12

To mains

connection

To range

Manifold

test point

pressure

1/8” NPT

Screw

Unscrew

Fig. 2.5

5.  Leak  Testing:

IMPORTANT: Leak  testing  of  the  appliance  shall  be  conducted  as  follows:

•  After  final  gas  connection  is  made,  turn  on  manual  gas  valve  and  test  all 

connections in gas supply piping and appliance for gas leaks with a soapy water 

solution.  During  this  test  all  appliance  gas  valves  have  to  be  closed.

•  In  order  to  avoid  property  damage  or  serious  personal  injury,  never  use  a  Iighted 

match.  If  a  leak  is  present,  tighten  joint  or  unscrew,  apply  more  joint  compound, 

tighten  again  and  retest  connection  for  leak.

b) Any conversion required must be performed by your dealer or a qualified licensed 

plumber  or  gas  service  company.  Please  provide  the  service  person  with  this 

manual before work is started on the range. (Gas conversions are the responsibility 

of  the  dealer  or  end  user.)

c)  This  range  can  be  used  with  NATURAL  or  LP/PROPANE  gas.  It  is  shipped  from 

the  factory  adjusted  for  use  with  NATURAL  gas.

d)  Manifold  pressure  should  be  checked  with  a  manometer;  NATURAL  gas  requires 

4.0”  W.C.P.  and  LP/PROPANE  requires  11.0”  W.C.P.  (see  side  figure).

  Incoming line pressure upstream from the regulator must be 1” W.C.P. higher than 

the  manifold  pressure  in  order  to  check  the  regulator. 

  The regulator used on this range can withstand a maximum input pressure of 1/2 

PSI  (14.0”  W.C.P).  If  the  line  pressure  is  in  excess  of  that  amount,  a  step-down 

regulator  will  be  required.

e)  The  appliance,  its  individual  shut-off  valve,  and  pressure  regulator  must  be 

disconnected  from  the  gas  supply  piping  system  during  any  pressure  testing  of 

that  system  at  pressures  in  excess  of  1/2  PSI  (3.5  kPa).

f)  The  appliance  must  be  isolated  from  the  gas  supply  piping  system  by  closing  its 

individual  manual  shut-off  valve  during  any  pressure  testing  of  the  gas  supply 

piping  system  at  test  pressure  equal  to  or  less  than  1/2  PSI  (3.5  kPa).

3.  Flexible  Connections:

If  local  codes  permit,  CSA  design-certified,  flexible  metal  appliance  connector  is 

recommended for connecting this range to the gas supply line. Do Not kink or damage 

the  flexible  connector  when  moving  the  range.  The  pressure  regulator  has  1/2"  NPT 

female  pipe  threads.You  will  need  to  determine  the  fittings  required,  depending  on 

the  size  of  your  gas  supply  line,  flexible  metal  connector  and  shutoff  valve.

4.  Rigid  Pipe  Connections:

If rigid pipe is used as a gas supply line, a combination of pipe fittings must be used 

to  obtain  an  in-line  connection  to  the  range.  All  strains  must  be  removed  from  the 

supply  and  fuel  lines  so  range  will  be  level  and  in  line.

•  Use  joint  compounds  and  gaskets    that    are  resistant  to  action  of  natural  or 

propane  gas  on  all  male  pipe  threads.

•  Do  not  over    tighten  gas  fitting  when  attaching  to  pressure  regulator.  Over 

tightening  may  crack  regulator. 

Содержание VEFSGG 244

Страница 1: ...ty Standard Title 24 CFR Part 3280 formerly the Federal Standard for Mobile Home Construction and Safety Title 24 HUD Part 280 or when such standard is not applicable the Standard for Manufactured Hom...

Страница 2: ...ighbor s phone Follow the gas supplier s instructions lf you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency...

Страница 3: ...f domestic household food and in not suitable for any none domestic application and therefore should not be used in a commercial environmement The appliance guarantee will be void if the appliance is...

Страница 4: ...lified installer service agent or the gas supplier IMPORTANT The use of suitable protective clothing gloves is recommended when handling installing of this appliance INSTALLATION INSTRUCTIONS TOOLS NE...

Страница 5: ...lation should comply with national and local codes 11 Air Supply and Ventilation The installer must refers to local national codes 12 Gas Manifold Pressure Natural gas 4 0 W C P LP Propane 11 0 W C P...

Страница 6: ...rfaces above 36 914 mm high There must be a minimum of 3 76 mm side clearance from the range to such combustible surfaces TO THE LEFT above the 36 914 mm high countertop or there must be a minimum of...

Страница 7: ...13 max 330 mm 914 mm 36 0 0 mm 20 min 500 mm 30 min 762 mm 457 mm 18 min PROXIMITY TO SIDE CABINETS Fig 1 3b ASSEMBLING THE BACKGUARD It is mandatory to install the backguard Assemble the backguard as...

Страница 8: ...o be attached as shown on figure below only rear right side it has to be fixed on the floor and on the rear wall by no 4 four suitable screws not supplied 2 After fixing the anti tip bracket slide ran...

Страница 9: ...cal gas supplier See page from 13 to 16 for L P gas conversion instructions 1 Manual Shut off Valve fig 2 1 A manual shut off valve must be installed in an accessible location in the gas line external...

Страница 10: ...ch Do not over tighten the connector Over tightening may crack regulator STEP 2 Assemble the 1 2 NPT connector pressure regulator group to the extension pipe interposing the gasket supplied The regula...

Страница 11: ...cal male 1 2 NPT female 1 2 NPT female WARNING check the right positioning of the gas regulator The arrow on the back of the gas regulator must be oriented toward the connector Arrow Extension pipe fe...

Страница 12: ...range can withstand a maximum input pressure of 1 2 PSI 14 0 W C P If the line pressure is in excess of that amount a step down regulator will be required e The appliance its individual shut off valve...

Страница 13: ...ers expressed in hundredths of a millimetre are marked on the body of each injector SETTING THE PRESSURE REGULATOR fig 2 6b The pressure regulator is accessible by removing the bottom drawer the press...

Страница 14: ...ratings the burner covers and the knobs Using a wrench substitute the nozzle injectors J figs 2 7 2 8 with those most suitable for the kind of gas for which it is to be used The burner are conceived i...

Страница 15: ...indicated by the arrow in fig 2 11 and replace it by the proper one according to the kind of gas Then replace the burner repeating the above steps in reverse order b Broil Burner Remove the burner by...

Страница 16: ...one only for the oven burner the broil is a fixed capacity by acting on the thermostat in the following way Turn on the burner by setting the thermostat knob on position Remove the knob and unscrew th...

Страница 17: ...personal safety this range must be grounded This range is equipped with a 3 prong ground plug To minimize possible shock hazard the cord must be plugged into a mating 3 prong ground type outlet ground...

Страница 18: ...18 WIRING DIAGRAM Fig 3 2...

Страница 19: ...19 19...

Страница 20: ...anscription errors in the present booklet The manufacturer re serves the right to make all modifications to its products deemed necessary for manufacture or commercial reasons at any moment and withou...

Отзывы: