11
Points to watch Part 2
:
Ensure
a clean run inside the pipework - leave no burrs or reducing shoulders.
With plastic
pipework, ensure that there is no reduction in the bore size and that there is adequate
support for horizontal runs to prevent sagging. Remember, ceiling voids can get very warm.
Avoid
running the drain line near or across hot water pipes.
Anti-syphon
precautions should be in line with general practice.
2.2.3 Overflow - Warning Pipe
The Vortex Is supplied with a 32mm (1 ¼“) tank connector which should be installed using
one of the predrilled holes in either the Left Hand side or Right Hand side of the water tank.
It is Important that any discharge from the warning pipe is visible.
Points to watch:
Ensure that the discharge from the overflow is visible.
Overflow arrangement must include an air break prior to a connection to a drain.
Waste must be run separately to soil stack or drain.
Do not reduce the diameter of the warning pipe at any point.
A standard warning pipe installation kit is available. Contact Vernacare Customer Care
Department for details.
2.3 Electrical
2.3.1 Single-phase electrical system (230v, 1 Ph, 50 HZ) (110v, 1 ph, 60 HZ)
The machine is supplied with a 3 metre length of 1.5mm flex to BS6500 which
shall be connected to:
• 230 Volt Machine – 16 Amp MCB to BS EN60898 Type C or fused 16 Amp to
IEC 60269.
• 110 Volt Machine – 16 Amp MCB to BS EN60898 Type C or fused 16 Amp to
IEC 60269.
Notes:
1.
All electrical installation to comply with current I.E.E. regulations.
2.
Mains supplies to be protected by:
1 Phase 230v ......... 16 Amp approved I.E.C. fuse.
1 Phase 110v…….. 16 Amp approved I.E.C. fuse.
3.
For all installations, an I.E.E. approved disconnection device
must
be fitted to the
final installation. This device shall be positioned in close proximity to the Vortex and
within easy reach of the operator & shall also be clearly marked as being the
disconnecting device for the machine.
Содержание Vortex
Страница 1: ...Issue No 2 ...
Страница 8: ...8 Figure 1 Dimensions of the Vernacare Vortex ...
Страница 20: ...20 7 Lid Arm Assembly Figure 5 Lid Arm Assembly ...
Страница 25: ...25 11 Water Distribution Figure 9 Water Distribution ...
Страница 27: ...27 12 Electrical Circuit Figure 10 Electrical Circuit ...
Страница 42: ...42 The latest version of this manual can be found at www vernacare com ...