled in with the heater serial number model number etc and shipped to the Company freight prepaid If determine...

Страница 32: ...H 12 H 6 H 5 H 4 H 10 H 13 H 2 V 4 S 4 M 3 M 6 S 5 M 1 B 6 M 5 S 4 C 11 P 9 M 1 G 2 B 3 B 5 C 1 M 2 M 3 C 6 C 7 M 1 R 3 S 2 H HONEYWELL MILLIVOLT PILOT HONEYWELL IID PILOT Fig 8132 Fig 8133 9 P 1 P 1...

Страница 33: ...Combination Valve Nat IID 003900F Combination Valve Pro IID 004306F H HEAT EXCHANGER 1 H Heat Exchanger Assy Complete 004694F 2 H Header Tubed Kit 004695F 3 H Baffle Kit 004715F 14 H U G Assy 002546F...

Страница 34: ...t Mounting Bracket IID 004717F Pilot Tube 004078F 15 P Hi Tension Wire IID 002654B Hi Tension Wire w Pilot Electrode 007864F R REFRACTORY 1 R Refractory Block Kit 003544F S SHEETMETAL 1 S Jacket Top 0...

Страница 35: ...35...

Страница 36: ......

Отзывы: